Plan Review Details - Permit 06051212
Plan Review Stops For Permit 06051212
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-19 Cont ID  
Sent By lursu Date 2006-10-19 Time 08:28 Rev Time 0.00
Received By lursu Date 2006-10-19 Time 08:28 Sent To PC
Notes
2006-10-19 08:29:40USE EXT #0021 UNDER 777 S FLAGLER DR , PCN = 74 43 43
 22 30 001 0060
2006-05-30 00:00:00EXT REQUIRED FOR #1200

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-18 Cont ID  
Sent By jwitmer Date 2006-10-18 Time 10:45 Rev Time 0.00
Received By jwitmer Date 2006-10-18 Time 10:45 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-19 Cont ID  
Sent By jwitmer Date 2006-09-19 Time 10:47 Rev Time 0.77
Received By jwitmer Date 2006-09-19 Time 10:47 Sent To  
Notes
2006-09-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06051212
 ADD: 777 S FLAGLER# 1200
 CONT: HEDRICK BROTHERS
 TEL: (561)718-8341
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) ENGINEER CLIFFORD DIAZ:
 STAMPED SEAL PLEASE REVIEW FL
 ADMINISTRATIVE CODE REQUIREMENTS FOR
 SIZE AND EMBOSSING REQUIREMENTS OF SEAL.
 61G15-23.001 SEALS ACCEPTABLE TO THE
 BOARD. PURSUANT TO SECTION 471.025 F.F.,
 THE BOARD HEREBY ESTABLISHES AS
 INDICATED BELOW THE FORMS OF EMBOSSING
 IMPRESSION SEALS WHICH ARE ACCEPTABLE TO
 THE BOARD. SAID SEAL SHALL BE A MINIMUM
 OF 1 7/8" IN DIAMETER. ALL ENGINEERS
 MUST BE UTILIZING A SEAL AS ILLUSTRATED
 IN THIS RULE NO LATER THAN JANUARY
 1,2006.
  
 3) ENGINEER CLIFFORD DIAZ:
 61G15-23.002 SEALS SIGNATURE AND DATE
 SHALL BE AFFIXED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-20 Cont ID  
Sent By jwitmer Date 2006-06-20 Time 08:24 Rev Time 3.33
Received By jwitmer Date 2006-06-20 Time 08:24 Sent To  
Notes
2006-06-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06051212
 ADD: 777 S FLAGLER# 1200
 CONT: HEDRICK BROTHERS
 TEL: (561)718-8341
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) SEE ELECTRICAL COMMENTS 2-5 ON
 LICENSING LAWS FL S. S. 471/ 481 FOR
 ENGINGEERS & ARCHITECTS.
  
 3) SHEET A0.03
 3A) PROJECT CODE DATA IS MISSING MINIMUM
 BUILDING TYPE SEE TABLE 503.
  
 3B) APPLICABLE CODE DATA LIST THE 2004
 FBC BUT NO MENTION TO THE 2004 FBC
 EXISTING BUILDING CODE PROVIDE WHAT
 LEVEL OF RENOVATION IS TO TAKE PLACE.
  
 4) SHEET A7.00 DETAILS 7 & 8 BOTH REFER
 TO DETAIL 1/ OF SHEET 9.00 MISSING?
  
 5) BOTH OF THE DETAILS MENTIONED ABOVE
 INDICATE THE USE OF WOOD PANELS, PROVIDE
 ADDITIONAL INFORMATION. WOOD PANEL
 FINISHES PROVIDE DOCUMENTATION TO BEING
 TESTED TO ASTM E 84 OR NFPA 286.
 803.1/ 803.2.
  
