Plan Review Details - Permit 06050695
Plan Review Stops For Permit 06050695
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-10-03 Cont ID  
Sent By shill Date 2006-10-03 Time 16:39 Rev Time 0.00
Received By shill Date 2006-10-03 Time 16:39 Sent To  
Notes
2006-10-03 00:00:00LETTER FROM ENGINEER RE: ROOF FRAMING
 AND SHEATHING, RUSSELL GOUDY PE DATED
 9/29

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-08-11 Cont ID  
Sent By shill Date 2006-08-11 Time 16:17 Rev Time 0.00
Received By shill Date 2006-08-11 Time 16:17 Sent To  
Notes
2006-08-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)AN APPLICATION WAS BROUGHT IN BY A
 CBC.THIS IS NOT WITHIN THE SCOPE OF
 CBC LICENSE.
  
 2.)THE APPLICATION WAS INSIDE OF THE
 PACKAGE AND NOT PROCESSED THROUGH THE
 DESK.HAVE A CONTRACTOR WHO IS LICENSED
 TO DO THIS WORK APPLY FOR THE WORK AS
 REQUIRED BY THE CBAA.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-05 Cont ID  
Sent By shill Date 2006-08-05 Time 15:06 Rev Time 0.00
Received By shill Date 2006-08-05 Time 15:06 Sent To  
Notes
2006-08-05 00:00:00***PROVISO***OBTAIN FIREPROOFING PERMIT
 PRIOR TO FINAL INSPECTION
  
 SITE SPECIFIC PRODUCT APPROVAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-28 Cont ID  
Sent By shill Date 2006-06-28 Time 12:49 Rev Time 0.00
Received By shill Date 2006-06-28 Time 12:49 Sent To FIRE
Notes
2006-06-28 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)ADDRESSED.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.THE STATE
 PRODUCT APPROVAL IS EXPIRED (2001 CODE
 RATHER THAN FBC2004).
  
 (3RD REVIEW) SEE FAC9B72.AN
 APPLICATION IS REQUIRED.ALL
 ENGINEERING IS TO BE SIGNED, SEALED,
 DATED ORIGINALS.
  
 3.)THE NOA STATES THAT THE PRODUCT
 SPECIFIED IS FOR USE OVER STEEL FRAMING.
 THE CBAA PAPERWORK INDICATES THAT THIS
 IS OVER WOOD FRAMING.ENGINEERING, WITH
 LOCAL PRODUCT APPROVAL APPLICATION, IS
 REQUIRED.
  
 NOT ADDRESSED.PLEASE SUBMIT LOCAL
 PRODUCT APPROVAL APPLICATION FAC9B72,
 WWW.FLORIDABUILDING.ORG.
  
 ALSO SUBMIT LEGIBLE MIAMI-DADE NOAS.
 THE NOAS SUBMITTED ARE DIFFICULT TO
 READ.
  
 4.) ADDRESSED.
  
 5.)THE CBAA CASE AND PAPERWORK
 INCLUDED REFER TO WORK WHICH IS NOT
 WITHIN THE SCOPE OF A CCC LICENSE: FIRE
 SPRINKLERS, FIREPROOFING OF STRUCTURAL
 ELEMENTS, REPAIR OF WOOD FRAMING.THE
 PLANS WHICH YOU WILL SUBMIT SHOULD MAKE
 CLEAR THE SCOPE OF WORK UNDER THIS
 PERMIT APPLICATION.PROVIDE APPLICATION
 NUMBERS OF THE OTHER WORK ASSOCIATED
 WITH THIS PROJECT, OR APPLY UNDER A
 CONTRACTOR LICENSED TO OVERSEE ALL WORK
 REQUIRED.
  
 AS DISCUSSED, HAVE A GENERAL CONTRACTOR
 (OR OTHER CONTRACTOR LICENSED TO PERFORM
 THE WORK) APPLY. AS DISCUSSED, THIS CAN
 BE DONE WITH A CHANGE OF CONTRACTOR.
 THE ROOFING CONTRACTOR WILL APPLY AS A
 SUBCONTRACTOR.
  
 3RD REVIEW - NOT ADDRESSED.
  
  
 8.)IS THERE A WOOD DECK IN ADDITION TO
 THE WOOD FRAMING?EXISTING CONDITIONS
 ARE NOT CLEAR.
  
 CBAA ORDER REFERS TO WOOD FRAMING.THIS
 IS NOT SHOWN ON THE ENGINEER'S PLAN.
 PROVIDE FRAMING INFORMATION (MATERIAL
 AND SPACING) SO THAT CODE COMPLIANCE CAN
 BE DETERMINED.
  
