Plan Review Details - Permit 06051149
Plan Review Stops For Permit 06051149
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-12-06 Cont ID  
Sent By amorse Date 2007-12-06 Time 17:43 Rev Time 0.00
Received By amorse Date 2007-12-06 Time 17:43 Sent To PC
Notes
2007-12-06 17:46:11 
  
 PASSED
  
 REVISION FOR BUILDING AND PLUMBING(SHEET A-1) IS
 APPROVED, ELECTRICAL SHEETS HAVE COMMENTS AND WILL NEED
 TO BE RESUBMITTED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-07-07 Cont ID  
Sent By amorse Date 2007-07-07 Time 10:03 Rev Time 0.00
Received By amorse Date 2007-07-07 Time 10:03 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-06-28 Cont ID  
Sent By amorse Date 2007-06-28 Time 18:09 Rev Time 0.00
Received By amorse Date 2007-06-28 Time 18:09 Sent To PC
Notes
2007-06-28 18:22:58 
 DENIED
  
 1)THE ATTIC ACCESS CANNOT BE INSTALLED IN THE FLAT
 ROOF AREA PLEASE REVISE.
  
 2)PLEASE PROVIDE THE FLORIDA STATEWIDE PRODUCT
 APPROVALS FOR 8" CASTCRETE LINTELS AND THE ROOF PRODUCT
 FOR THE FLAT ROOF. ASPHALT SHINGLES CANNOT BE USED ON
 ROOF SLOPES LESS THAN 2/12
  
 3)TRUSS ENGINEERING MUST BE SIGNED AND SEALED BY THE
 TRUSS MANUFACTURERS DESIGN PROFESSIONAL.
  
 4)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID
  
 5)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES
 ONLY FOR REFERENCE
 PLEASE DO NOT ATTACH PRODUCT APPROVALS TO DRAWING
 SETS.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-03-31 Cont ID  
Sent By amorse Date 2007-03-31 Time 12:44 Rev Time 0.00
Received By amorse Date 2007-03-31 Time 12:44 Sent To PC
Notes
2007-03-31 13:24:56 
  
 DENIED
  
 ****NOTE****
 THE FOLLOWING COMMENTS FROM THE 2ND BUILDING REVIEW
 WERE NOT ADDRESSED.
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 3) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. *****NOT SIGNED AND DATED BY
 OWNER/AGENT******
  
 6) THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*.
 ******REVIEWED AND APPROVED BY PERSON RESPONSIBLE FOR
 DRAWINGS*******
  
 7) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD.
  
 9) PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 ******THE
 DRAINAGE PROVISION IS TO SHOW POSITIVE DRAINAGE AWAY
 FROM NEW STRUCTURE AND ALSO SHOW THAT DOES NOT FLOW
 ONTO ADJOINING PROPERTY******
  
 ******NEW COMMENTS******
  
 1) THE PROVIDED ATTIC ACCESS IS THROUGH THE PROPOSED
 GIRDER BEAM PLEASE RELOCATE TO AN AREA THAT PROVIDES
 30" OF HEADROOM ABOVE ACCESS.
  
 2) UNDER THE EXISTING BUILDING CODE ADDITIONS ARE
 TREATED AS NEW CONSTRUCTION AND THE ACCESSIBILITY
 REQUIREMENTS OF ONE BATHROOM WITH A MIN 29" CLEAR
 OPENING WITH DOOR AT 90 DEGREES IS REQUIRE PER R322.1.1
 FBC
  
 3) UNDER THE EXISTING BUILDING CODE ADDITIONS, SMOKE
 ALARMS SHALL BE PROVIDED IN THE EXISTING PORTIONS OF
 THE BUILDING PER 904.2 FBC (EXISTING)
  
 4) THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED.
 PLEASE NOTE THAT I HAVE PRINTED THESE FOR YOUR WINDOWS
 AND PRECAST LINTELS
  