 6) DETAIL# 5/ A8.20 INDICATES THE USE OF
  
 3/4" PANELING WITHOUT SOLID BACKING.
 SEE 803.4.2,803.4.2 SET-OUT
 CONSTRUCTION.
 WHERE WALLS AND CEILINGS ARE REQUIRED TO
 BE OF FIRE-RESISTANCE-RATED OR
 NONCOMBUSTIBLE CONSTRUCTION AND WALLS
 ARE SET OUT OR CEILINGS ARE DROPPED
 DISTANCES GREATER THAN SPECIFIED IN
 SECTION 803.4.1 , CLASS A FINISH
 MATERIALS SHALL BE USED EXCEPT WHERE
 INTERIOR FINISH MATERIALS ARE PROTECTED
 ON BOTH SIDES BY AN AUTOMATIC SPRINKLER
 SYSTEM OR ATTACHED TO NONCOMBUSTIBLE
 BACKING OR FURRING STRIPS INSTALLED AS
 SPECIFIED IN SECTION 803.4.1 . THE
 HANGERS AND ASSEMBLY MEMBERS OF SUCH
 DROPPED CEILINGS THAT ARE BELOW THE MAIN
 CEILING LINE SHALL BE OF NONCOMBUSTIBLE
 MATERIALS, EXCEPT THAT IN TYPE III AND V
 CONSTRUCTION, FIRE-RETARDANT-TREATED
 WOOD SHALL BE PERMITTED. THE
 CONSTRUCTION OF EACH SET-OUT WALL SHALL
 BE OF FIRE-RESISTANCE-RATED CONSTRUCTION
 AS REQUIRED ELSEWHERE IN THIS CODE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-12-31 Cont ID  
Sent By dpalmer Date 2006-12-31 Time 08:47 Rev Time 0.00
Received By dpalmer Date 2006-12-31 Time 08:30 Sent To PC
Notes
2006-12-31 08:49:14*** REV FOR ADDITION OF UPS SPECS AND OCCUPANCY TYPE
 DEVICES.VALUE INCREASED ALSO TO PRINT NEW CARD
 REV FOR RISER DID NOT COME BACK IN.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-11-28 Cont ID  
Sent By dpalmer Date 2006-11-28 Time 19:16 Rev Time 0.00
Received By dpalmer Date 2006-11-28 Time 18:30 Sent To  
Notes
2006-11-28 19:16:47**** UNSAT ***
  
 1) NOTE: PLEASE SEE MISSING LIGHTING CONTROL OVER RIDE
 DEVICE IN ROOM 1205.
 13-415.1.ABC.1.2 PLEASE ADJUST ON E-3
  
 2) NOTE: PLEASE SEE MISSING ONLY THE CANDELA LEVELS
 REQUIRED PER FBC 2004 11-4.28.1 AND 11-4.28.3(4) IS
 PERMITTED. THIS IS 75 MIN. PLEASE ADJUST NOTE ON E-5
  
 3) NOTE: PLEASE SEE COMPLETE UPS BACK UP SYSTEM NOT IN
 SCOPE OR PERMITTED UNDER THIS PERMIT IS NOW BEING SHOWN
 ON PLANS. THE INFORMATION FOR ALL EQUIPMENT AND VALUE
 FOR SCOPE OF WORK WAS PREVIOUSLY REQUESTED ON REVIEWS
 DATING BACK BEFORE PERMITTING AND THE DESIGNER OF
 RECORD REMOVED FROM PROJECT STATING THIS SCOPE OF WORK
 WOULD NOT BE DONE. PLEASE SEE NOW PLANS INDICATE THIS.
 PLEASE SUBMIT ALL THE PREVIOUSLY REQUESTED INFORMATION
 FOR SAID SYSTEM UNDER A SEPARATE PERMIT INCLUDING
 PERMIT APPLICATION, SIGNED DATED AND SEALED PLANS,
 ALONG WITH ALL MANUFACTURES SPEC/CUT SHEETS FOR ALL UPS
 EQUIPMENT.
 PLEASE KNOW THE VALUE FOR THIS SCOPE OF WORK SHALL BE
 BASED ON ALL LABOR AND MATERIALS WHETHER OR NOT
 EQUIPMENT IS OWNER SUPPLIED. PLEASE KNOW, ONCE A PERMIT
 FOR THIS SCOPE OF WORK IS ISSUED, THEN A REVISION
 INCLUDING THIS SCOPE OF WORK ON THE MAIN BUILDING
 PERMIT MAY BE SUBMITTED, HOWEVER NOTING THIS WORK UNDER
 A SEPARATE PERMIT.
  
