Plan Review Details - Permit 06051102
Plan Review Stops For Permit 06051102
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-23 Cont ID  
Sent By jgomez Date 2006-06-23 Time 08:44 Rev Time 0.40
Received By jgomez Date 2006-06-23 Time 08:44 Sent To  
Notes
2006-06-23 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- CONTRACTOR TO CLEARLY IDENTIFY
 SPECIFIC FLAT ROOF APPROVED ASSEMBLY TO
 BE INSTALLED AS REQUIRED BY CITY POLICY
 FOR RE-ROOFING PERMITS. SEE ATTACHED
 COPY OF THE POLICY.
  
 2- IF SELECTED INSULATED ASSEMBLY IS
 LIMITED BY GENERAL LIMITATION #7, THEN
 PROVIDE THE CALCULATIONS FOR ENHANCED
 UPLIFT PRESSURES AT CORNER AND PERIMETER
 AREAS. SEE TABLE 1609.6B FBC 2004 FOR
 CALCULATEDDESIGN PRESSURES AT CORNER
 AND PERIMETER AREAS. SEE ATTACHED COPY.
 CALCULATIONS TO BE DONE AS PER RAS 117.
 SEE LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED.
  
 3- PROVIDE COVER PAGE OF FLORIDA PRODUCT
 APPROVAL AS REQUIRED BY CITY POLICY FOR
 RE-ROOFING PERMITS. SEE ATTACHED COPY.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 5- CONTRACTOR'S VALUATION IS TOO LOW.
 OWES $546.61 FOR UPDATED VALUATION.
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-26 Cont ID  
Sent By jgomez Date 2006-05-26 Time 10:20 Rev Time 0.75
Received By jgomez Date 2006-05-26 Time 10:20 Sent To  
Notes
2006-05-26 00:00:00BUILDING REVIEW CHECKLIST:
 1- AS PER DBPR REGULATIONS GENERAL
 CONTRACTOR IS NOT ALLOWED TO DO FLAT
 ROOF. CONTACT DBPR FOR ADDITIONAL
 INFORMATION. NEED A ROOFING CONTRACTOR
 TO APPLY FOR THE PERMIT.
  
 2- CLARIFY SCOPE OF WORK. PERMIT
 APPLICATION SAYS SQUARE FOOTAGE 65. IS
 THIS 65SF OR 65 SQUARES. THIS IS A LARGE
 BUILDING AND NEED TO CONFIRM IF WORK IS
 TO RE-ROOF ENTIRE BUILDING OR JUST
 PATCHING A SMALL AREA. PERMIT FEES WILL
 BE ADJUSTED ACCORDINGLY.
 SPECIFY MEAN ROOF HEIGHT AS REQUIRED BY
 CITY POLICY FOR RE-ROOFING PERMITS. THIS
 BUILDING HAS SEVERAL STORIES AND NEED TO
 CONFIRM INFORMATION TO VERIFY COMPLIANCE
 WITH SECTION 1609 FBC 2004.
  
 3- PROVIDE COMPLETE AND SPECIFIC
 INFORMATION FOR FLAT ROOF SYSTEM
 APPROVED ASSEMBLY TO BE INSTALLED. SEE
 COPY OF CITY POLICY FOR RE-ROOF PERMITS
 AND PROVIDE ALL THE INFORMATION.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712