Plan Review Stops For Permit 06051134 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2006-06-09 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2006-06-09 |
Time |
09:03 |
Rev Time |
0.40 |
Received By |
jgomez |
Date |
2006-06-09 |
Time |
09:03 |
Sent To |
PC |
|
Notes |
2006-06-09 00:00:00 | PERMIT UNDER "E". |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-05-31 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2006-05-31 |
Time |
16:54 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2006-05-31 |
Time |
16:54 |
Sent To |
|
|
Notes |
2006-05-31 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- ENGLERT SERIES 1300 METAL PANELS | | (DADE COUNTY NOA #03-0108.03): | | A) MAXIMUM DESIGN PRESSURES FOR THIS | | SYSTEM IS -60PSF. DESIGN PRESSURES FOR | | CORNER AND PERIMETER ZONES ARE HIGHER. | | SEE TABLE 1609.6B FBC 2004. NEED TO | | PROVIDE CALCULATIONS FOR INCREASED | | DESIGN PRESSURES AT THESE ZONES. ALL | | CALCULATIONS TO BE PERFORMED SIGNED AND | | SEALED BY ANY ONE OF THE PROFESSIONALS | | LISTED IN SYSTEM LIMITATION NUMBER 1. | | SEE PAGE 5 OF 6. | | B) CLEARLY IDENTIFY APPROVED ASSEMBLY | | TO BE INSTALLED. SEE ATTACHED COPY OF | | CITY POLICY FOR RE-ROOFING PERMITS AND | | INFORMATION REQUIRED TO BE SUBMITTED. | | C) SPECIFY MEAN ROOF HEIGHT. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
|