Plan Review Stops For Permit 06050845 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
8 |
Status |
P |
Date |
2008-07-29 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-07-29 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-07-29 |
Time |
08:50 |
Sent To |
|
|
Notes |
2008-07-29 08:51:04 | RESTAMP SHEETS M2, M3, M5 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
F |
Date |
2008-07-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-07-21 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-07-21 |
Time |
10:30 |
Sent To |
|
|
Notes |
2008-07-21 10:32:11 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.SHEETS M2, M3, M5 DO NOT MATCH OUR RECORDS (WRONG | | REVISION).PLEASE RESUBMIT.ALL OTHER PLAN SHEETS | | HAVE BEEN STAMPED AND MAY BE USED IN THE FIELD. | | | | M2 AND M3 SHOULD INCLUDE REVISION 6. | | | | M5 HAD A REVISION 1 WHICH FOLLOWED REVISION 3.IT IS | | UNCLEAR WHY THE NUMBERING CHANGED; REGARDLESS, THE PLAN | | SUBMITTED FOR RESTAMP SHOULD EXACTLY MATCH THE PLAN ON | | FILE.SHEET M5 HAD A MAJOR LAYOUT REVISION AFTER THE | | REVISION 3 (AND WAS LABELED REVISION1).PLEASE NOTE | | THAT IT IS MORE CLEAR IF ALL REVISIONS FOLLOW | | SEQUENTIAL NUMBERING. | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
F |
Date |
2008-07-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-07-17 |
Time |
09:34 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-07-17 |
Time |
09:34 |
Sent To |
|
|
Notes |
2008-07-17 09:38:40 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.ROBERT F. PETERSON, PE SIGNED ALL SHEETS IN THE | | PERMIT DOCUMENTS.NOW ROGER MORSE HAS SIGNED AND | | SEALED THIS SHEETS.IS THERE A CHANGE IN DESIGN | | PROFESSIONAL?PLEASE SHOW COMPLIANCE WITH SUCCESSOR | | ENGINEER REQUIREMENTS OF FAC61G15 AND SUBMIT NEW SHEETS | | FOR OUR PERMIT SET AS A REVISION.THIS IS NOT A | | RESTAMP; A RESTAMP INVOLVES STAMPING IDENTICAL SHEETS. | | | | | | 2.SEE SHEET MARKED PLANS INDEX.OUR RECORD SET IS | | DATED 7/17/06, BUT THE SHEET SUBMITTED HAS A 9/29/06 | | REVISION.OTHER SHEETS MAY BE AFFECTED, PLEASE CHECK | | ALL!PLEASE CHECK ALL SHEETS AND SUBMIT THE IDENTICAL | | PLANS FOR RESTAMP OR SUBMIT AS A REVISION. | | | | 3.THE ARCHITECT'S SEAL IS TO INCLUDE THE DATE, | | FAC61G1-16, FS481. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2008-03-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-03-25 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-03-25 |
Time |
14:47 |
Sent To |
|
|
Notes |
2008-03-25 14:48:38 | SPLIT SLEEVE UL FIRE STOP SHOPS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2007-02-06 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-02-06 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-02-06 |
Time |
09:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2006-09-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-09-12 |
Time |
09:49 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-09-12 |
Time |
09:49 |
Sent To |
|
|
Notes |
2006-09-15 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC RFLORIDA BUILDING CODE 2004 | | RESIDENTIAL | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | THE CA NUMBER, 9666, ON THE PLAN IS NOT | | UNDER THE NAME OF MORSE ZEHNTER | | ASSOCIATES.TO PRACTICE ARCHITECTURE | | AND ENGINEERING THROUGH A COMPANY, | | BUSINESS LICENSE NUMBERS ARE REQUIRED | | FOR BOTH ARCHITECTURE AND ENGINEERING. | | | | THE STUCTURAL ENGINEER'S LETTER IS | | ENCLOSED IN THIS PACKAGE. | | | 2006-09-12 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC RFLORIDA BUILDING CODE 2004 | | RESIDENTIAL | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.)REVISED S1 STATES DESIGN AS | | ASCE7-98, SHOULD BE ASCE7-02 FBC 35. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-08-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-08-11 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-08-11 |
Time |
13:12 |
Sent To |
|
|
Notes |
2006-08-11 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.)PROVIDE ENERGY CALCS, FBC13. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-06-14 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-06-14 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-06-14 |
Time |
10:17 |