 5) PROVIDE NEW UPDATED MIAMI-DADE NOA'S FOR THE
 OAKRIDGE PRO 40 SHINGLES AS THIS NOA HAS EXPIRED. ALSO
 A NOA WILL BE REQUIRED FOR THE FLAT ROOF I WOULD
 SUGGEST THAT YOUR ROOFING CONTRACTOR SUPPLIES YOU WITH
 THIS PRODUCT APPROVAL AS THERE ARE THOUSANDS OF
 VARIATIONS AND THE EXACT ONE MUST BE CHOSEN AND
 INSTALLED TO PASS INSPECTION. PROVIDE PRODUCT APPROVAL
 FOR MULLION WHERE 2 OR MORE WINDOWS ARE JOINED TOGETHER
 AS IN MASTER BEDROOM.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-24 Cont ID  
Sent By tgordon Date 2007-03-01 Time 11:26 Rev Time 0.00
Received By alange Date 2006-10-24 Time 08:09 Sent To  
Notes
2006-10-24 08:14:57DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE WIL HAVE TO BE REVISED.
  
 A MINIMUM OF $112,596 IS REQUIRED JUST
 FOR THE ROOM ADDITION PLUS THE CARPORT
 ENCLOSURE.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 3.SIGN OWNER/AGENT ON ENERGY CALCS.
  
 4.PRODUCT APPROVALS REQUIRED FOR
 LINTELS.
 **SUBMIT TWO COMPLETE SETS OF ALL PRODUCT APPROVALS
 WITH THE APPROPRIATE STATE PRODUCT APPROVAL ATACHED
  
 5.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 7.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PRIOR TO INSTALLATIONPER 2004 FBC
 R-802.10.1
  
 8.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 9.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 IMPORTANT;
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-29 Cont ID  
Sent By alange Date 2006-06-29 Time 11:32 Rev Time 1.50
Received By alange Date 2006-06-29 Time 11:10 Sent To  
Notes
2006-06-29 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE WIL HAVE TO BE REVISED.
  
 A MINIMUM OF $112,596 IS REQUIRED JUST
 FOR THE ROOM ADDITION PLUS THE CARPORT
 ENCLOSURE.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 3.SIGN OWNER/AGENT ON ENERGY CALCS.
  
 4.PRODUCT APPROVALS REQUIRED FOR
 LINTELS AND OVEWRHEAD GARAGE DOOR.
 SUBMIT TWO COMPLETE SETS OF ALL PRODUCT APPROVALS.
  
 5.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 7.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 8.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 9.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 10.FOOTING DEPTH SHALL BE A MINIMUM OF
 12" BELOW UNDISTURBED SOIL R-403.1.4
  
 11.NOTE: SEPERATE PERMITS REQUIRED FOR
 ALL TRADES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2007-07-07 Cont ID  
Sent By   Date   Time 10:00 Rev Time 0.00
Received By amorse Date   Time 10:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-03-26 Cont ID  
Sent By dpalmer Date 2008-03-26 Time 11:42 Rev Time 0.00
Received By dpalmer Date 2008-03-26 Time 11:42 Sent To PC
Notes
2008-03-26 11:44:31TO VIF THE ACTUAL FEEDERS FROM METER/MAIN PANEL TO SUB
 PANEL. RISER SHOWS #3 AND PANEL SCHEDULE SHOWS #2.
 LOAD CALCULATIONS STATES SERVICE IS EXISTING WHEN
 SERVICE ON PLANS AND LOCATION AT JOB IS NEW. OLD
 METER/SERVICE IS BEING REMOVED.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-11-09 Cont ID  
Sent By dpalmer Date 2007-11-09 Time 10:50 Rev Time 0.00
Received By dpalmer Date 2007-11-09 Time 09:39 Sent To P
Notes
2007-11-09 10:50:31** DENIEDREVISION **
  
  
 1) NOTE: PLEASE SEE PLANS AND RISER CALL FOR A NEW
 120AMP DISCONNECT AND PANEL HOWEVER 120AMP IS NOT A
 RECOGNIZED STANDARD SIZE OF OVER CURRENT PROTECTION.
 PLEASE SEE 240.6.
  
