Plan Review Details - Permit 06050791
Plan Review Stops For Permit 06050791
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-27 Cont ID  
Sent By adarroug Date 2006-06-27 Time 16:35 Rev Time 0.00
Received By adarroug Date 2006-06-27 Time 16:35 Sent To M
Notes
2006-06-27 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-22 Cont ID  
Sent By tgordon Date 2006-05-22 Time 12:14 Rev Time 0.00
Received By tgordon Date 2006-05-22 Time 09:53 Sent To  
Notes
2006-05-22 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-28 Cont ID  
Sent By tgordon Date 2006-06-28 Time 11:31 Rev Time 0.30
Received By tgordon Date 2006-06-28 Time 11:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-22 Cont ID  
Sent By tgordon Date 2006-05-22 Time 11:57 Rev Time 1.00
Received By tgordon Date 2006-05-22 Time 11:57 Sent To  
Notes
2006-05-22 00:00:00*** DENIED ***
 1) THE ENGINEER'S SEAL AND SIGNATURE
 MUST BE ON PLANS THAT HAVE HIS NAME IN
 THE TITLE BLOCK, PER FAC61G15-23.002 .
  
 2) A/C DUCT LAY-OUT ON MECHANICAL PLANS
 CAN NOT BE DONE IN PENCIL.
  
 3) PLEASE SHOW THE SIZE OF THE RETURN
 AIR TRANSFER GRILLS OVER THE BEDROOM
 DOORS.
  
 4) PLEASE SHOW CONDENSATE DRAIN LINE
 LOCATION ON PLANS.
  
 5) SHOW DUCT SIZE FROM AHU TO MIXING
 BOX.
  
 6) PLEASE SHOW GRILL SIZE AND CFM'S. FOR
 DINING ROOM AND KITCHEN.
  
 7) PLEASE SUBMIT A PROROSAL FOR JOB WITH
 PRICE AND CUSTOMERS SIGNATURE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  