Sent To |
|
|
Notes |
2006-06-14 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.)PLANS ARE NOT SIGNED AND SEALED. | | | | 2.)INCLUDE GOVERNING CODE ON PLANS | | INDEX. | | | | 3.)DECLARE LEVEL OF ALTERATION FBC EB | | 3. | | | | 4.)CONSTRUCTION CLASS (PLANS INDEX) | | SHOULD INCLUDE TYPE A OR B.CONFIRM | | THAT YOU HAVE DECLARED THE CORRECT | | MINIMUM CONSTRUCTION TYPE, FBC 6. | | | | 5.)A-1 REFERS TO 713 JOINT SYSTEMS. | | PROVIDE A DETAIL. | | | | 6.)IF YOU ARE USING ALLOWABLE | | INCREASES AS INDICATED ON PLANS INDEX | | SHEET, PROVIDE CALCULATIONS.PROVIDE SF | | PER FLOOR. | | | | 7.)2ND FLOOR A2 SHOWS A JURY ROOM. | | COURTROOMS ARE A3 OCCUPANCY, 2 HOUR | | SEPARATION REQUIRED, FBC TABLE 302.3.2. | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2006-08-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-08-06 |
Time |
16:36 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-08-06 |
Time |
16:27 |
Sent To |
|
|
Notes |
2006-08-06 00:00:00 | ** RELINED PLANS** | | | | | | ANY COLOR CODING FOR 277/480V SHALL BE | | BROWN, PURPLE, YELLOW. | | | | ALL ELECTRICAL SHEETS STAMPED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-06-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-06-10 |
Time |
18:10 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-06-10 |
Time |
17:35 |
Sent To |
|
|
Notes |
2006-06-10 00:00:00 | ** UNSAT ** | | | | ** PLEASE SEE THIS WAS ORIGINALLY | | SUBMITTED UNDER THE 2001 FBC AND ONLY AS | | A "PLAN REVIEW". | | PLEASE SEEE THIS IS NOW SUBMITTED UNDER | | THE 2004 FBC. | | | | 1) NOTE: PLEASE SEE FBC CHAPTER 13 FOR | | MIN CALCULATIONS FOR RENOVATIONS TO | | EXISTING. | | PLEASE SEE PRESCRIPTIVE REQUIREMENTS | | AND FORM USE. PLEASE SEE THIS WILL ALSO | | BE IN THE MECHANICAL REVIEW NOTES. | | PLEASE SEE 13-413.1.ABC.1 FOR VOLTAGE | | DROP. | | PLEASE SEE A WORST CASE VOLTAGE DROP | | SHALL BE SHOWN ON PLANS. ONE FOR THE | | FEEDERS AND ONE FOR THE NEW BRANCH | | CIRCUITS. | | | | 2) NOTE: PLEASE SEE THE ONE LINE RISER | | DIAGRAM WHICH ONLY SHOWS ONE SET OF | | 500MCM'S TO EACH "AM" AND "BM". | | PLEASE SEE THIS SEEMS TO BE A MISPRINT | | AS ONE SETS TO EACH ONLY PROVIDES 400A'S | | WHEREAS THE MAINS ARE 800A. | | 310.16,240.4 ETC | | | | 3) NOTE: PLEASESHOW OR NOTE THAT THE | | CONTINUOUS LOADS AND LARGEST MOTOR LOADS | | ARE ALREADY FIGURED IN THE CALCULATIONS | | AT 125%. PLEASE REVISE CALCULATIONS TO | | INCLUDE THIS . | | 215.3, 230.42 | | | | PLEASE REMOVE OLD/VOIDED SHEETS AND ONLY | | INSERT NEW REVISED SHEETS INTO COMPLETE | | SETS FOR REVIEW AND STAMPING. | | ONE COPY OF ANY OF THE OLD REMOVED | | VOIDED SHEETS SHOULD BE SUBMITTED FOR | | REFERECNE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2006-06-19 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2006-06-19 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2006-06-19 |
Time |
10:50 |
Sent To |
|
|
Notes |
2006-06-19 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | 2. EXITS SHALL NOT BE BLOCKED BY | | CONSTRUCTION DEBRIS AND THEY SHALL | | REMAIN PASSABLE AT ALL TIMES. | | | | 3. INTERIOR FINISH ON WALLS AND CEILINGS | | IN EXIT ACCESS AND EXIT AREAS SHALL BE | | CLASS A. | | | | 4. ALL NEW ELECTRICAL WORK TO COMPLY | | WITH NFPA 70, THE NATIONAL ELECTRICAL | | CODE. | | | | 5. THE NEW DUCT SMOKE DETECTORS WHEN | | ACTIVATED SHALL ACTIVATE THE BUILDINGS | | FIRE ALARM SYSTEM. | | | | 6. ALL NEW FIRE DAMPERS AFTER | | INSTALLATION ARE TO BE TESTED TO ENSURE | | PROPER FUNCTION AND OPERATION. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER | | 804-4709 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
13 |
Status |
N |
Date |
2008-08-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-08-04 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-08-04 |
Time |
15:04 |
Sent To |
M |
|
Notes |
2008-08-04 15:05:04 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
12 |
Status |
N |
Date |
2008-07-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-23 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-23 |
Time |
13:36 |
Sent To |
M |
|
Notes |
2008-07-23 13:36:54 | TO "M" BOX/RESTAMP |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
11 |
Status |
N |
Date |