 2) NOTE: PLEASE COMPLETE PLANS AND RISER WITH ALL
 MINIMUM REQUIRED CONDUCTORS.
 240.4, 310.16
  
 3) NOTE: PLEASE SEE THAT THE PLANS ARE REQUIRED TO BE
 SIGNED BY THE DESIGNER OF RECORD.
 FBC 106.1.2, 106.5
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTIONS SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-06-20 Cont ID  
Sent By dpalmer Date 2007-06-20 Time 14:24 Rev Time 0.00
Received By dpalmer Date 2007-06-20 Time 14:16 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-03-01 Cont ID  
Sent By dpalmer Date 2007-03-01 Time 09:16 Rev Time 0.00
Received By dpalmer Date 2007-03-01 Time 07:20 Sent To M
Notes
2007-03-01 09:17:04*** UNSAT 3RD REVIEW ***
  
 ** PLEASE SEE SCOPE OF WORK AND PLANS HAS NOW
 COMPLETELY CHANGED. PLEASE SEE COMMENTS.
  
 1) NOTE: PLEASE SEE PLANS NOW CALL FOR FAMILY ROOM AS
 EXISTING WHEREAS THE PREVIOUS TWO SETS OF PLANS
 SUBMITTED INDICATED THIS AREA AS A NEW PROPOSED
 ADDITION. PLEASE CLARIFY THIS AS REVIEW IS NOW CONFUSED
 OVER SEPARATE PLANS FOR NEW AND EXISTING.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE FBC R313 FOR NEW SMOKE ALARMS
 NEEDED. PLEASE ALSO SEE NOTE BELOW.
 **
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
  
 3) NOTE: PLEASE SEE RISER AND PANEL AND NOTES FOR PANEL
 DO NOT CORRELATE. SHOWS 200AMP MAIN BREAKER ON A 150AMP
 PANEL AND ALSO SHOWS A 150AMP RATED MAIN??
 106.1.2.
 NEC 230.70, 310.16, 240.4 ETC
  
 4) NOTE: PLEASE SEE THE SEALS ON PLANS ARE NOT CLEAR
 AND VISIBLE ON PLANS AS REQUIRED PER FAC 61G15-23.001,
 .002 AND FS 471.025.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE SEE MISSING RECEPTACLE(S) PER 210.52,
 REDLINED IN ADDITION.
  
 6) NOTE: PLEASE SEE MISSING COUNTER SPACE GFI PER
 210.8A6.
  
 7) NOTE: PLEASE SEE PLANS INDICATE A NEW STOVE, YET NO
 RECEPTACLE OUTLET IS BEING SHOWN FOR THIS? PLEASE ALSO
 SEE THAT THE REFRIGERATOR IS BEING SHOWN THE SAME WAY.
 PANEL SCHEDULE INDICATES BOTH OF THESE.
 PLEASE CORRELATE.
 106.1.2.
  
 8) NOTE:PLEASE SEE DISHWASHER AND DISPOSAL BEING
 SHOWN ON THE SAME SINGLE POLE CIRCUIT WHICH WILL PLACE
 LOAD ON THIS CIRCUIT WHICH EXCEEDS THAT OF THE RATING
 OF SAID BREAKER.
 PLEASE SEE 210.4.
 PLEASE SEE 240, 310.16, 422ETC
 PLEASE SEE FBC 106.3.5.4
  
 9) NOTE: PLEASE SEE PANEL SCHEDULE WHICH IS MISSING THE
 TWO REQUIRED SMALL APPLIANCE CIRCUITS AS SHOWN IN LOAD
 CALCULATIONS.
 210.52B1, 210.11C1, 220.16
  