 9.)PROVIDE WIND DESIGN CRITERIA
 FBC1603.1.4, INCLUDING DESIGN PRESSURES
 FOR THE ROOF.
  
 10.) ON THE APPLICATION, CONTRACTOR
 STATES THAT THE ROOF PITCH IS 1/12.THE
 DRAWINGS SHOW 2 1/2/12.CLARIFY THE
 DISCREPANCY.DESIGN PRESSURES ARE
 DIFFER FOR THE TWO DIFFERENT CONDITIONS.
  
 11.)THE 60 MINUTE FIRE SPEC TEST WAS
 OVER DOUGLAS FIR PLYWOOD; THE ENGINEER'S
 DRAWING SHOWS THE PRODUCT OVER
 INSULATION.THIS DOES NOT APPEAR TO
 PROVIDE THE 1 HOUR PROTECTION REQUIRED
 BY THE CBAA ORDER.
  
 NOT ADDRESSED.
  
 12.)THE NOC IS FOR REROOF ONLY.A NEW
 NOC WILL BE REQUIRED.
  
 13.)PROVIDE PRODUCT APPROVAL FOR THE
 TU PLUS SHOWN ON THE ENGINEER'S DRAWING
 (METAL UNDERLAYMENT).
  
 NOT ADDRESSED.PRODUCT APPROVALS TO BE
 REVIEWED BY DESIGNER OF RECORD.
  
 14.)IT IS NOT CLEAR HOW DETAIL A, 1/2,
 FLASHING AT WALL, WILL KEEP WATER FROM
 GETTING UNDER WHAT THE PLAN CALLS
 "PHILADELPHIA FLASHING", FBC1503.2.
  
 ***********************
 7/13/06
 AS THE ROOF IS LEAKING, TO ASSIST IN
 GETTING THE ROOF PERMIT ISSUED, THE
 FOLLOWING IS ACCEPTABLE:
  
 CHANGE OF CONTRACTOR FOR 06050695 (FROM
 CCC TO A CGC OR CBC OR OTHER CONTRACTOR
 LICENSED TO PERFORM OR OVERSEE THE SCOPE
 OF WORK)
  
 ROOFING CONTRACTOR TO APPLY FOR ROOF
 PERMIT, REFERRING TO 06050695 AS MASTER
 PERMIT NUMBER
  
 LOCAL PRODUCT APPROVAL MAY BE SUBMITTED
 SEPARATELY FROM THE RESUB FOR 06050695
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-13 Cont ID  
Sent By shill Date 2006-06-13 Time 14:44 Rev Time 0.00
Received By shill Date 2006-06-13 Time 14:44 Sent To FIRE
Notes
2006-06-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)ADDRESSED.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.THE STATE
 PRODUCT APPROVAL IS EXPIRED (2001 CODE
 RATHER THAN FBC2004).
  
 NOT ADDRESSED.SEE COMMENT 3 BELOW.
 LOCAL PRODUCT APPROVAL REQUIRED.
  
 3.)THE NOA STATES THAT THE PRODUCT
 SPECIFIED IS FOR USE OVER STEEL FRAMING.
 THE CBAA PAPERWORK INDICATES THAT THIS
 IS OVER WOOD FRAMING.ENGINEERING, WITH
 LOCAL PRODUCT APPROVAL APPLICATION, IS
 REQUIRED.
  
 NOT ADDRESSED.PLEASE SUBMIT LOCAL
 PRODUCT APPROVAL APPLICATION FAC9B72,
 WWW.FLORIDABUILDING.ORG.
  
 ALSO SUBMIT LEGIBLE MIAMI-DADE NOAS.
 THE NOAS SUBMITTED ARE DIFFICULT TO
 READ.
  
 4.) ADDRESSED.
  
 5.)THE CBAA CASE AND PAPERWORK
 INCLUDED REFER TO WORK WHICH IS NOT
 WITHIN THE SCOPE OF A CCC LICENSE: FIRE
 SPRINKLERS, FIREPROOFING OF STRUCTURAL
 ELEMENTS, REPAIR OF WOOD FRAMING.THE
 PLANS WHICH YOU WILL SUBMIT SHOULD MAKE
 CLEAR THE SCOPE OF WORK UNDER THIS
 PERMIT APPLICATION.PROVIDE APPLICATION
 NUMBERS OF THE OTHER WORK ASSOCIATED
 WITH THIS PROJECT, OR APPLY UNDER A
 CONTRACTOR LICENSED TO OVERSEE ALL WORK
 REQUIRED.
  
 AS DISCUSSED, HAVE A GENERAL CONTRACTOR
 (OR OTHER CONTRACTOR LICENSED TO PERFORM
 THE WORK) APPLY. AS DISCUSSED, THIS CAN
 BE DONE WITH A CHANGE OF CONTRACTOR.
 THE ROOFING CONTRACTOR WILL APPLY AS A
 SUBCONTRACTOR.
  