2008-07-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-18 |
Time |
16:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-18 |
Time |
16:30 |
Sent To |
B |
|
Notes |
2008-07-18 16:31:19 | TO "SHILL" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2008-07-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-11 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-11 |
Time |
11:31 |
Sent To |
B |
|
Notes |
2008-07-11 11:33:20 | TO "SHILL" DESK/RESTAMP |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2008-06-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-02 |
Time |
08:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-02 |
Time |
08:29 |
Sent To |
M |
|
Notes |
2008-06-02 08:29:49 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2008-05-08 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-08 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-08 |
Time |
14:28 |
Sent To |
M |
|
Notes |
2008-05-08 14:29:08 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2008-02-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-21 |
Time |
14:34 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-21 |
Time |
14:34 |
Sent To |
M |
|
Notes |
2008-02-21 14:35:04 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2007-10-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-15 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-15 |
Time |
09:30 |
Sent To |
M |
|
Notes |
2007-10-15 09:31:09 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2006-12-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-18 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-18 |
Time |
08:51 |
Sent To |
|
|
Notes |
2007-01-11 08:38:22 | TO "COMM" BD#45 | 2006-12-18 08:52:03 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2006-08-31 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-08-31 |
Time |
14:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-08-31 |
Time |
14:43 |
Sent To |
|
|
Notes |
2006-09-05 00:00:00 | TO "COMM" BD#33 | 2006-08-31 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-08-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-08-05 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-08-05 |
Time |
14:25 |
Sent To |
|
|
Notes |
2006-08-05 00:00:00 | TO COMM BOARD #31 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-07-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-07-22 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-07-22 |
Time |
15:48 |
Sent To |
|
|
Notes |
2006-07-22 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-07-21 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2006-06-24 |
Time |
09:16 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-06-24 |
Time |
09:16 |
Sent To |
|
|
Notes |
2006-06-06 00:00:00 | TO "COMM" BD#36 | 2006-05-22 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
10 |
Status |
P |
Date |
2008-08-22 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-08-22 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-08-21 |
Time |
14:06 |
Sent To |
PC |
|
Notes |
2008-08-22 08:22:55 | REV 7 PAGES M-1 AND M-2 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
9 |
Status |
P |
Date |
2008-06-03 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-06-03 |
Time |
08:30 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-06-03 |
Time |
08:11 |
Sent To |
PC |
|
Notes |
2008-06-03 08:30:00 | PAGES M-2 AND M-3 REVISION #6 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
8 |
Status |
F |
Date |
2008-05-27 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-05-27 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-05-27 |
Time |
14:31 |
Sent To |
PC |
|
Notes |
2008-05-27 14:39:34 | PG M-2 REVISION 5 | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | COMMENTS: | | | | 1. IN THIS REVISION, RETURN AIR HAS BEEN REMOVED AN | | OFFICE IN QUADRANT 2A. BALANCED RETURN IS REQUIRED IN | | THIS AREA IN ACCORDANCE WITH FBCM 601.4. SHOW HOW | | BALANCED AIR IS TO BE ACHIEVED. | | | | 2. THE SUPPLY BRANCH FEEDING VAV 05 IN THE SAME OFFICE | | IS MISSING SIZE ON THE PLANS. PLEASE PROVIDE MISSING | | INFORMATION ON PLANS. FBCM 603.1 AND FBCB 106.1.1. | | | | NOTE: PREVIOUS REVISION 5 ON PAGE M-3 WAS REVIEWED WITH | | A PROVISO REGARDING AN OFFICE WHICH WAS MISSING A | | RETURN. PLEASE ADDRESS THE PROVISO ON M-3 WHEN | | RESUBMITTING PAGE M-2. WORK SHALL BE INSTALLED IN | | ACCORDANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS, | | AND ANY CHANGES MADE DURING CONSTRUCTION THAT ARE NOT | | IN COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS | | SHALL BE RESUBMITTED FOR APPROVAL AS AN AMENDED SET OF | | CONSTRUCTION DOCUMENTS IN ACCORDANCE WITH FBCM 106.4. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