 10) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION FOR
 THE AHU IS BEING SHOWN IS HIGH FOR A UNIT WHICH IS
 BEING SHOWN AS 7.5KW ON LOAD CALCULATIONS. PLEASE SEE
 THE MECHANICAL PLANS INDICATE THIS UNIT AS 10KW. IF
 INDEED THIS IS THE CASE, THEN REVISE THE LOAD
 CALCULATIONS AND NOT THE OVER CURRENT PROTECTION OF THE
 BREAKER AS SHOWN ON PANEL SCHEDULE.
 240.4, 310.16 ETC
 PLEASE SEE 220.31B FOR LOAD CALCULATIONS FOR ADDITIONS
 TO EXISTING DWELLINGS.
 PLEASE SEE THAT PLANS SEEM TO BE INDICATING A NEW CU,
 OR IS THIS RELOCATED. PLEASE SEE THE CLEARANCE REQUIRED
 FOR A/C EQUIPMENT ON THE ELECTRICAL PLANS DOES NOT SEEM
 TO BE MET FOR MINIMUM REQUIRED FOR CU EQUIPMENT. PLEASE
 SEE THE MECHANICAL PLANS ARE DIFFERENT.
 110.26 AND SEE MECHANICAL CODE FOR THEIR MINIMUM
 REQUIRED.
  
 11) NOTE: PLEASE SEE MISSING GFI FOR NEW CU. 210.63,
 210.8A2
  
 12) NOTE: PLEASE SEE OTHER CIRCUITS BEING SHOWN ON
 PANEL SCHEDULE WHICH ARE SHOWN AS BLANK OR OTHER 2-POLE
 BREAKERS AS SPARES??
 PLEASE CLARIFY.
 PLEASE INDICATE THE CIRCUITS FOR NEW WIRING AND ANY
 EXISTING AS SUCH.
 408.6, 240.4, 310.16,
 FBC 106.3.5.4
  
 13) NOTE: ** PLEASE KNOW THAT ONE SET OF EACH SET OF
 PLANS WILL BE RETAINED AND PLACED WITH PREVIOUS HELD
 PLANS FOR THE SAME DESIGNER OF RECORD AND FORWARDED TO
 THE STATE OF FLORIDA, AND FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS. PLEASE SEE FS 471.025(3)
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-15 Cont ID  
Sent By dpalmer Date 2006-10-15 Time 20:50 Rev Time 0.00
Received By dpalmer Date 2006-10-15 Time 20:35 Sent To P
Notes
2006-10-15 20:50:20********* UNSAT2ND REVIEW *************
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ALONG
 WIHT SOME NEW COMMENTS DUE TO THE PLANS SUBMITTED FOR
 THIS REVIEW.
  
  
 1)NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE:NO, SAME NOTE. PLEASE STILL MISSING
 DISCONNETC FOR WH AND MIN CLEARENACE FOR BOTH THE CU
 AND AHU.
  
 ** PREVIOUS REVIEW NOTE **
 ]PLEASE INCLUDE ALL MIN
 CLEARENCES FOR DISCONNECTS FOR CU, AHU
 AND WATER HEATER.
 110.26.
 PLEASE ALSO INCLUDE ALL DISCONNECTS.
 440.11,422.31 ETC.
  
 7) NOTE: NO, PLEASE STILL SEE MISSINGRECEPTS AS
 REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING RECEPTS
 REQ'D PER 210.52
  
 8) NOTE:OK.
  
 9) NOTE: OK, HOWEVER STILL SEE ZONING COMMENTS AS THIS
 MAY AFFECT PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE SUBSTANTIAL COMMENTS
 FROM ZONING WHICH WILL AFFECT PLANS AND
 DESIGN.
  
 10) NOTE: OK.
  
