Plan Review Details - Permit 06050939
Plan Review Stops For Permit 06050939
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-15 Cont ID  
Sent By adarroug Date 2006-06-15 Time 11:52 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 11:52 Sent To M
Notes
2006-06-15 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2006-06-15 Cont ID  
Sent By adarroug Date 2006-05-30 Time 11:51 Rev Time 0.00
Received By adarroug Date 2006-05-24 Time 18:58 Sent To  
Notes
2006-05-24 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-20 Cont ID  
Sent By tgordon Date 2006-06-20 Time 09:11 Rev Time 0.30
Received By tgordon Date 2006-06-20 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-30 Cont ID  
Sent By tgordon Date 2006-05-30 Time 08:48 Rev Time 0.30
Received By tgordon Date 2006-05-30 Time 08:48 Sent To  
Notes
2006-05-30 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 2) JOB ADDRESS NEEDS TO APPEAR ON PLANS.
  
 3) PLEASE PROVIDE COMBUSTION AIR FOR GAS
 CLOTHES DRYER, (OR IS IT A DIRECT VENT
 DRYER IF SO STATE THIS ON PLANS).
  
 4) RETURN AIR CAN NOT GET FROM RETURN
 AIR TRANSFER DUCT IN DEN TO AHU #1
 RETURN AIR GRILL, PLEASE CORRECT.
  
 5) RETURN AIR TRANSFER DUCT TO DEN IS TO
 SMALL, PLEASE SEE NOTE #7.
  
 6)CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
  
 7) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.