Plan Review Details - Permit 06051259
Plan Review Stops For Permit 06051259
Review Stop AD ADDRESSING
Rev No 2 Status F Date 2006-12-12 Cont ID  
Sent By lursu Date 2006-12-12 Time 09:09 Rev Time 0.00
Received By lursu Date 2006-12-12 Time 09:08 Sent To  
Notes
2006-12-12 09:09:07UNITY OF TITLE IS REQUIRED IF THE BAYS ARE COMBINED.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-23 Cont ID  
Sent By lursu Date 2006-10-23 Time 14:10 Rev Time 0.00
Received By lursu Date 2006-10-23 Time 14:09 Sent To  
Notes
2006-06-20 00:00:00NEEDS EXT FOR SPACE?

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-20 Cont ID  
Sent By jwitmer Date 2006-06-20 Time 11:27 Rev Time 2.22
Received By jwitmer Date 2006-06-20 Time 11:27 Sent To  
Notes
2006-06-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06051259
 ADD: 5407 N HAVERHILL RD
 CONT: GABCO
 TEL: (561)644-1434
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) AS STATED BY OTHER REVIEWERS, THE
 LICENSE HOLDER GABCO REMODELING IS A
 GENERAL CONTRACTOR AND NOT LICENSED TO
 INSTALL COOLERS AND FREEZERS. THE PLANS
 ONLY INDICATE COOLER AND FREEZERS NO
 OTHER WORK IS SHOWN.
  
 2603.4.1.2 COOLER AND FREEZER WALLS.
 FOAM PLASTIC INSTALLED IN A MAXIMUM
 THICKNESS OF 10 INCHES (254 MM) IN
 COOLER AND FREEZER WALLS SHALL:
 1.HAVE A FLAME SPREAD INDEX OF 25
 OR LESS AND A SMOKE-DEVELOPED INDEX OF
 NOT MORE THAN 450, WHERE TESTED IN A
 MINIMUM 4 INCH (102 MM) THICKNESS.
 2.HAVE FLASH IGNITION AND
 SELF-IGNITION TEMPERATURES OF NOT LESS
 THAN 600?F AND 800?F (316?C AND 427?C),
 RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN
 0.032-INCH (0.8 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160
 INCH (0.4 MM) AT ANY POINT.
 4.BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM. WHERE THE COOLER OR
 FREEZER IS WITHIN A BUILDING, BOTH THE
 COOLER OR FREEZER AND THAT PART OF THE
 BUILDING IN WHICH IT IS LOCATED SHALL BE
 SPRINKLERED.
  
 2603.4.1.3 WALK-IN COOLERS.
 IN NONSPRINKLERED BUILDINGS, FOAM
 PLASTIC HAVING A THICKNESS THAT DOES NOT
 EXCEED 4 INCHES (102 MM) AND A MAXIMUM
 FLAME SPREAD INDEX OF 75 IS PERMITTED IN
 WALK-IN COOLERS OR FREEZER UNITS WHERE
 THE AGGREGATE FLOOR AREA DOES NOT EXCEED
 400 SQUARE FEET (37 M 2 ) AND THE FOAM
 PLASTIC IS COVERED BY A METAL FACING NOT
 LESS THAN 0.032-INCH-THICK (0.81 MM)
 ALUMINUM OR CORROSION-RESISTANT STEEL
 HAVING A MINIMUM BASE METAL THICKNESS OF
 0.016 INCH (0.41 MM). A THICKNESS OF UP
 TO 10 INCHES IS PERMITTED WHERE
 PROTECTED BY A THERMAL BARRIER.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-20 Cont ID  
Sent By dpalmer Date 2006-06-20 Time 08:58 Rev Time 0.00
Received By dpalmer Date 2006-06-19 Time 16:53 Sent To  
Notes
2006-06-20 00:00:00********* UNSAT ***************
  
 1A) NOTE: PLEASE SEE PERMIT APPLICATION
 IS SOMEWHAT CONFUSING. APPL MENTIONS
 "COOLER AND FREEZER" INSTALL, YET IT
 ALSO MENTIONS COOLER PERMIT UNDER
 SEPARATE PERMIT??
 PLEASE SEE PLANS ALSO MENTION COOLER AND
 FREEZER IS "NOT" INCLUDED??
 PLEASE SEE COMMENTS FROM BUILDING REVIEW
 AS SCOPE OF WORK DOES NOT SEEM TO ALLOW
 A PERRMIT UNDER THE "U" LICENSE.
 THE PRIME SOURCE OF WORK IS MECHANICAL
 AND IT SEEMS THIS SHOULD BE THE PRIME
 FROM THE MECHANICAL CONT.
  
