2006-06-02 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR PLAN REVIEW FOR A GAS PERMIT: |
| |
| 1. THE MASTER PERMIT #05120685 INDICATES |
| A PROPOSED GENERATOR. NOTE: GAS PERMIT |
| CAN NOT BE ISSUED UNTIL A GEN/RES PERMIT |
| APPLICATION HAS BEEN APPLIED FOR AND |
| APPROVED BY ZONING FOR GENERATOR |
| LOCATION. THE GENERATOR COULD BE |
| INDICATED ON THE DRAWING AS A FUTURE |
| GENERATOR, WITH PIPING AT OWN RISK. |
| 2. PLEASE INDICATE THE MATERIAL TYPE IN |
| THE DROP TO THE FIREPLACE, DRYER, AND |
| THE RUN TO THE BBQ. |
| 3. THE GAS REGULATOR INDICATED FOR THE |
| POOL IS UNDER SIZED. THE INDIVIDUAL LOAD |
| CAPACITY FOR A MAXITROL 325-5 IS ONLY |
| 300,000 BTU/HR, POOL HEATER INDICATED ON |
| DRAWING IS 400,000 BTU/HR, A MAXITROL |
| 325-7 IS REQUIRED. PLEASE SEE CORRECTED |
| DRAWING IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| 4. THE GAS REGULATOR INDICATED FOR THE |
| THE HOUSE IS THE WRONG PIPE SIZE, A |
| MAXITROL 325-3 IS 1/2", A 3/4", 325-5A |
| REGULATOR IS REQUIRED. PLEASE SEE |
| CORRECTED DRAWING IN RED INK FOR |
| REFERENCE FOR RESUBMITTAL. |
| 5. THE CSST TO THE WATER HEATER IS UNDER |
| SIZED PER TABLE 402.4(14) PLEASE SEE |
| ATTACHED TABLE AND CORRECTED DRAWING FOR |
| REFERENCE FOR RESUBMITTAL. |
| 6. PLEASE NOTE ON THE CORRECTED DRAWING |
| THE SYSTEMS BREAK DOWN BETWEEN 2LB AND |
| 12" W.C. WITH THE LONGEST LENGTH AND THE |
| TOTAL BTU'S INDICATED FOR EACH SYSTEM. |
| IN THE FUTURE IN ORDER TO EXPIDITE PLAN |
| REVIEW PLEASE HAVE THIS ON THE DRAWING. |
| 7. ONLY ONE CORRECTED DRAWING IN RED |
| INK. |
| |
| END OF COMMENTS: |
| |