Plan Review Details - Permit 06050874
Plan Review Stops For Permit 06050874
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-12-15 Cont ID  
Sent By shill Date 2006-12-15 Time 08:05 Rev Time 0.00
Received By shill Date 2006-12-15 Time 08:05 Sent To  
Notes
2006-12-15 08:09:05SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 4TH REVIEW, FROM PREVIOUS LIST:
  
 _XX_4.ANCHORING NOT COMPLIANT FOR
 THE DESIGN PRESSURES YOU HAVE DECLARED.
  
 THE SCHEDULE SPECIFIES 6", NOT COMPLIANT FOR -120PSF.
 85" SPAN SHOULD USE THE 8' CHART, NOT THE 7' CHART.IF
 YOU NEED ASSISTANCE IN PROPERLY COMPLETING AN
 INSTALLATION SCHEDULE, PLEASE SCHEDULE AN APPOINTMENT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-16 Cont ID  
Sent By shill Date 2006-08-16 Time 14:29 Rev Time 0.00
Received By shill Date 2006-08-16 Time 14:29 Sent To  
Notes
2006-08-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 3RD REVIEW, FROM PREVIOUS LIST:
  
 _XX_2.PROVIDE BUILDING HEIGHT ON THE
 PLAN.DESIGN PRESSURES FOR BUILDINGS
 OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7, FBC1609.1.1 AND MUST BE
 DONE BY AN ENGINEER. DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 2ND REVIEW - PAPERWORK SUBMITTED SHOWS A
 MEAN ROOF HEIGHT OF 120'.
  
 3RD REVIEW - ENGINEERING REQUIRED.
  
 _XX_4.ANCHORING NOT COMPLIANT FOR
 THE DESIGN PRESSURES YOU HAVE DECLARED.
  
 3RD REVIEW - YOU HAVE CIRCLED ANCHORING
 FOR -60PSF, THE COMPUTERIZED ENGINEERING
 SPECIFIES -108.6.
  
 DESIGN PRESSURES FOR BUILDINGS OVER 60'
 MUST BE SPECIFIED BY AN ENGINEER.TWO
 SIGNED, SEALED, DATED ORIGINALS
 REQUIRED.YOU CANNOT USE A COMPUTER
 PROGRAM TO DETERMINE DESIGN PRESSURES
 FOR BUILDINGS OVER 60' UNLESS IT IS
 SEALED BY AN ENGINEER.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-07 Cont ID  
Sent By shill Date 2006-07-07 Time 15:18 Rev Time 0.00
Received By shill Date 2006-07-07 Time 15:18 Sent To  
Notes
2006-07-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 2ND REVIEW, FROM PREVIOUS LIST:
  
  
  
 _XX_2.PROVIDE BUILDING HEIGHT ON THE
 PLAN.DESIGN PRESSURES FOR BUILDINGS
 OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7, FBC1609.1.1 AND MUST BE
 DONE BY AN ENGINEER. DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 2ND REVIEW - PAPERWORK SUBMITTED SHOWS A
 MEAN ROOF HEIGHT OF 120'.
  
 NEW COMMENT:
  
 _XX_3.PROVIDE A COPY OF THE CONDO
 ASSOCIATION APPROVAL.
  
 _XX_4.ANCHORING NOT COMPLIANT FOR
 THE DESIGN PRESSURES YOU HAVE DECLARED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By shill Date 2006-05-31 Time 11:38 Rev Time 0.00
Received By shill Date 2006-05-31 Time 11:38 Sent To  
Notes
2006-05-31 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED
 ITEMS APPLY
  
 ____1.A NOTICE OF COMMENCEMENT MUST
 BE FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED, FS713.13.
  
 _XX_2.PROVIDE BUILDING HEIGHT ON THE
 PLAN.DESIGN PRESSURES FOR BUILDINGS
 OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7, FBC1609.1.1 AND MUST BE
 DONE BY AN ENGINEER. DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 IN THE PAPERWORK SUBMITTED YOU HAVE
 PROVIDED A ROOF HEIGHT OF 35 FEET.
 ISN'T THIS BUILDING A HIGH RISE?PLEASE
 CONTACT ME BY TELEPHONE BEFORE
 RESUBMITTAL IF THE ROOF HEIGHT IS 35'.
  
 ____3.PROVIDE A COPY OF THE CONDO
 ASSOCIATION APPROVAL.
  
 ____4.COMPLETE THE ATTACHED
 INSTALLATION SCHEDULE OR PROVIDE
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.YOU MAY SHOW ANCHOR SPACING BY
 CIRCLING IT ON THE APPROPRIATE CHARTS ON
 THE PRODUCT APPROVAL.PLEASE USE INK
 RATHER THAN HIGHLIGHTER.
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72,
 WWW.FLORIDABUILDING.ORG.
  
 ____6.ON THE PRODUCT APPROVAL, MARK
 WHICH DETAILS APPLY TO THIS JOB.PLEASE
 USE INK RATHER THAN A HIGHLIGHTER.
  
 ____7.SHOW THE EMERGENCY MEANS OF
 ESCAPE, FBC R310.
  
 ____8.PROVIDE A FLOOR PLAN SHOWING
 WHERE THE SHUTTERS WILL BE INSTALLED AND
 PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 4 ABOVE.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-16 Time 10:58 Rev Time 0.00
Received By adarroug Date 2006-11-16 Time 10:58 Sent To B
Notes
2006-11-16 10:59:03TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 17:02 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 17:02 Sent To B
Notes
2006-08-08 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-25 Cont ID  
Sent By adarroug Date 2006-06-25 Time 18:13 Rev Time 0.00
Received By adarroug Date 2006-06-25 Time 18:13 Sent To B
Notes
2006-06-25 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-31 Cont ID  
Sent By shill Date 2006-05-31 Time 11:40 Rev Time 0.00
Received By shill Date 2006-05-23 Time 16:05 Sent To  
Notes