Plan Review Details - Permit 06050845
Plan Review Stops For Permit 06050845
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-07-29 Cont ID  
Sent By shill Date 2008-07-29 Time 08:50 Rev Time 0.00
Received By shill Date 2008-07-29 Time 08:50 Sent To  
Notes
2008-07-29 08:51:04RESTAMP SHEETS M2, M3, M5

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-07-21 Cont ID  
Sent By shill Date 2008-07-21 Time 10:30 Rev Time 0.00
Received By shill Date 2008-07-21 Time 10:30 Sent To  
Notes
2008-07-21 10:32:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.SHEETS M2, M3, M5 DO NOT MATCH OUR RECORDS (WRONG
 REVISION).PLEASE RESUBMIT.ALL OTHER PLAN SHEETS
 HAVE BEEN STAMPED AND MAY BE USED IN THE FIELD.
  
 M2 AND M3 SHOULD INCLUDE REVISION 6.
  
 M5 HAD A REVISION 1 WHICH FOLLOWED REVISION 3.IT IS
 UNCLEAR WHY THE NUMBERING CHANGED; REGARDLESS, THE PLAN
 SUBMITTED FOR RESTAMP SHOULD EXACTLY MATCH THE PLAN ON
 FILE.SHEET M5 HAD A MAJOR LAYOUT REVISION AFTER THE
 REVISION 3 (AND WAS LABELED REVISION1).PLEASE NOTE
 THAT IT IS MORE CLEAR IF ALL REVISIONS FOLLOW
 SEQUENTIAL NUMBERING.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-07-17 Cont ID  
Sent By shill Date 2008-07-17 Time 09:34 Rev Time 0.00
Received By shill Date 2008-07-17 Time 09:34 Sent To  
Notes
2008-07-17 09:38:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.ROBERT F. PETERSON, PE SIGNED ALL SHEETS IN THE
 PERMIT DOCUMENTS.NOW ROGER MORSE HAS SIGNED AND
 SEALED THIS SHEETS.IS THERE A CHANGE IN DESIGN
 PROFESSIONAL?PLEASE SHOW COMPLIANCE WITH SUCCESSOR
 ENGINEER REQUIREMENTS OF FAC61G15 AND SUBMIT NEW SHEETS
 FOR OUR PERMIT SET AS A REVISION.THIS IS NOT A
 RESTAMP; A RESTAMP INVOLVES STAMPING IDENTICAL SHEETS.
  
  
 2.SEE SHEET MARKED PLANS INDEX.OUR RECORD SET IS
 DATED 7/17/06, BUT THE SHEET SUBMITTED HAS A 9/29/06
 REVISION.OTHER SHEETS MAY BE AFFECTED, PLEASE CHECK
 ALL!PLEASE CHECK ALL SHEETS AND SUBMIT THE IDENTICAL
 PLANS FOR RESTAMP OR SUBMIT AS A REVISION.
  
 3.THE ARCHITECT'S SEAL IS TO INCLUDE THE DATE,
 FAC61G1-16, FS481.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-25 Cont ID  
Sent By shill Date 2008-03-25 Time 14:47 Rev Time 0.00
Received By shill Date 2008-03-25 Time 14:47 Sent To  
Notes
2008-03-25 14:48:38SPLIT SLEEVE UL FIRE STOP SHOPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-02-06 Cont ID  
Sent By shill Date 2007-02-06 Time 09:57 Rev Time 0.00
Received By shill Date 2007-02-06 Time 09:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-09-12 Cont ID  
Sent By shill Date 2006-09-12 Time 09:49 Rev Time 0.00
Received By shill Date 2006-09-12 Time 09:49 Sent To  
Notes
2006-09-15 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 THE CA NUMBER, 9666, ON THE PLAN IS NOT
 UNDER THE NAME OF MORSE ZEHNTER
 ASSOCIATES.TO PRACTICE ARCHITECTURE
 AND ENGINEERING THROUGH A COMPANY,
 BUSINESS LICENSE NUMBERS ARE REQUIRED
 FOR BOTH ARCHITECTURE AND ENGINEERING.
  
 THE STUCTURAL ENGINEER'S LETTER IS
 ENCLOSED IN THIS PACKAGE.
  
2006-09-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)REVISED S1 STATES DESIGN AS
 ASCE7-98, SHOULD BE ASCE7-02 FBC 35.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By shill Date 2006-08-11 Time 13:12 Rev Time 0.00
Received By shill Date 2006-08-11 Time 13:12 Sent To  
Notes
2006-08-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)PROVIDE ENERGY CALCS, FBC13.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-14 Cont ID  
Sent By shill Date 2006-06-14 Time 11:56 Rev Time 0.00
Received By shill Date 2006-06-14 Time 10:17 Sent To  
Notes
2006-06-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)PLANS ARE NOT SIGNED AND SEALED.
  