 ** NEW NOTE **
 11) NOTE: PLEASE SEE NOTE BELOW WHICH REQUESTED ALL
 OLD/VOIDED SHEETS TO BE REMOVED AND INSERT NEW SHEETS
 INTO COMPLETE SETS FOR REVIEW AND PROCESSING. PLEASE
 SEE THIS WAS NOT DONE. SHEETS ARE LOOSE AND NOT IN
 SETS. PLEASE KNOW, WHEN PLANS COME BACK AND THIS IS NOT
 DOWN, PLANS WILL BE REQUIRED TO BE PICKED UP BEFORE
 REVIEWS WILL COMMENCE.
  
 ** PREVIOUS NOTE**
 ** WHEN RESUBMITTING PLANS, PLEASE BE
 SURE TO COMPLETELT REMOVE ANY OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETED SETS FOR REVIEW
 AND STAMPING.
 PLEASE SUBMIT ONLY ONE COPY OF THE
 OLD/VOIDED SHEETS.
  
 12) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIEM, HOWEVER
 ELECTRICAL PLANS ARE BEING RETAINED.
  
 13) NOTE: PLEASE CORRELATE RISER AND PLANS AS PLANS
 SHOW A MAIN DISCONNECT AND RISER DOES NOT.
 FBC 106.1.2, 106.3.5.4
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By dpalmer Date 2006-06-13 Time 20:01 Rev Time 0.00
Received By dpalmer Date 2006-06-13 Time 19:38 Sent To P
Notes
2006-06-13 00:00:00********* UNSAT *************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6 (IF EXISTING SHOW, IF
 NOT EXISTING GFI, THEN GFI RECEPTS WILL
 BE REQUIRED IN KITCHEN AS PART OF A
 LEVEL 3 ALTERATION IN THE FBC EXISTING
 BUILDING CODE AND NEC.
  
 3) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 PLEASE SEE MISSING RECEPT(S) ETC.
 PLEASE SEE EXISTING BATH WILL BE
 REQUIRED TO EITHER CONTAIN A NEW 20A GFI
 CIRCUIT OR SHOW AS EXISTING.
  
 4) NOTE: PLEASE SUBMIT A PANEL SCHEDULE
 SHOWING ALL MIN REQUIRED CIRCUITS,
 CONDUCTOR AND OCP SIZES.
 240.4,310.16,215.5,408.4
  
 5) NOTE: PLEASE SHOW ALL SD'S IN
 EXISTING DWELLING. IF EXISTING, SHOW, IF
 NOT NEW SD'S WILL BE REQUIRED.
 R-313, NFPA-72 11.5.1.1., 11.8.3.5
 THIS IS A LEVEL-3 ALTERATION WHICH ALSO
 INCLUDES LEVELS 1 AND 2 AND R-313 AND
 ADDTIONS COVERED IN THE RESIDENTIAL 2004
 FBC.
  
 6) NOTE: PLEASE INCLUDE ALL MIN
 CLEARENCES FOR DISCONNECTS FOR CU, AHU
 AND WATER HEATER.
 110.26.
 PLEASE ALSO INCLUDE ALL DISCONNECTS.
 440.11,422.31 ETC.
  
 7) NOTE: PLEASE SEE MISSING RECEPTS
 REQ'D PER 210.52
  
 8) NOTE: PLEASE SEE MISSING REQUIRED LT
 FIXTURE OF SOME SORT AT LOCATIONS SHWON
 AS "J-BOX" . 210.70,NFPA-101 7.8,
 CHAPTER 24 RESIDENTIAL.
  
 9) NOTE: PLEASE SEE SUBSTANTIAL COMMENTS
 FROM ZONING WHICH WILL AFFECT PLANS AND
 DESIGN.
  
 10) NOTE: PLEASE SEE
 220.16,210.11,210.52F FOR MIN VA FOR WASHER/LAUNDRY
 CIRCUIT. 1500VA MIN.
  