 ** PLEASE SEE SHEETS E-3- E-5 WHICH WERE STAMPED AND
 WERE BEING REDLINED WERE STAMPED "VOID" UNTIL SCOPE
 ABOVE IS ADDRESSED.
 THIS WORK WAS TAKEN OUT OF THE ORIGINAL PLANS.
  
 FBC 106.1.2, 106.3.5.1.2
 NEC 110.3, 90.7, 645.11 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, COMMENTS OR IF ANY PART OF
 NOTES ABOVE ARE NOT UNDERSTOOD OR TYPED IN A MANNER
 WHICH IS NOT CLEAR, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE OR REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-19 Cont ID  
Sent By dpalmer Date 2006-10-19 Time 08:59 Rev Time 0.00
Received By dpalmer Date 2006-10-18 Time 21:05 Sent To AD
Notes
2006-10-19 08:59:52********* PROVSIO ********
  
  
 1) NOTE: PLEASE SEE CONFERENCE ROOMS 1201 AND 1203 DO
 NOT SEEM TO CONTAIN OVER-RIDE DEVICES FOR LIGHTING
 CONTROLS. PLEASE SEE LIGHTING RELAY SCHEDULE ALSO DOES
 NOT SEEM TO INDICATE THESE CIRCUITS.
  
 2) NOTE: PLEASE SEE REDLINE E-5 AS COMMENT FOR MINIMUM
 LEVELS FOR HORN/STROBES IS NOT STAED. THIS HAS NOW
 BECOME PART OF THE ELECTRICAL PLAN REVIEW PROCESS.
 PLEASE SEE FBC 200411-4.28., 11-4.28.2, FOR MIN
 ADUDIBLE LEVELS AND 11-4.28.3(4) FOR MIN LIGHTING
 CANDELA.
  
 ** PLEASE BE SURE TO SHOW THESE AND AND INCLUDE ON
 PLANS. SUBMIT REVISED PLANS ALONG WITH ANY OTHER
 REVISIONS BEFORE ANY ROUGHT ELECTRICLA INSPECTION.
 REVISED STAMPED PLANS MUST BE ON SITE FOR ELECTRICLA
 INSPECTOR.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PAN REVIEW
 561-805-6717
2006-10-18 21:05:33IN ELECTRICAL FOR REVIEW, REVIEW IN PROGRESS

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-20 Cont ID  
Sent By dpalmer Date 2006-08-20 Time 15:41 Rev Time 0.00
Received By dpalmer Date 2006-08-20 Time 15:00 Sent To  
Notes
2006-08-20 00:00:00**** UNSAT 2ND REVIEW *******
  
 ** PLEASE SEE SOME NOTE FROM PREVIOUS
 REVIEW AND SOME NEW NOTES ARE IN NEED OF
 ADDRESSING.
  
 1) NOTE: OK, AS SCOPE ON PLANS HAS
 DECREASED.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: NO, PLEASE SEE THE E-SHEETS
 WERE NOTE DATED WHEN SIGNED BY THE
 ENGINEER. PLEASE MAKE SURE ALL THE NEW
 REVISED SHEETS ARE DATED WHEN SIGNING
 AND SEALING SADI DOCUMENTS. FS 471.025,
 FAC 61G15-23.002.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THAT PLANS ARE NOTE DATED BY
 THE ARCHITECT OR ENGINEER AS REQUIRED
 UNDER FS 481.221, 471.025.
  
