Plan Review Details - Permit 06050871
Plan Review Stops For Permit 06050871
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2006-10-18 Cont ID  
Sent By mperson Date 2006-10-18 Time 14:03 Rev Time 0.33
Received By mperson Date 2006-10-18 Time 14:03 Sent To PC
Notes
2006-10-18 14:05:54REVISION: CHANGED LOCATION OF GENERATOR WHICH CHANGES
 THE GAS PIPE. REFERENCE GEN/RES PERMIT #06031477.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2006-09-29 Cont ID  
Sent By mperson Date 2006-09-29 Time 08:50 Rev Time 0.45
Received By mperson Date 2006-09-29 Time 08:50 Sent To PC
Notes
2006-09-29 00:00:00******REVISION DENIED******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW ON THE SUBMITTED
 REVISION:
  
 1. SUBMIT TWO COPIES OF A SITE SURVEY
 PLAN INDICATING THE NEW PROPOSED
 LOCATION OF THE GENERATOR WITH THE
 INDICATION OF ALL DIMENSIONS FROM
 PROPERTY LINES AND DISTANCES FROM
 ADJACENT STRUCTURES.
 2. INDICATE ON THE SITE SURVEY PLAN THAT
 THE NEW LOCATION GENERATOR EXHAUST ARE
 NOT INSTALLED ANY CLOSER THAN TEN FEET
 FROM ANY OPENING INTO THE DWELLING
 STRUCTURE. THIS INCLUDES DOORS, WINDOWS,
 AND ATTIC VENTILATION OPENINGS.
 3. SUBMIT TWO COPIES OF MANUFACTURER
 INSTALLATION INSTRUCTIONS AND
 MANUFAFTURER SPECIFICATIONS INDICATING
 GENERATOR DIMENTIONS, BTU LOAD AND
 INSTALLATIONCLEARENCES FROM ADJACENT
 STRUCTURES.
 4. THE APPROVED GENERATOR FOR SAID
 ADDRESS IS A 37KW NATURAL GAS GENERATOR
 NOT A 38KW PLEASE CORRECT FOR
 RESUBMITTAL.
 5. THE APPROVED GENERATOR BTU LOAD IS
 570,000 NOT 623,000 PLEASE CORRECT FOR
 RESUBMITTAL.
 6. THE TOTAL BTU'S ARE INCORRECT ON THE
 DRAWING. THE CORRECT TOTAL BTU'S SHOULD
 BE 1,292,000 NOT 1,345,OOO PLEASE
 CORRECT FOR RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-06-07 Cont ID  
Sent By mperson Date 2006-06-07 Time 16:44 Rev Time 0.33
Received By mperson Date 2006-06-07 Time 16:43 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By mperson Date 2006-05-31 Time 15:45 Rev Time 0.45
Received By mperson Date 2006-05-31 Time 15:45 Sent To PC
Notes
2006-05-31 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING IS REQUIRED FOR PLAN
 REVIEW FOR A GAS PERMIT:
  
 1. PER CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL.(NOTE: REMOVE EXISTING
 SIGNATURES OR PROVISO FROM DRAWINGS FOR
 RESUBMITTAL. REMOVE FBC-2001 FROM
 DRAWINGS AND ADD FBC-2004 FUEL GAS TO
 RESUBMITTED DRAWINGS. CLEARLY INDICATE
 ON RESUBMITTED DRAWINGS THE GAS METER
 LOCATION. CLEARLY INDICATE EXISTING ON
 EXISTING SYSTEM PIPES.)
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, AND ALL PIPE SIZES. NOTE THE
 2"X1-1/4" RISER TO THE GENERATOR IS
 SIZED WRONG, IT SHOULD BE 2"X1-1/2"
 RISER TO THE GENERATOR, AND WHAT TYPE OF
 MATERIAL IS THE RISER TO THE GENERATOR,
 PLEASE CORRECT FOR RESUBMITTAL.
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).(NOTE: THE ENTIRE BTU LOAD
 NEEDS TO BE INDICATED ON DRAWING NOT
 JUST THE GENERATOR LOAD PLEASE
 CORRECT FOR RESUBMITTAL.)
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).(NOTE: THE
 LONGEST RUN IS INCORRECT, PLEASE CORRECT
 FOR RESUBMITTAL.)
 5. PLEASE SEE ATTACHED TABLES AND
 CORRECTED DRAWINGS IN RED INK FOR
 REFERENCE FOR RESUBMITTAL
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-16 Cont ID  
Sent By adarroug Date 2006-10-16 Time 13:52 Rev Time 0.00
Received By adarroug Date 2006-10-16 Time 13:52 Sent To G
Notes
2006-10-16 13:52:41TO "G" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-26 Cont ID  
Sent By adarroug Date 2006-09-26 Time 11:35 Rev Time 0.00
Received By adarroug Date 2006-09-26 Time 11:35 Sent To G
Notes
2006-09-26 00:00:00TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 10:02 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 10:02 Sent To G
Notes
2006-06-07 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-31 Cont ID  
Sent By mperson Date 2006-05-31 Time 16:19 Rev Time 0.00
Received By mperson Date 2006-05-24 Time 14:25 Sent To  
Notes
2006-05-24 00:00:00TO "G" BOX