Plan Review Details - Permit 06050979
Plan Review Stops For Permit 06050979
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-12 Cont ID  
Sent By rnuquist Date 2006-06-12 Time 19:12 Rev Time 0.00
Received By rnuquist Date 2006-06-12 Time 19:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-10 Cont ID  
Sent By btrobaug Date 2006-07-10 Time 08:30 Rev Time 0.50
Received By btrobaug Date 2006-07-10 Time 08:21 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By btrobaug Date 2006-06-13 Time 15:01 Rev Time 0.50
Received By btrobaug Date 2006-06-13 Time 14:20 Sent To P
Notes
2006-06-13 00:00:00NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2. FBC AS
 AMENDED. THIS ARTICLE ALSO IS AN
 EXTRACTION FROM THE EXEMPTION IN CHAPTER
 471 OF THE FLORIDA STATUTES , 471.003,
 ALLOWING THE CONTRACTOR TO DRAW THEIR
 OWN PLANS.
  
 2} SHEET ? SHOWS "OUT TO FPL"TO OR FROM
 A DISCONNECT.PLEASE CLARIFY.
  
 3} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 4} PLEASE LOCATE ALL SERVICE
 EQUIPMENT ON A SITE PLAN, METER
 ENCLOSURE, DISCONNECTS, PANELS,GENERATOR
 AND TRANSFER SWITCH, SO THAT COMPLIANCE
 WITH ARTICLES 225 AND 230 CAN BE
 REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-06-14 Cont ID  
Sent By mperson Date 2006-06-14 Time 16:29 Rev Time 0.15
Received By mperson Date 2006-06-14 Time 16:29 Sent To M
Notes
2006-06-14 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-03 Cont ID  
Sent By adarroug Date 2006-07-03 Time 13:12 Rev Time 0.00
Received By adarroug Date 2006-07-03 Time 13:12 Sent To E
Notes
2006-07-03 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-26 Cont ID  
Sent By adarroug Date 2006-06-26 Time 15:25 Rev Time 0.00
Received By adarroug Date 2006-06-26 Time 15:25 Sent To Z
Notes
2006-06-26 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-01 Cont ID  
Sent By adarroug Date 2006-06-01 Time 16:37 Rev Time 0.00
Received By adarroug Date 2006-06-01 Time 16:37 Sent To E
Notes
2006-06-01 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-26 Cont ID  
Sent By adarroug Date 2006-06-19 Time 15:23 Rev Time 0.00
Received By adarroug Date 2006-05-24 Time 18:40 Sent To  
Notes
2006-05-24 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-06-19 Cont ID  
Sent By tgordon Date 2006-06-19 Time 09:45 Rev Time 0.05
Received By tgordon Date 2006-06-19 Time 09:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-14 Cont ID  
Sent By mperson Date 2006-06-14 Time 16:28 Rev Time 0.00
Received By mperson Date 2006-06-14 Time 16:28 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-06-30 Cont ID  
Sent By mmclean Date 2006-06-30 Time 16:29 Rev Time 0.00
Received By mmclean Date 2006-06-30 Time 16:29 Sent To I
Notes
2006-06-30 00:00:00NOTE:
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 1FT FROMSIDE PROPERTY
 LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-05-27 Cont ID  
Sent By mmclean Date 2006-05-27 Time 19:21 Rev Time 0.00
Received By mmclean Date 2006-05-27 Time 19:21 Sent To I
Notes
2006-05-27 00:00:00DENIED,
 1. MUST SHOW THE SIDE & REAR SETBACK OF
 THE PROPOSED GENERATOR ON TWO COPY OF
 CURRENT SURVEY.
 2. GENERATOR MUST NOT BE LOCATED IN THE
 UTITLITY EASMEN.
 3. MUST BE LOCATED IN THE REQUIRED REAR
 SETBACK OF PROPERTY
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720