 5) NOTE: OK/NO, PLEASE SEE NEW ENERGY
 CALCUALTIONS WERE SUBMITTED HOWEVER
 THESE DO NOT CONTAIN A RAISED SEAL AS
 REQUIRED. PLEASE SEE A "RUBBER STAMP" IS
 PLACE IN LEIU OF THE REQUIRED RAISED
 SEASL. FAC 61G15-23.001
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE CORRECTED ENERGY
 CODE CALCULATIONS SHAL BE DESIGNED UNDER
 FBC 2004.
 PLEASE SEE THEY CURRENTY INDICATE THE
 2001 ICC.
 PLEASE BE SURE THEY ARE SIGNED , DATED
 AND SEALED BY THE ENGINEER OF RECORD.
 PLEASE SEE FBC CHAPTER 13 13-415.1.AB.1,
 13-415.2.ABC.1
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK, SEE NEW NOTES.
  
 11) NOTE: OK.
  
 12) NOTE: NO, THIS IS UNCLEAR STILL AS
 RISER NOW SHOWS A MAIN AHEAD OF THE FPL
 METER. PLEASE KNOW, PER FPL GUIDLINES
 FOR SERVICES, A MAIN IS REQUIRED ON THE
 LOAD SIDE OF METER. PLEASE KNOW, IF
 INDEED THIS IS INSTALLED AS SHOWN PLEASE
 BE SURE TO INDICATE A "FLOATING
 NEUTRAL".
 PLEASE SEE NEW NOTES FOR LOAD
 CALCUALTIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY RISER, IS THE
 "EXISTING TENANT" BEING SHOWN ON THE
 RISER ANOTHER TENANT SPACE OR IS THIS
 THE EXISTING TENANT RISER FOR THIS
 SPACE?
 AS SHOWN, THERE SEEMS TO BE AN EXISTING
 TENANT AND THIS NEW BUILD OUT IS NOTW
 TAPPING THE EXISTING METER AS SHOWN??
 THIS IS NOT CLEAR AT THIS TIME.
 215.5
  
 13) NOTE: NO/UNCLEAR SEE NOTE ABOVE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE EXISTING , OR
 NEW METER SIZE AND WHERE THE
 DISCONNECTING MEANS FOR SERVICE IS
 LOCATED AND THE OCP AND SIZE OF TENANT
 SERVICE DISCONNECT.
 CURRENTLY THIS IS NOT SHOWING ANY MAIN,
 AND A 42 CIRCUIT MLO FOR TENANTS
 DISCONNECTING MEANS.
 215.5,240.4,310.16,230.70 ETC
  
 14) NOTE: NO, PLEASE SEE ATTACHMENT ONLY
 BEING NTOED FOR THE 45K UNIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE TH ACTUAL
 ATTACHMENT FOR THE GROUNDING ELECTRODE
 OF THE NEW SEPARATELY DERIVED
 TRANSFORMERS.
 250.66, 250.30
 THE NOTE ON PLANS NEEDS TO BE SHOWN.
  
 15) NOTE: OK. SEE NEW NOTES.
  
  
 16) NOTE: OK.
  
  
 ** NEW NOTES**
  
 17) NOTE: PLEASE SSUBMIT COMPLETE LOAD
 CALCULATIONS FOR THE EXISTING 200A MIAN
 AND METER BEING SHOWN. (LOADS FOR "H",
 "L" AND "CR.
 220,
 FBC 106.1.2
  
 18) NOTE: PLEASE SEE IT ROOM DOES NOT
 INDICATE THE TRANSFORMER ON ROOM LAYOUT?
 PLEASE SEE RISER AND NOTE MENTIONS THIS
 IS A FLR MOUNTED UNIT.
 PLEASE SEE 110.26
  
 19) NOTE: PLEASE SEE PANEL "CP" IS BEING
 SHOWN AS 125A RATED AND FED FROM "RP"
 WHICH IS 150A MCB AND FEED-THRU LUGS.
 THEN PANEL "CP" WOULD ALSO BE REQUIRED
 TO BE 150A RATED, OR IF USING A TAPPED
 CONDUCTOR RULE, TERMINATE IN OCP WHICH
 LIMITS THE LOAD.
 240.21, 408.16, 240.3
 THIS WAS SHOWN AS THE SAME ON PREVIOUS
 PLANS, HOWEVER WAS NOT COMMENTED ON.
  