 2.)INCLUDE GOVERNING CODE ON PLANS
 INDEX.
  
 3.)DECLARE LEVEL OF ALTERATION FBC EB
 3.
  
 4.)CONSTRUCTION CLASS (PLANS INDEX)
 SHOULD INCLUDE TYPE A OR B.CONFIRM
 THAT YOU HAVE DECLARED THE CORRECT
 MINIMUM CONSTRUCTION TYPE, FBC 6.
  
 5.)A-1 REFERS TO 713 JOINT SYSTEMS.
 PROVIDE A DETAIL.
  
 6.)IF YOU ARE USING ALLOWABLE
 INCREASES AS INDICATED ON PLANS INDEX
 SHEET, PROVIDE CALCULATIONS.PROVIDE SF
 PER FLOOR.
  
 7.)2ND FLOOR A2 SHOWS A JURY ROOM.
 COURTROOMS ARE A3 OCCUPANCY, 2 HOUR
 SEPARATION REQUIRED, FBC TABLE 302.3.2.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-06 Cont ID  
Sent By dpalmer Date 2006-08-06 Time 16:36 Rev Time 0.00
Received By dpalmer Date 2006-08-06 Time 16:27 Sent To  
Notes
2006-08-06 00:00:00** RELINED PLANS**
  
  
 ANY COLOR CODING FOR 277/480V SHALL BE
 BROWN, PURPLE, YELLOW.
  
 ALL ELECTRICAL SHEETS STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-10 Cont ID  
Sent By dpalmer Date 2006-06-10 Time 18:10 Rev Time 0.00
Received By dpalmer Date 2006-06-10 Time 17:35 Sent To  
Notes
2006-06-10 00:00:00** UNSAT **
  
 ** PLEASE SEE THIS WAS ORIGINALLY
 SUBMITTED UNDER THE 2001 FBC AND ONLY AS
 A "PLAN REVIEW".
 PLEASE SEEE THIS IS NOW SUBMITTED UNDER
 THE 2004 FBC.
  
 1) NOTE: PLEASE SEE FBC CHAPTER 13 FOR
 MIN CALCULATIONS FOR RENOVATIONS TO
 EXISTING.
 PLEASE SEE PRESCRIPTIVE REQUIREMENTS
 AND FORM USE. PLEASE SEE THIS WILL ALSO
 BE IN THE MECHANICAL REVIEW NOTES.
 PLEASE SEE 13-413.1.ABC.1 FOR VOLTAGE
 DROP.
 PLEASE SEE A WORST CASE VOLTAGE DROP
 SHALL BE SHOWN ON PLANS. ONE FOR THE
 FEEDERS AND ONE FOR THE NEW BRANCH
 CIRCUITS.
  
 2) NOTE: PLEASE SEE THE ONE LINE RISER
 DIAGRAM WHICH ONLY SHOWS ONE SET OF
 500MCM'S TO EACH "AM" AND "BM".
 PLEASE SEE THIS SEEMS TO BE A MISPRINT
 AS ONE SETS TO EACH ONLY PROVIDES 400A'S
 WHEREAS THE MAINS ARE 800A.
 310.16,240.4 ETC
  
 3) NOTE: PLEASESHOW OR NOTE THAT THE
 CONTINUOUS LOADS AND LARGEST MOTOR LOADS
 ARE ALREADY FIGURED IN THE CALCULATIONS
 AT 125%. PLEASE REVISE CALCULATIONS TO
 INCLUDE THIS .
 215.3, 230.42
  
 PLEASE REMOVE OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE COPY OF ANY OF THE OLD REMOVED
 VOIDED SHEETS SHOULD BE SUBMITTED FOR
 REFERECNE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-06-19 Cont ID  
Sent By mcarsill Date 2006-06-19 Time 11:02 Rev Time 0.00
Received By mcarsill Date 2006-06-19 Time 10:50 Sent To  
Notes
2006-06-19 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. EXITS SHALL NOT BE BLOCKED BY
 CONSTRUCTION DEBRIS AND THEY SHALL
 REMAIN PASSABLE AT ALL TIMES.
  