 ** WHEN RESUBMITTING PLANS, PLEASE BE
 SURE TO COMPLETELT REMOVE ANY OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETED SETS FOR REVIEW
 AND STAMPING.
 PLEASE SUBMIT ONLY ONE COPY OF THE
 OLD/VOIDED SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-03-25 Cont ID  
Sent By adarroug Date 2008-03-25 Time 15:02 Rev Time 0.00
Received By adarroug Date 2008-03-25 Time 15:02 Sent To E
Notes
2008-03-25 15:02:22TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 14:50 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 14:50 Sent To E
Notes
2007-11-07 14:50:52TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-07-05 Cont ID  
Sent By adarroug Date 2007-07-05 Time 08:56 Rev Time 0.00
Received By adarroug Date 2007-07-05 Time 08:56 Sent To B
Notes
2007-07-05 08:57:10TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 14:39 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 14:39 Sent To E
Notes
2007-06-19 14:40:06TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-06-04 Cont ID  
Sent By eschneid Date 2007-06-19 Time 10:42 Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 11:43 Sent To Z
Notes
2007-06-04 11:43:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-27 Cont ID  
Sent By adarroug Date 2007-02-27 Time 17:54 Rev Time 0.00
Received By adarroug Date 2007-02-27 Time 17:54 Sent To E
Notes
2007-02-27 17:55:07TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-20 Cont ID  
Sent By adarroug Date 2007-02-20 Time 18:21 Rev Time 0.00
Received By adarroug Date 2007-02-20 Time 18:21 Sent To Z
Notes
2007-02-20 18:21:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-12 Cont ID  
Sent By adarroug Date 2006-10-12 Time 14:54 Rev Time 0.00
Received By adarroug Date 2006-10-12 Time 14:54 Sent To E
Notes
2006-10-12 14:55:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-06 Cont ID  
Sent By adarroug Date 2006-10-06 Time 11:27 Rev Time 0.00
Received By adarroug Date 2006-10-06 Time 11:27 Sent To Z
Notes
2006-10-06 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 10:26 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 10:26 Sent To E
Notes
2006-06-12 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-29 Cont ID  
Sent By alange Date 2006-06-29 Time 11:32 Rev Time 0.00
Received By alange Date 2006-05-27 Time 13:51 Sent To  
Notes
2006-05-27 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-06-21 Cont ID  
Sent By tgordon Date 2007-06-21 Time 07:54 Rev Time 0.30
Received By tgordon Date 2007-06-21 Time 07:54 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-01 Cont ID  
Sent By tgordon Date 2007-03-01 Time 11:27 Rev Time 0.45
Received By tgordon Date 2007-03-01 Time 11:27 Sent To P
Notes
2007-03-01 11:54:25*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) THE MECHANICAL PLANS NEED THE PREPARER'S SIGNATURE
 ON THEM. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3) THE MECHANICAL PLANS ARE SHOWING A 4" SUPPLY AIR
 DUCT TO THE MASTER BEDROOM WITH 196 CFM'S, THAT WOULD
 BE AT A VELOCITY OF 2250 FPM. MANUAL J CALCULATIONS
 STATE MAXIMUM VELOCITY TO BE 900 FPM, PLEASE CORRECT.
  
 4) MECHANICAL PLANS SHOW A 10" SUPPLY AIR DUCT TO THE
 MIXING BOX FOR THE MASTER SUITE, THIS WOULD REQUIRE A
 14" RETURN AIR TRANSFER DUCT. PLANS DO NOT STATE IF THE
 RETURN AIR DUCT IS A TRANSFER DUCT OR DIRECT DUCTED TO
 THE AHU, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-01 Cont ID  
Sent By tgordon Date 2006-06-16 Time 14:47 Rev Time 0.15
Received By tgordon Date 2006-06-16 Time 14:47 Sent To B
Notes
2006-06-16 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.
  
 *** SEE REVIEW 3-1-07 ***

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-11-28 Cont ID  
Sent By jleech Date 2007-11-28 Time 07:10 Rev Time 0.00
Received By jleech Date 2007-11-28 Time 07:10 Sent To B
Notes
2007-11-28 07:12:51REVISED MASTER BATH LAY OUT.