 20) NOTE: PLEASE SEE THE FOLLOWING AS
 THE FIRST COMMENT FROM BUILDING REVIEWER
 REQUESTED ALL OLD/VOIDED SHEETS BE
 REMOVED, YET PLEASE SEE ALL OLD
 ELECTRICAL SHEETS WERE LEFT IN SETS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By dpalmer Date 2006-06-19 Time 14:40 Rev Time 0.00
Received By dpalmer Date 2006-06-19 Time 08:48 Sent To  
Notes
2006-06-19 00:00:00IN ELEC FOR REVIEW.
 ********** UNSAT ***********
  
 1) NOTE: PLEASE SEE VALUE FOR SCOPE OF
 WORK SHALL INCLUDE ALL MATERIALS AND
 LABOR (EVEN IF ANY EQUIPMENT IS OWNER
 SUPPLIED).
 PLEASE SEE UPGRADE , AND SPECIALLY
 DESIGNED LIGHTING CONTROL SYSTEMS ETC
 SHALL ALOS BE INCLUDED IN VALUE IF SHOWN
 ON PLANS.
 ALL PERMANANTLY INSTALLED SYSTEMS.
 FBC ADMINISTRATIVE SECTION 108.3 AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON ALL TITLE BLOCKS ON PLANS.
 PLEASE SEE MISSING ARCHITECTURAL FIRM
 CERTIFICATE OF AUTHORIZATION #.
 PLEASE SEE MISSING ENGINEERING FIRM CA#.
 PLEASE SEE MISSING THE PRINTED NAME AND
 PRINTED LICENSE # OF SAID ARCHITECT.
 PLEASE SEE ALL OF THE ABOVE IS REQUIRED
 PER FLORIDA ADMINISTRATIVE CODES
 61G1-16.004, 61G15-23.002, FLORIDA
 STATUES 481.219, AND FS471.023
 ** THIS IS REQUIRED OF ALL TRADES AND
 FOR ALL SHEET WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.001 WHICH
 PASSED A RULING IN FEB 04 WHICH REQUIRED
 ALL ENGINEER'S SEALS TO CONTAIN THE
 WORDING OF "LICENSE" IN SEAL. PLEASE SEE
 THAT ALL SEALS WITH THE WORDING OF
 "CERTIFICATE" ARE NOT LONGER ACCEPTABLE.
  
 4) NOTE: PLEASE SEE THAT PLANS ARE NOT
 DATED BY THE ARCHITECT OR ENGINEER AS
 REQUIRED UNDER FS 481.221 AND 471.025
  
 5) NOTE: PLEASE SEE CORRECTED ENERGY
 CODE CALCULATIONS SHAL BE DESIGNED UNDER
 FBC 2004.
 PLEASE SEE THEY CURRENTY INDICATE THE
 2001 ICC.
 PLEASE BE SURE THEY ARE SIGNED , DATED
 AND SEALED BY THE ENGINEER OF RECORD.
 PLEASE SEE FBC CHAPTER 13 13-415.1.AB.1,
 13-415.2.ABC.1
  
 6) NOTE: PLEASE BE SURE PLANS INCLUDIGN
 ELECTRICAL REFLECT THE CURRNT CODE IN
 EFFECT FOR DESIGN.
 PLEASE SEE PLANS SHOULD INCLUDE THE
 FOLLOWING AT A MIN.
 2002 NFPA-70, (2005 SHOWN), 2003
 NFPA-101, NFPA-72 2002, NFPA-75 2003.
  