7 |
Status |
P |
Date |
2008-05-27 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-05-27 |
Time |
14:31 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-05-27 |
Time |
14:30 |
Sent To |
PC |
|
Notes |
2008-05-27 14:31:10 | PG M-1 REVISION 5 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2008-03-25 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-03-25 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-03-25 |
Time |
14:17 |
Sent To |
PC |
|
Notes |
2008-03-25 15:01:56 | PROVISO: PG M-3 OFFICE 1 HAS NO RETURN. BALANCED RETURN | | IS REQUIRED IN ACCORDANCE WITH FBCM 601.4. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2007-10-22 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-10-20 |
Time |
20:25 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-10-20 |
Time |
19:48 |
Sent To |
PC |
|
Notes |
2007-10-20 20:25:03 | REVISION PG M-5 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2007-02-05 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-02-05 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-02-01 |
Time |
13:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2006-09-28 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2006-09-28 |
Time |
17:04 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2006-09-28 |
Time |
17:04 |
Sent To |
|
|
Notes |
2006-09-28 00:00:00 | ----------------DENIED------------------ | | 1. PAGE M2 QUADRANT 2B: MISSING FIRE | | DAMPER ON 8" ROUND DUCT FROM TO 05 VAV | | IN 'RECEPTION' TO 'OFFICE' 250 CFM DROP. | | | | 2. PAGE M10 DETAIL #2: PLEASE INDICATE | | OF WHAT MATERIAL THE ROOF DUCT STANDS | | ARE TO BE CONSTRUCTED, AS WELL AS DETAIL | | FOR FASTENING STANDS TO ROOF IN ORDER TO | | MEET WIND-LOAD REQUIREMENTS. | | | | 3. PAGE M10 DETAIL #1B: ALL UL 155 | | LISTED FIRE DAMPERS MUST BE INSTALLED | | ACCORDING TO MANUFACTURER'S INSTALLATION | | INSTRUCTIONS. PROVIDE THEM EITHER ON THE | | PLAN OR SEPERATELY. | | | | RONALD J REGUEIRO | | 561.805.6734 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2006-08-18 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-08-18 |
Time |
15:26 |
Rev Time |
1.30 |
Received By |
tgordon |
Date |
2006-08-18 |
Time |
15:26 |
Sent To |
|
|
Notes |
2006-08-18 00:00:00 | *** DENIED *** | | 1) SEE PAGE M-2 NEED FIRE DAMPERS AT 5" | | AND 4" DUCTS TO OFFICE, SEE HIGH LIGHT | | (JURY ROOM ON ELECT. PG. E-3). | | | | 2) SEE PAGE M-4 MANY DUCTS AND GRILLS | | ARE NOT SIZED, SEE HIGH LIGHT. | | | | 3) SEE PAGE S-1 WIND LOAD FBC 2001, WE | | ARE PRESENTLY USING 2004 FBC, PLEASE | | CORRECT. | | | | 5) SHOW ON MECHANICAL PLANS LOCATION OF | | CONDENSATE LINES AND WERE THEY WILL | | TERMINATE. | | | | 6) PLEASE SUBMIT ENERGY CALCULATIONS, | | PER 2004 FBC/EB 611.1 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-06-24 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2006-06-24 |
Time |
08:44 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2006-06-24 |
Time |
08:44 |
Sent To |
|
|
Notes |
2006-06-24 00:00:00 | PLAN DENIED | | 1) MISSING FIRE DAMPER IN CONFERENCE | | ROOM PAGE M-1. | | 2) MISSING FIRE DAMPER IN JURY ROOM PAGE | | M-2 | | 3) PLEASE PROVIDE ON THE PLANS ALL DUCT | | AND GRILL SIZE FOR QUADRANT 4-B PAGE M-4 | | 4) PLEASE REFER TO SECTION 606.4.1 | | SUPREVISON 2004 FBC(M) | | 5) PLEASE REFER TO SECTION 307.2.3 | | AUXILIARY AND SECONDARY DRAIN SYSTEM. | | 2004 FBC(M). | | 6) PLEASE REFER TO SECTION 307.2.1 | | CONDENSATE DISPOSIAL 2004 FBC(M). | | 7) PLEASE PROVIDE MANUFACTURERS | | INSTALLATION INSTRUCTIONS ON NOTE # 2 | | PAGE M-10 | | 8) PLEASE PROVIDE A DETAIL FOR A/C CURB | | TIE DOWN TO ROOF ON PLANS. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|