Plan Review Details - Permit 06050940
Plan Review Stops For Permit 06050940
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-15 Cont ID  
Sent By adarroug Date 2006-06-15 Time 11:56 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 11:56 Sent To M
Notes
2006-06-15 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-30 Cont ID  
Sent By tgordon Date 2006-05-30 Time 08:46 Rev Time 0.00
Received By tgordon Date 2006-05-24 Time 18:57 Sent To  
Notes
2006-05-24 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-20 Cont ID  
Sent By tgordon Date 2006-06-20 Time 09:25 Rev Time 0.30
Received By tgordon Date 2006-06-20 Time 09:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-30 Cont ID  
Sent By tgordon Date 2006-05-30 Time 08:33 Rev Time 0.30
Received By tgordon Date 2006-05-30 Time 08:33 Sent To  
Notes
2006-05-30 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 2) JOB ADDRESS NEEDS TO APPEAR ON PLANS.
  
 3) PLEASE PROVIDE COMBUSTION AIR FOR GAS
 CLOTHES DRYER, (OR IS IT A DIRECT VENT
 DRYER IF SO STATE THIS ON PLANS).
  
 4) AHU #1, TWO 10" RETURN AIR DUCTS DO
 NOT ALLOW ENOUGH RETURN AIR FOR A 3.5
 TON A/C SYSTEM, PLEASE CORRECT.
  
 5)CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.