 7) NOTE: PLEASE CLARIFY LIGHTING
 CONTROLS FOR ALL ROOMS AS SOME COULD NOT
 BE LOCATED FOR THE OVER RIDE DEVICES AS
 REQUIRED.
 FBC 13-415.1.ABC.1.1, .1.2 ETC.
 1205,1202,1203,1201
 ** PLEASE SPECIFY TIME LIMITS ON
 DEVICES. CAN BE A "TYPICAL" NOT FOR NO
 MORE THAN 30 MINS FOR OS TYOE DEVICES
 AND 4HRS FOR TIMED TYPE DEVICES.
 ** PLEASE SEE A OSZ2 DEVICE IS SHOWN ON
 PLANS, HOWEVER COULD NOT LOCATED THIS ON
 LEGEND?
  
 8) NOTE:PLEASE SEE FIRE REVIEW
 COMMENTS AS TYPE OF "ELEC LOCK" FOR
 ACCESS CONTROLS NEED TO BE CLARIFIED.
 PLEASE SEE THAT IN THE EVENT OF POWER
 FAILURE, EGREES SHALL NOT IMPEDED.
  
 9) NOTE: PLEASE SEE THAT PLANS CLEARLY
 INDICATE THE FLR AND SUITE NUMBER IN
 TITLE BLOCK.
 FAC 61G1-16.004
  
 10) NOTE: PLEASE KNOW, AN "ALTERNATE"
 SYSTEM IS BEING SHOWN FOR THE IT ROOM.
 PLEASE KNOW, IF THIS SYSTEM IS BEING
 PROPOSED THEN IT SHOULD BE ON PLANS, IF
 NOT THIS SHOULD BE REMOVED. IF THIS
 SYSTEM IS GOING TO BE INSTALLED, PLEASE
 PROVIDE ALL MANUFACTURES SPCES/CUT
 SHEETS INDICATE A LISTING FROM A NRTL.
 215.5
  
 11) NOTE: PLEASE CLARIFY ROOM BEING
 INDICATE AS AN "IT" ROOM ON PLANS WHICH
 SHALL MEET NFPA-75 AND NEC 645.
 PLEASE CLARIFY IF THERE IS A RAISED
 FLOOR? IF SO, PLEASE INDICATE THE
 REQUIRMENTS/ SD UNDER FLR.
 8.2
  
 12) NOTE: PLEASE CLARIFY RISER, IS THE
 "EXISTING TENANT" BEING SHOWN ON THE
 RISER ANOTHER TENANT SPACE OR IS THIS
 THE EXISTING TENANT RISER FOR THIS
 SPACE?
 AS SHOWN, THERE SEEMS TO BE AN EXISTING
 TENANT AND THIS NEW BUILD OUT IS NOTW
 TAPPING THE EXISTING METER AS SHOWN??
 THIS IS NOT CLEAR AT THIS TIME.
 215.5
  
 13) NOTE: PLEASE PROVIDE EXISTING , OR
 NEW METER SIZE AND WHERE THE
 DISCONNECTING MEANS FOR SERVICE IS
 LOCATED AND THE OCP AND SIZE OF TENANT
 SERVICE DISCONNECT.
 CURRENTLY THIS IS NOT SHOWING ANY MAIN,
 AND A 42 CIRCUIT MLO FOR TENANTS
 DISCONNECTING MEANS.
 215.5,240.4,310.16,230.70 ETC
  
 14) NOTE: PLEASE INDICATE TH ACTUAL
 ATTACHMENT FOR THE GROUNDING ELECTRODE
 OF THE NEW SEPARATELY DERIVED
 TRANSFORMERS.
 250.66, 250.30
 THE NOTE ON PLANS NEEDS TO BE SHOWN.
  
 15) NOTE: PLEASE SEE MININUM CLEARENCES
 FOR TRANSFORMER AND PANELS DO NOT MEET
 110.26, 450.13,450.9 ETC
 PLEASE SEE PLANS MENTIONS THESE TO BE
 FLR MOUNTED WHICH WOULD PLACE THEM
 DIRECTLY INFRONT OF PANEL(S).
  