 3. INTERIOR FINISH ON WALLS AND CEILINGS
 IN EXIT ACCESS AND EXIT AREAS SHALL BE
 CLASS A.
  
 4. ALL NEW ELECTRICAL WORK TO COMPLY
 WITH NFPA 70, THE NATIONAL ELECTRICAL
 CODE.
  
 5. THE NEW DUCT SMOKE DETECTORS WHEN
 ACTIVATED SHALL ACTIVATE THE BUILDINGS
 FIRE ALARM SYSTEM.
  
 6. ALL NEW FIRE DAMPERS AFTER
 INSTALLATION ARE TO BE TESTED TO ENSURE
 PROPER FUNCTION AND OPERATION.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 15:04 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 15:04 Sent To M
Notes
2008-08-04 15:05:04TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-07-23 Cont ID  
Sent By adarroug Date 2008-07-23 Time 13:36 Rev Time 0.00
Received By adarroug Date 2008-07-23 Time 13:36 Sent To M
Notes
2008-07-23 13:36:54TO "M" BOX/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-07-18 Cont ID  
Sent By adarroug Date 2008-07-18 Time 16:30 Rev Time 0.00
Received By adarroug Date 2008-07-18 Time 16:30 Sent To B
Notes
2008-07-18 16:31:19TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 11:31 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 11:31 Sent To B
Notes
2008-07-11 11:33:20TO "SHILL" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-06-02 Cont ID  
Sent By adarroug Date 2008-06-02 Time 08:29 Rev Time 0.00
Received By adarroug Date 2008-06-02 Time 08:29 Sent To M
Notes
2008-06-02 08:29:49TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 14:28 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 14:28 Sent To M
Notes
2008-05-08 14:29:08TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 14:34 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 14:34 Sent To M
Notes
2008-02-21 14:35:04TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 09:30 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 09:30 Sent To M
Notes
2007-10-15 09:31:09TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 08:51 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 08:51 Sent To  
Notes
2007-01-11 08:38:22TO "COMM" BD#45
2006-12-18 08:52:03WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-31 Cont ID  
Sent By adarroug Date 2006-08-31 Time 14:43 Rev Time 0.00
Received By adarroug Date 2006-08-31 Time 14:43 Sent To  
Notes
2006-09-05 00:00:00TO "COMM" BD#33
2006-08-31 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-05 Cont ID  
Sent By dpalmer Date 2006-08-05 Time 14:25 Rev Time 0.00
Received By dpalmer Date 2006-08-05 Time 14:25 Sent To  
Notes
2006-08-05 00:00:00TO COMM BOARD #31

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-22 Cont ID  
Sent By adarroug Date 2006-07-22 Time 15:48 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 15:48 Sent To  
Notes
2006-07-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-21 Cont ID  
Sent By hmoser Date 2006-06-24 Time 09:16 Rev Time 0.00
Received By rbrown Date 2006-06-24 Time 09:16 Sent To  
Notes
2006-06-06 00:00:00TO "COMM" BD#36
2006-05-22 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2008-08-22 Cont ID  
Sent By rregueir Date 2008-08-22 Time 08:22 Rev Time 0.00
Received By rregueir Date 2008-08-21 Time 14:06 Sent To PC
Notes
2008-08-22 08:22:55REV 7 PAGES M-1 AND M-2

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2008-06-03 Cont ID  
Sent By rregueir Date 2008-06-03 Time 08:30 Rev Time 0.00
Received By rregueir Date 2008-06-03 Time 08:11 Sent To PC
Notes
2008-06-03 08:30:00PAGES M-2 AND M-3 REVISION #6

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2008-05-27 Cont ID  
Sent By rregueir Date 2008-05-27 Time 14:39 Rev Time 0.00
Received By rregueir Date 2008-05-27 Time 14:31 Sent To PC
Notes
2008-05-27 14:39:34PG M-2 REVISION 5
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 COMMENTS:
  
 1. IN THIS REVISION, RETURN AIR HAS BEEN REMOVED AN
 OFFICE IN QUADRANT 2A. BALANCED RETURN IS REQUIRED IN
 THIS AREA IN ACCORDANCE WITH FBCM 601.4. SHOW HOW
 BALANCED AIR IS TO BE ACHIEVED.
  
 2. THE SUPPLY BRANCH FEEDING VAV 05 IN THE SAME OFFICE
 IS MISSING SIZE ON THE PLANS. PLEASE PROVIDE MISSING
 INFORMATION ON PLANS. FBCM 603.1 AND FBCB 106.1.1.
  
