Plan Review Details - Permit 06050976
Plan Review Stops For Permit 06050976
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-27 Cont ID  
Sent By dpalmer Date 2006-06-27 Time 10:33 Rev Time 0.00
Received By dpalmer Date 2006-06-27 Time 10:33 Sent To PC
Notes
2006-06-27 00:00:00** PERMIT REQUIRED FOR LIFT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-14 Cont ID  
Sent By btrobaug Date 2006-06-14 Time 10:39 Rev Time 0.50
Received By btrobaug Date 2006-06-14 Time 07:57 Sent To PC
Notes
2006-06-14 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A LOAD CALCULATION FOR THE
 PANEL SERVICING THE LIFT INCLUDING ALL
 ADDED LOADS.
  
 2} PROVIDE CONDUCTOR AND CONDUIT SIZE
 AND TYPE. INDICATE THE OCP FOR THE
 CONDUCTORS.
  
 3} PROVIDE CIRCUIT NUMBERS FOR THE NEW
 LOADS, AND ORIGINATING PANEL
 DESIGNATION.
  
 4} INDICATE THE RATING FOR THE EQUIPMENT
 DISCONNECT AND IF ITS FUSED OR
 NON-FUSED.
  
 5} THE TITLE BLOCK OF THE ARCHITECTURAL
 FIRM MUST CONTAIN THE CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED BY THE
 STATE PER 61G1-16.004(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 07:58 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 07:58 Sent To E
Notes
2006-06-22 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-14 Cont ID  
Sent By btrobaug Date 2006-06-14 Time 07:57 Rev Time 0.00
Received By btrobaug Date 2006-05-24 Time 16:07 Sent To E
Notes
2006-05-24 00:00:00TO "E" BOX