Plan Review Details - Permit 06051009
Plan Review Stops For Permit 06051009
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 13:48 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 13:48 Sent To M
Notes
2006-06-22 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-01 Cont ID  
Sent By tgordon Date 2006-06-01 Time 09:48 Rev Time 0.00
Received By tgordon Date 2006-05-26 Time 10:32 Sent To  
Notes
2006-05-26 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-23 Cont ID  
Sent By tgordon Date 2006-06-23 Time 09:14 Rev Time 0.30
Received By tgordon Date 2006-06-23 Time 09:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-01 Cont ID  
Sent By tgordon Date 2006-06-01 Time 09:19 Rev Time 0.45
Received By tgordon Date 2006-06-01 Time 09:19 Sent To  
Notes
2006-06-01 00:00:00*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS,
 PER 2004 FBC 13-600.0 .
  
 2) PLEASE AJUST THE VALUE ON THE PERMIT
 APPLICATION, THE VALUE NEEDS TO SHOW THE
 COST OF ALL MATERIALS AND LABOR (EVEN IF
 SUPPLYED BY OTHERS) OR THE CITY OF WPB
 WILL NEED TO AJUST THE VALUE.
  
 3) PLEASE ENTER A CORRECT PHONE NUMBER
 ON THE PERMIT APPLICATION, THE PHONE
 NUMBER FOR THE BELL SOUTH LONG DISTANCE
 SERVICE IS OF NO HELP, AND WILL ONLY
 DELAY INPROCESSING YOUR APPLICATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.