Review Stop P PLUMBING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2007-06-26 Time   Rev Time 0.00
Received By jleech Date 2007-06-26 Time 13:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-03-12 Cont ID  
Sent By jleech Date 2007-03-12 Time 07:42 Rev Time 0.00
Received By jleech Date 2007-03-12 Time 07:42 Sent To B
Notes
2007-03-12 07:58:15DENIED;
 1. AUTOMATIC CLOTHES WASHER; ALL SINGLE FAMILY HOMES
 ARE REQUIRED TO HAVE A HOOK UP FOR W/M SEE FBC-2004
 PLUMBING TABLE 403.1(R3).
 2. RISER DIAGRAM DOES NOT MATCH FLOOR PLAN.
 3. TWO WAY CLEANOUT REQUIRED WERE THE BUILD DRAIN MEETS
 THE BUILDING SEWER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-10-21 Cont ID  
Sent By jleech Date 2006-10-21 Time 13:58 Rev Time 0.00
Received By jleech Date 2006-10-21 Time 13:58 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-16 Cont ID  
Sent By jleech Date 2006-06-16 Time 09:19 Rev Time 0.00
Received By jleech Date 2006-06-16 Time 09:18 Sent To M
Notes
2006-06-16 00:00:00DENIED;
 1.RISER DIAGRAM; L.T. MISSING, W/M
 OUTLET TO BE 2" NOT 1 1/2", AND A
 CLEANOUT SHOULD BE AT 48" AFF.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2007-06-19 Cont ID  
Sent By eschneid Date 2007-06-15 Time 12:16 Rev Time 0.00
Received By eschneid Date 2007-06-19 Time 10:42 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2007-02-26 Cont ID  
Sent By eschneid Date 2007-02-26 Time 14:37 Rev Time 0.00
Received By eschneid Date 2007-02-26 Time 14:36 Sent To I
Notes
2007-02-26 14:39:05FAILED
  
 1) SHOW ALL DIMENSIONS FOR THE ADDITION ON THE SITE
 PLAN.
  
 2) SHOW THE AC UNIT AND ITS SETBACK DIMENSION ON THE
 SITE PLAN.
  
 3) SHOW THE WESTERN SETBACK FROM THE HOUSE TO THE
 PROPERTY LINE.
  
 4) PROVIDE A SURVEY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-10-11 Cont ID  
Sent By eschneid Date 2006-10-11 Time 18:03 Rev Time 0.00
Received By eschneid Date 2006-10-11 Time 17:55 Sent To  
Notes
2006-10-11 18:17:471) SHOW ALL DIMENSIONS FOR THE ADDITION ON THE SITE
 PLAN.
  
 2) SHOW THE AC UNIT AND ITS SETBACK DIMENSION ON THE
 SITE PLAN.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-10 Cont ID  
Sent By mmclean Date 2006-06-10 Time 09:45 Rev Time 0.00
Received By MMCLEAN Date 2006-06-10 Time 17:54 Sent To I
Notes
2006-06-10 00:00:00DENIED,
 1. THE PROPOSED WORK ADDITION & NEW
 CARPORT ENCLOSURE MUST MEET THE CURRENT
 SETBACK FOR SF7 (SEC 94-72)
 SIDE: FIVE FEET MINIMUM, 15FT TOTAL
 2. THE COMPLETE DEMO OF CARPORT FOR NEW
 CARPORT MUST MEET THE CURRENT ZONING
 CODE
 3. SITE PLANS (SCALE) SHOW THE SIDE
 SETBACK AT 4' AND 3'11", BUT SHOWS BELOW
 THE REQUIRED MIN., NEED TO CLARIFY.
  
  
 NOTE: THE PROPOSED ADDITION CANNOT
 PROJECT INTO THE 12' EASEMENT IN THE
 REAR OF PROPERTY.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720