Plan Review Details - Permit 06050916
Plan Review Stops For Permit 06050916
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-14 Cont ID  
Sent By btrobaug Date 2006-07-14 Time 10:02 Rev Time 0.50
Received By btrobaug Date 2006-07-14 Time 09:44 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-15 Cont ID  
Sent By btrobaug Date 2006-06-15 Time 07:35 Rev Time 0.50
Received By btrobaug Date 2006-06-15 Time 07:00 Sent To PC
Notes
2006-06-15 00:00:00 
  
  
  
  
 NONCOMPLIANT
  
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW. SECOND REVIEW WITH SAME COMMENTS
 AS THE FIRST REVIEW.
  
 1}THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2. FBC AS
 AMENDED. THIS ARTICLE ALSO IS AN
 EXTRACTION FROM THE EXEMPTION IN CHAPTER
 471 OF THE FLORIDA STATUTES , 471.003,
 ALLOWING YOU TO DRAW YOUR OWN PLANS .
  
 AS PER INSTRUCTION FROM THE BUILDING
 OFFICIAL, THIS DEPARTMENT REQUIRES ALL
 PLANS MUST CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE DESIGNER OF RECORD AS
 THE STATUTE INTENDS. PLEASE COMPLY WITH
 THIS STATUTE ON ALL DOCUMENTS DRAWN BY
 YOU AND SUBMITTED FOR REVIEW. THERE IS
 NO "PRINTED" NAME ON RESUBMITTED
 DOCUMENTS.
  
 2} THE LOAD CALCULATION MUST BE PER 220,
 PART II, OR 220.31(B), FOR EXISTING
 DWELLINGS.
 PLEASE RECALCULATE AND INDICATE WHICH
 ARTICLE IS BEING APPLIED. THE
 APPLICATIION INDICATES 5KW HEAT. THE
 LOAD CALCULATION IS FOR 7.5KW HEAT. IS
 THE 5000 WATTS BEING ADDED TO THE 7500?
 IF SO USE 220.31(B), IF NOT, SEE EXAMPLE
 IN THE 2002 NEC HANDBOOK.
  
 3} THIS APPLICATION INDICATES WIRING AN
 A/C SYSTEM, BUT NO DRAWINGS FOR
 LOCATION,CONDUIT OR CONDUCTOR TYPE AND
 SIZE WHERE SUBMITTED, ALL OF WHICH ARE
 REQUIRED FOR REVIEW.
  
 THE CODE REFERENCE NEC 384 IS FROM THE
 1996 CODE. PLEASE UPDATE CODE SECTIONS
 IF USING THEM AS REFERENCE.
  
 PLEASE SEE FLORIDA STATUTE #
 553.80(2)(B), REGARDING THE REQUIRED FEE
 THAT MUST BE IMPOSED AFTER THE NEXT
 REVIEW FOR THE SAME COMMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-02 Cont ID  
Sent By btrobaug Date 2006-06-02 Time 08:46 Rev Time 0.50
Received By btrobaug Date 2006-06-02 Time 08:44 Sent To PC
Notes
2006-06-02 00:00:00 
 NONCOMPLIANT
  
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE
 DESIGN MUST PRINT AND SIGN THEIR NAME TO
 SAME PER 106.3.4.2. FBC AS AMENDED. THIS
 ARTICLE ALSO IS AN EXTRACTION FROM THE
 EXEMPTION IN CHAPTER 471 OF THE FLORIDA
 STATUTES , 471.003, ALLOWING YOU TO DRAW
 YOUR OWN PLANS .
  
 AS PER INSTRUCTION FROM THE BUILDING
 OFFICIAL, THIS DEPARTMENT REQUIRES ALL
 PLANS MUST CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE DESIGNER OF RECORD AS
 THE STATUTE INTENDS. PLEASE COMPLY WITH
 THIS STATUTE ON ALL DOCUMENTS DRAWN BY
 YOU AND SUBMITTED FOR REVIEW.
  
 PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.THIS IS ALSO A
 REQUIREMENT OF THIS DEPARTMENT.
  
 THE LOAD CALCULATION MUST BE PER 220,
 PART II, OR 220.31(B), FOR EXISTING
 DWELLINGS.
 PLEASE RECALCULATE AND INDICATE WHICH
 ARTICLE IS BEING APPLIED.
  
 THIS APPLICATION INDICATES WIRING AN A/C
 SYSTEM, BUT NO DRAWINGS FOR LOCATION,
 CONDUIT OR CONDUCTOR TYPE AND SIZE WHERE
 SUBMITTED, ALL OF WHICH ARE REQUIRED FOR
 REVIEW.
  
 THE CODE REFERENCE ?NEC 384? IS FROM THE
 1996 CODE. PLEASE UPDATE CODE SECTIONS
 IF USING THEM AS REFERENCE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-08 Cont ID  
Sent By adarroug Date 2006-07-08 Time 16:15 Rev Time 0.00
Received By adarroug Date 2006-07-08 Time 16:14 Sent To E
Notes
2006-07-08 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 16:37 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 16:37 Sent To E
Notes
2006-06-08 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-02 Cont ID  
Sent By btrobaug Date 2006-06-02 Time 08:46 Rev Time 0.00
Received By btrobaug Date 2006-05-25 Time 10:31 Sent To E
Notes
2006-05-25 00:00:00TO "E" BOX