 16) NOTE: PLEASE VERIFY LOAD
 CALCULATIONS WHICH SHOULD INDICATE ALL
 CONTINOUS LOADS AT 125%.
 PLEASE SEE THE DEMAND IS SHOWN AS 1.25
 ON PANELS, BUT NOT ON MAIN PANEL AND THE
 CONTINUOUS LOADS DO NOT NOT SEEM TO HAVE
 BEEN CARRIED OVER.
 215.3,230.42
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS AND DESIGN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-08 Cont ID  
Sent By mawillia Date 2007-01-08 Time 17:20 Rev Time 0.00
Received By mawillia Date 2007-01-08 Time 17:20 Sent To  
Notes
2007-01-08 17:29:22*****APPROVED*****
  
  
  
 REVISED SPRINKLER PLAN (SP-1) SHEET STAMPED, SIGNED,
 AND DATED.FIRE ALARM/LIFE SAFETY PLAN (E-5) SHEET TO
 BE DONE UPON ELECTRICAL PLAN REVIEW COMMENT HAS BEEN
 SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-28 Cont ID  
Sent By mwennerg Date 2006-09-28 Time 10:30 Rev Time 0.00
Received By mwennerg Date 2006-09-28 Time 10:30 Sent To  
Notes
2006-09-28 00:00:00***PROVISO***
  
 PLANS HAVE BEEN APPROVED BUT NOT STAMPED
 UNTIL OTHER FS AND FAC REQUIREMENTS ARE
 MET. PREVIOUS FIRE REVIEW HAS BEEN
 ADDRESSED.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By mwennerg Date 2006-06-22 Time 15:23 Rev Time 0.00
Received By mwennerg Date 2006-06-22 Time 15:23 Sent To  
Notes
2006-06-22 00:00:00***DENIED***
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS
 REGARDING FAC REQUIREMENTS FOR TITLE
 BLOCKS.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL. PLEASE NOTE THAT THE WORD
 CHANGE FROM 'CERTIFICATE' TO 'LICENSE'
 IS REQUIRED FOR ANY SEALED DRAWINGS
 SUBMITTED FOR THESE SYSTEMS.
  
 3) FOR SPRINKLER REMODEL, NFPA 13, 2002
 EDITION SHALL BE REFERENCED.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 5) PLANS ILLUSTRATE ELECTRIC LOCKS AND
 CARD READERS. WHAT IMPACT WILL THIS
 ARRANGEMENT HAVE ON REQUIRED EXITING?
 DOORS SHALL COMPLY WITH NFPA 101, 2003
 EDITION SEC. 7.2.1.5.
  
 6) 2A-10B,C RATED FIRE EXTINGUISHERS
 SHALL BE MOUNTED AT DISTANCES NOT TO
 EXCEED 75' TRAVEL DISTANCE REQUIREMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 11:57 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 11:57 Sent To E
Notes
2006-12-27 11:57:25TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-16 Time 08:54 Rev Time 0.00
Received By adarroug Date 2006-11-16 Time 08:54 Sent To  
Notes
2006-11-27 16:39:08TO "COMM" BD#13
2006-11-16 08:55:11WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-05 Cont ID  
Sent By adarroug Date 2006-10-05 Time 15:46 Rev Time 0.00
Received By adarroug Date 2006-10-05 Time 15:46 Sent To  
Notes
2006-10-18 08:40:12TO "BOB"#3
2006-10-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 13:15 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 13:15 Sent To  
Notes
2006-08-17 00:00:00TO "COMM" BD#59
2006-08-16 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-07-19 Time 13:14 Rev Time 0.00
Received By adarroug Date 2006-05-30 Time 15:02 Sent To  
Notes
2006-06-15 00:00:00TO "COMM" BD#48
2006-06-01 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-11-28 Cont ID  
Sent By tgordon Date 2006-11-28 Time 14:25 Rev Time 0.30
Received By tgordon Date 2006-11-28 Time 14:25 Sent To  
Notes
2006-11-28 14:26:58REVISION TO MECH. PLANS PAGE M-1, M-2, M-3. AND M-4.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-18 Cont ID  
Sent By tgordon Date 2006-10-18 Time 12:32 Rev Time 0.30
Received By tgordon Date 2006-10-18 Time 12:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-17 Cont ID  
Sent By tgordon Date 2006-08-17 Time 16:30 Rev Time 0.40
Received By tgordon Date 2006-08-17 Time 16:30 Sent To  
Notes
2006-08-17 00:00:00*** DENIED ***
 1) THE ENGINEER CLIFFORD DIAS MUST SHOW
 THE DATE HE SIGNED AND SEALED THE PLANS,
 PER FAC 61G15-23.002 .
  
