Plan Review Details - Permit 06050785
Plan Review Stops For Permit 06050785
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 10:16 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 10:16 Sent To P
Notes
2006-06-20 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-09 Cont ID  
Sent By adarroug Date 2006-06-09 Time 10:56 Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 10:56 Sent To P
Notes
2006-06-09 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-01 Cont ID  
Sent By mperson Date 2006-06-01 Time 16:57 Rev Time 0.00
Received By mperson Date 2006-05-22 Time 09:00 Sent To  
Notes
2006-05-22 00:00:00TO "E" BOX W/PERMIT#06050786

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-06-26 Cont ID  
Sent By mperson Date 2006-06-26 Time 11:45 Rev Time 2.25
Received By mperson Date 2006-06-26 Time 11:45 Sent To PC
Notes
2006-06-26 00:00:00 
  
  
 ******PROVISO******
 FBC-2004 PLUMBING
 A) 1101.8 CLEANOUTS REQUIRED: CLEANOUTS
 SHALL BE INSTALLED IN THE STORM DRAINAGE
 SYSTEM AND SHALL COMPLY WITH THE PROVI-
 SIONS OF THIS CODE FOR SANITARY DRAINAGE
 PIPE CLEANOUTS.
 ........................................
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-06-14 Cont ID  
Sent By mperson Date 2006-06-14 Time 11:55 Rev Time 0.33
Received By mperson Date 2006-06-14 Time 11:55 Sent To PC
Notes
2006-06-14 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR PLUMBING PLAN REVIEW FOR
 STORM DRAIN ONLY TO FOUNDATION PERMIT
 #06020847.
  
 1. THE COMMENTS FROM THE PRIVIOUS PLAN
 REVIEW HAVE NOT BEEN ADDRESSED, PLEASE
 ADDRESS THOSE COMMENTS BEFORE RESUBMIT-
 TING. PLEASE SEE ATTACHED IMPORTANT
 NOTICE PER STATE STATUTE 553.80(2)(B)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-26 Cont ID  
Sent By mperson Date 2006-05-26 Time 11:28 Rev Time 0.45
Received By mperson Date 2006-05-26 Time 11:28 Sent To PC
Notes
2006-05-26 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW FOR STORM DRAIN
 ONLY TO FOUNDATION PERMIT #06020847
  
 1. SHEET U-P INDICATES A 10" STORM DRAIN
 WITH FOUR BRANCHES AND THE END RUN
 CAPPED, IS THIS THE INTENT, OR ARE THEY
 TO TURN UP TO CATCH RISERS? MORE
 INFORMATION REQUIRED
 2. PER SECTION 106.3.5.1.3 PLUMBING: A
 STORM SYSTEM RISER DIAGRAM, WITH PIPE
 SIZES, DRAIN LOCTIONS, AND SQUARE
 FOOTAGE PER RISER AND TOTAL SQUARE
 FOOTAGE FOR SYSTEM NEEDS TO BE INDICATED
 ON DRAWING.
 3. PER TABLE 1102.4 PLEASE INICATE ON
 SHEET U-P THE TYPE OF MATERIAL BEING
 USED.
 FOOTAGE OF AREAS TO BE DRAINED REQUIRED
 4. ANY PERMIT BEING DONE OFF OF A
 FOUNDATION PERMIT WITH OUT A PLUMBING
 PLAN REVIEW OF ENTIRE BUILDING TO BE
 DONE AT OWN RISK.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721