 NOTE: PREVIOUS REVISION 5 ON PAGE M-3 WAS REVIEWED WITH
 A PROVISO REGARDING AN OFFICE WHICH WAS MISSING A
 RETURN. PLEASE ADDRESS THE PROVISO ON M-3 WHEN
 RESUBMITTING PAGE M-2. WORK SHALL BE INSTALLED IN
 ACCORDANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS,
 AND ANY CHANGES MADE DURING CONSTRUCTION THAT ARE NOT
 IN COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS
 SHALL BE RESUBMITTED FOR APPROVAL AS AN AMENDED SET OF
 CONSTRUCTION DOCUMENTS IN ACCORDANCE WITH FBCM 106.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-05-27 Cont ID  
Sent By rregueir Date 2008-05-27 Time 14:31 Rev Time 0.00
Received By rregueir Date 2008-05-27 Time 14:30 Sent To PC
Notes
2008-05-27 14:31:10PG M-1 REVISION 5

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-03-25 Cont ID  
Sent By rregueir Date 2008-03-25 Time 15:02 Rev Time 0.00
Received By rregueir Date 2008-03-25 Time 14:17 Sent To PC
Notes
2008-03-25 15:01:56PROVISO: PG M-3 OFFICE 1 HAS NO RETURN. BALANCED RETURN
 IS REQUIRED IN ACCORDANCE WITH FBCM 601.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-10-22 Cont ID  
Sent By rregueir Date 2007-10-20 Time 20:25 Rev Time 0.00
Received By rregueir Date 2007-10-20 Time 19:48 Sent To PC
Notes
2007-10-20 20:25:03REVISION PG M-5

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-02-05 Cont ID  
Sent By rregueir Date 2007-02-05 Time 11:39 Rev Time 0.00
Received By rregueir Date 2007-02-01 Time 13:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-09-28 Cont ID  
Sent By rregueir Date 2006-09-28 Time 17:04 Rev Time 0.00
Received By rregueir Date 2006-09-28 Time 17:04 Sent To  
Notes
2006-09-28 00:00:00----------------DENIED------------------
 1. PAGE M2 QUADRANT 2B: MISSING FIRE
 DAMPER ON 8" ROUND DUCT FROM TO 05 VAV
 IN 'RECEPTION' TO 'OFFICE' 250 CFM DROP.
  
 2. PAGE M10 DETAIL #2: PLEASE INDICATE
 OF WHAT MATERIAL THE ROOF DUCT STANDS
 ARE TO BE CONSTRUCTED, AS WELL AS DETAIL
 FOR FASTENING STANDS TO ROOF IN ORDER TO
 MEET WIND-LOAD REQUIREMENTS.
  
 3. PAGE M10 DETAIL #1B: ALL UL 155
 LISTED FIRE DAMPERS MUST BE INSTALLED
 ACCORDING TO MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. PROVIDE THEM EITHER ON THE
 PLAN OR SEPERATELY.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-18 Cont ID  
Sent By tgordon Date 2006-08-18 Time 15:26 Rev Time 1.30
Received By tgordon Date 2006-08-18 Time 15:26 Sent To  
Notes
2006-08-18 00:00:00*** DENIED ***
 1) SEE PAGE M-2 NEED FIRE DAMPERS AT 5"
 AND 4" DUCTS TO OFFICE, SEE HIGH LIGHT
 (JURY ROOM ON ELECT. PG. E-3).
  
 2) SEE PAGE M-4 MANY DUCTS AND GRILLS
 ARE NOT SIZED, SEE HIGH LIGHT.
  
 3) SEE PAGE S-1 WIND LOAD FBC 2001, WE
 ARE PRESENTLY USING 2004 FBC, PLEASE
 CORRECT.
  
 5) SHOW ON MECHANICAL PLANS LOCATION OF
 CONDENSATE LINES AND WERE THEY WILL
 TERMINATE.
  
 6) PLEASE SUBMIT ENERGY CALCULATIONS,
 PER 2004 FBC/EB 611.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-24 Cont ID  
Sent By hmoser Date 2006-06-24 Time 08:44 Rev Time 0.00
Received By hmoser Date 2006-06-24 Time 08:44 Sent To  
Notes
2006-06-24 00:00:00PLAN DENIED
 1) MISSING FIRE DAMPER IN CONFERENCE
 ROOM PAGE M-1.
 2) MISSING FIRE DAMPER IN JURY ROOM PAGE
 M-2
 3) PLEASE PROVIDE ON THE PLANS ALL DUCT
 AND GRILL SIZE FOR QUADRANT 4-B PAGE M-4
 4) PLEASE REFER TO SECTION 606.4.1
 SUPREVISON 2004 FBC(M)
 5) PLEASE REFER TO SECTION 307.2.3
 AUXILIARY AND SECONDARY DRAIN SYSTEM.
 2004 FBC(M).
 6) PLEASE REFER TO SECTION 307.2.1
 CONDENSATE DISPOSIAL 2004 FBC(M).
 7) PLEASE PROVIDE MANUFACTURERS
 INSTALLATION INSTRUCTIONS ON NOTE # 2
 PAGE M-10
 8) PLEASE PROVIDE A DETAIL FOR A/C CURB
 TIE DOWN TO ROOF ON PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732