Plan Review Details - Permit 06051071
Plan Review Stops For Permit 06051071
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-12 Cont ID  
Sent By rnuquist Date 2006-06-12 Time 19:17 Rev Time 0.00
Received By rnuquist Date 2006-06-12 Time 19:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-07 Cont ID  
Sent By dpalmer Date 2006-07-07 Time 17:42 Rev Time 0.00
Received By dpalmer Date 2006-07-07 Time 17:42 Sent To PC
Notes
2006-07-07 00:00:00REDLINED MIN CLEARENCE FOR LIQUID
 COOLED UNITS PER MANUFACTURE CUT
 SHEETS/SPECS ATTACHED TO SETS.
 3' AIR COOLED, AND 5' FOR LIQUID COOLED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By dpalmer Date 2006-06-22 Time 20:54 Rev Time 0.00
Received By dpalmer Date 2006-06-22 Time 20:28 Sent To M
Notes
2006-06-22 00:00:00********** UNSAT ************
  
 1) NOTE: PLEASE SEE SITE SURVEY WHICH
 WILL REQUIRE ALL SETBACKS AND DIMENSIONS
 FROM DWELLING AND PROPERTY LINES. PLEASE
 SEE THAT THE CLEARENCS OF THE GEN CAN
 NOT BE VERIFIED AT THIS TIME.
 215.5
  
 2) NOTE: PLEASE PROVIDE A SERVICE
 ENTRANCE RATED ATS WHICH DISCONNECTS
 POWER FROM FPL AND GEN OR PROVIDE A
 DISCONNECITNG MEANS FOR FEEDERS FROM GEN
 ALSO.
 CAN NOT VEIRFY THE MEANS OF DISCONNECT
 FOR THE LINE SIDE POWER FROM FPL MEETING
 230.70,230.76,230.79.
 PLEASE SEE 225.31-225.39
 PLEASE SEE SPECS SUBMITTED WILL NOT BE
 ACCEPTABLE AS SHOWN.
  
 3) NOTE: PLEASE INDICATE LOCATION OF ALL
 EQUIPMENT ON A LAYOUT FOR HOUSE.
 215..
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE ALSO INDICATE THE RATING FOR ATS.
  
 5) NOTE: PLEASE SEE LOAD CALCULATIONS
 SUBMITTED SEEM TO BE MISSING MANY OTHER
 LOADS IN DWELLING.
 WASHER, LAUNDRY, DRYER, WATER HEATER,
 PUUMPS ETC.
 ANY GAS APPLIANCE SHALL BE INDICATED.
 PLEASE PROVIDE A COMPLETE PANEL SCHEDULE
 FOR INTENDED LOADS.
 PLEASE KNOW, IF LOADS EXCEED RATING OF
 GEN, LOAD SHEDDING MAY BE APPLIED,
 HOWEVER SHOW DETAIL.
 702.5,220,220.16,220.18, ETC.
 215.5
  
 6) NOTE: PLEASE SEE THAT THE RESPONSIBLE
 LICENSE CONTRACTOR SHALL PRINT NAME AND
 SIGN PLANS.
 FBC 106.2.1, 106.3.2.1 ADMIN SECT AS
 ADOPTED BY THE CITY OF WEST PALM BEACH
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 7) NOTE: PLEASE SEE THAT VALUE SHALL BE
 ADJUSTED TO INLCUDE ALL LABOR AND
 MATERIALS EVEN IF ANY EQUIPMENT ETC IS
 OWNER SUPPLIED.
 FBC 108.3 ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
 ** PLEASE KNOW, IF VALUE IS NOT
 ADJUSTED, ONE WILL BE CALCUALTE BY THIS
 OFFICE USING MARSHALL'S/ SWIFT GUIDE AS
 ADOPTED INTO THE FBC.
 ANY INCREASE IN VALUE SHALL BE DONE WHEN
 RE-SUBMITTIGN PLANS AND PERMIT
 APPLICATION.
  
 8) NOTE: PLEASE BE SURE THE MANUFACTURES
 SPECS / CUT SHEETS SHALL INDICATE THE
 MIN CLEARENCES SET BY THE MANUFACTURE.
 215.5
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
2006-06-08 00:00:00NEEDS TO UPDATE VALUE FOR TOTAL SCOPE.
 LOOK FOR REVIEW NOTES. FBC 108.3

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-06-23 Cont ID  
Sent By mperson Date 2006-06-23 Time 11:52 Rev Time 0.15
Received By mperson Date 2006-06-23 Time 11:52 Sent To PC
Notes
2006-06-23 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-07-07 Time 11:47 Rev Time 0.00
Received By adarroug Date 2006-07-07 Time 11:47 Sent To E
Notes
2006-07-07 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-01 Cont ID  
Sent By adarroug Date 2006-06-01 Time 16:48 Rev Time 0.00
Received By adarroug Date 2006-06-01 Time 16:48 Sent To E
Notes
2006-06-01 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-06-23 Time 11:45 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 14:40 Sent To  
Notes
2006-05-26 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-23 Cont ID  
Sent By tgordon Date 2006-06-23 Time 09:43 Rev Time 0.15
Received By tgordon Date 2006-06-23 Time 09:43 Sent To P
Notes
2006-06-23 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-23 Cont ID  
Sent By mperson Date 2006-06-23 Time 11:51 Rev Time 0.00
Received By mperson Date 2006-06-23 Time 11:51 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-05-27 Cont ID  
Sent By mmclean Date 2006-05-27 Time 21:22 Rev Time 0.00
Received By mmclean Date 2006-05-27 Time 21:22 Sent To I
Notes
2006-05-27 00:00:00NOTE: GENERATOR MUST ON ENCROACH 4FT
 INTO REQUIRED SETBACK