 2) SEE PAGE M-4 A/C UNIT SCHEDULE, NEED
 TO SHOW THE SEER OF THE A/C SYSTEMS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By tgordon Date 2006-07-19 Time 08:30 Rev Time 0.35
Received By tgordon Date 2006-07-19 Time 08:30 Sent To  
Notes
2006-07-19 00:00:00*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES #2, 3, 4,
 &5, PLEASE CORRECT
  
 2) PLEASE SHOW ON MECHANICAL PLANS HOW
 ROOF TOP CONDENSER UNIT "STANDS" AND
 CONDENSER UNITS ARE TO BE SECURED TO
 ROOF AND THAT THIS COMPLIES WITH 2004
 FBC 1606 WIND LOADS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-01-17 Cont ID  
Sent By kstevens Date 2007-01-17 Time 15:57 Rev Time 0.00
Received By kstevens Date 2007-01-17 Time 15:57 Sent To  
Notes
2007-01-17 15:58:57REVISION OK - SHT P-1

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-10-18 Cont ID  
Sent By kstevens Date 2006-10-18 Time 14:09 Rev Time 0.00
Received By kstevens Date 2006-10-18 Time 14:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-09-05 Cont ID  
Sent By kstevens Date 2006-09-05 Time 16:01 Rev Time 0.00
Received By kstevens Date 2006-09-05 Time 16:01 Sent To  
Notes
2006-09-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEW:
  
 1. SHT P-1 WATER PIPING SCHEMATIC: SEC
 604.9 A WATER HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK CLOSING VALVES ARE
 UTILIZED, AND INSTALLED PER MANUFACTUES
 SPECIFICATIONS.
 ****RESPONSE NOTED, BUT THE WATER HAMMER
 ARRESTOR REQUIRED FOR THE DISH WASHER IS
 LOCATED AT THE WATER HEATER, AND ON THE
 COLD WATER LINE. ARRESTOR SHALL BE
 LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" PER PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. THE
 ARRESTOR FOR THE ICE MAKER SHALL BE
 LOCATED NEAR THE REFRIG..
  
 **************NEW COMMENTS**************
  
 1B. THE DATE THAT THE SIGNATURE AND SEAL
 IS AFFIXED AS PROVIDED HERIN SHALL BE
 ENTERED ON SAID PLANS OR OTHER DOCUMENTS
 IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL ENGINEER. 61G15-23.002(1)
 AND FS 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-02 Cont ID  
Sent By pschmitz Date 2006-07-02 Time 11:08 Rev Time 0.00
Received By pschmitz Date 2006-07-02 Time 10:59 Sent To  
Notes
2006-07-02 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1) SHT P-1WATER PIPING SCHEMATIC:
 SEC 604.9 A WATER HAMMER ARRESTOR, SHALL
 BE INSTALLED WHERE QUICK CLOSING VALVES
 ARE UTILIZED AND INSTALLED PER
 MANFACTURES SPECIFICATIONS.
  
 2) SPECIFY TYPE OF AIR GAP FITTING FOR
 DISH WASHER WASTE.
  
 3) PLEASE SEE PLAN REVIEW COMMENTS BY
 OTHER PLAN REVIEWERS.
  
 END OF COMMENTS, QUESTIONS 561-805-6692