 ** PLEASE KNOW, IN EITHER CASE THE
 COMPLETE VALUE FOR SCOPE PF WORK SHALL
 INCLUDE ALL LABOR AND
 MATERIALS,INCLUSIVE OF ANY MATERIALS OR
 EQUIPMENT WHICH MAY BE OWNER SUPPLIED.
 PLEASE SEE VALUE OF $15K IS WAY LOW FOR
 SCOPE ON PLANS.
 FBC 108.3 ADMIN SECT.
  
 1B) NOTE: PLANS INDICATE THESE WERE TWO
 TENANT SPACES WHICH ARE NOW BECOMING
 ONE, PLEASE SEE BUILDING REVIEW NOTES
 FOR STRUCTURAL SCOPE OF WORK NOT BEING
 SHOWN.
  
 2) NOTE: PLEASE SEE RISER FEEDERS DO NOT
 MEET MIN SIZES AS REQUIRED FOR THE NEW
 400A SERVICE BEING PROVIDED.
 PLEASE ALSO INCLUDE CONDUCTORS FROM
 GUTTER TO METER AND METER TO MAIN.
 PLEASE SEE 250.6,250.24B,310.16, 240.4,
 ETC
 215.5
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4) NOTE: PLEASE INDICATE OF TOTAL LOAD
 SHOWN ON SERVICE CALC IS INCLUDING NEW
 LOADS?
 PLEASE ALSO INDICATE THE CONTINOUS LOADS
 AND ANY LARGEST MOTOR LOADS AT 125%.
 215.3,230.42 ETC.
  
 5) NOTE: PLEASE SUBMIT ENERGY CODE
 COMPLIANCE FORMS FOR EQUIPMENT AND
 SPACE.THESE SAHLL BE SIGNED , DATED AND
 SEALED BY THE REPSONSIBLE ENGINEER OF
 RECORD.
 FBC 2004 CHAPTER 13
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By mcarsill Date 2006-06-19 Time 10:25 Rev Time 0.00
Received By mcarsill Date 2006-06-19 Time 10:13 Sent To  
Notes
2006-06-19 00:00:001. PLANS DO NOT INDICATE IF THE EXISTING
 TENANT SPACE IS EQUIPPED WITH FIRE
 SPRINKLER PROTECTION. IF EXISTING FIRE
 SPRINKLER PROTECTION IS PRESENT, THE NEW
 COOLERS SHALL BE FIRE SPRINKLER
 PROTECTED WITHIN AND ABOE THE NEW
 COOLERS WITH DRY PENDENT TYPE HEADS.
 SEPARATE PLANS AND PERMIT REQUIRED FOR
 FIRE SPRINKLER HEAD INSTALLATION.
  
 2. PLEASE EXPLAIN HOW INGRESS/EGRESS IS
 ACCOMPLISHED FROM THE COOLER AREA. IS
 ANY EXIT MARKINBG OR EMERGENCY LIGHTING
 PLANNED SHOULD LOSS OF POWER OCCUR
 WITHIN THE BUILDING OR TENANT SPACE.
 PLEASE EXPLAIN.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-12 Cont ID  
Sent By jleech Date 2006-07-02 Time 15:03 Rev Time 0.00
Received By jleech Date 2006-06-01 Time 14:33 Sent To  
Notes
2006-06-19 00:00:00TO "COMM" BD#15
2006-06-06 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-23 Cont ID  
Sent By tgordon Date 2006-06-23 Time 15:45 Rev Time 0.30
Received By tgordon Date 2006-06-23 Time 15:45 Sent To  
Notes
2006-06-23 00:00:00*** DENIED ***
 1) IF THE PERMIT IS FOR INSTALLING THE
 FREEZER AND COOLER BOXES ONLY THAN
 EXPLAIN THAT ON THE PERMIT APPLICATION.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR THE FREEZER & COOLER
 BOXES.
  
 3) PLEASE SEE THE BUILDING REVIEW NOTES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-02 Cont ID  
Sent By pschmitz Date 2006-07-02 Time 12:54 Rev Time 0.00
Received By pschmitz Date 2006-07-02 Time 12:54 Sent To  
Notes
2006-07-02 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 SEE OTHER PLAN REVIEW COMMENTS, THAT MAY
 EFFECT PLUMBING PLAN REVIEW.
  
  
 END OF COMMENTS, QUESTIONS 561-805-6692