 6.)AS NO PLANS WERE SUBMITTED, CODE
 COMPLIANCE CANNOT BE DETERMINED.BASED
 ON THE FORMULA ON THE PRODUCT APPROVAL,
 THIS PRODUCT DOES NOT MEET THE DESIGN
 PRESSURE LIMITATION FOR ZONES 2 AND 3
 FOR A ROOF 0- 10 DEGREES.
  
 NOT PROPERLY ADDRESSED.DESIGN
 PRESSURES WERE NOT PROVIDED BY THE
 ENGINEER, AND CONFLICTING INFORMATION
 PROVIDED IN REGARDS TO THE ROOF PITCH.
  
 DESIGN PRESSURE LIMITATIONS FOR THE
 PRODUCT ARE NOT CLEAR.THE PRODUCT
 CONTAINS A FORMULA TO DETERMINE UPLIFT
 DP.ACCORDING TO THE FORMULA, DP IS
 -35.37, NOT COMPLIANT FOR COMPONENTS &
 CLADDING.I HAVE LEFT A MESSAGE WITH
 THE MANUFACTURER FOR CLARIFICATION.
  
 7.)DESIGNER OF RECORD IS TO REVIEW THE
 PRODUCT APPROVALS, FBC*106.3.3.
  
 8.)IS THERE A WOOD DECK IN ADDITION TO
 THE WOOD FRAMING?EXISTING CONDITIONS
 ARE NOT CLEAR.
  
 CBAA ORDER REFERS TO WOOD FRAMING.THIS
 IS NOT SHOWN ON THE ENGINEER'S PLAN.
 PROVIDE FRAMING INFORMATION (MATERIAL
 AND SPACING) SO THAT CODE COMPLIANCE CAN
 BE DETERMINED.
  
 NEW COMMENTS:
  
 9.)PROVIDE WIND DESIGN CRITERIA
 FBC1603.1.4, INCLUDING DESIGN PRESSURES
 FOR THE ROOF.
  
 10.) ON THE APPLICATION, CONTRACTOR
 STATES THAT THE ROOF PITCH IS 1/12.THE
 DRAWINGS SHOW 2 1/2/12.CLARIFY THE
 DISCREPANCY.DESIGN PRESSURES ARE
 DIFFER FOR THE TWO DIFFERENT CONDITIONS.
  
 11.)THE 60 MINUTE FIRE SPEC TEST WAS
 OVER DOUGLAS FIR PLYWOOD; THE ENGINEER'S
 DRAWING SHOWS THE PRODUCT OVER
 INSULATION.THIS DOES NOT APPEAR TO
 PROVIDE THE 1 HOUR PROTECTION REQUIRED
 BY THE CBAA ORDER.
  
 12.)THE NOC IS FOR REROOF ONLY.A NEW
 NOC WILL BE REQUIRED.
  
 13.)PROVIDE PRODUCT APPROVAL FOR THE
 TU PLUS SHOWN ON THE ENGINEER'S DRAWING
 (METAL UNDERLAYMENT).
  
 14.)IT IS NOT CLEAR HOW DETAIL A, 1/2,
 FLASHING AT WALL, WILL KEEP WATER FROM
 GETTING UNDER WHAT THE PLAN CALLS
 "PHILADELPHIA FLASHING", FBC1503.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-22 Cont ID  
Sent By shill Date 2006-05-22 Time 10:08 Rev Time 0.00
Received By shill Date 2006-05-22 Time 10:08 Sent To  
Notes
2006-05-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)THE CBAA CASE STATES THAT FIRE
 RESISTANCE IS REQUIRED, "APPLICANT IS TO
 PROVIDE ENGINEERING DOCUMENTATION TO THE
 BUILDING OFFICIAL."PROVIDE ENGINEERING
 AS AGREED CBAA CASE 1295.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.THE STATE
 PRODUCT APPROVAL IS EXPIRED (2001 CODE
 RATHER THAN FBC2004).
  
  
 3.)THE NOA STATES THAT THE PRODUCT
 SPECIFIED IS FOR USE OVER STEEL FRAMING.
 THE CBAA PAPERWORK INDICATES THAT THIS
 IS OVER WOOD FRAMING.ENGINEERING, WITH
 LOCAL PRODUCT APPROVAL APPLICATION, IS
 REQUIRED.
  
 4.) ON THE PERMIT APPLICATIN, INCLUDE
 ALL INFORMAITON REQUIRED BY THE ATTACHED
 POLICY.ROOF DECK TYPE IS NOT ON THE
 APPLICATION.
  
 5.)THE CBAA CASE AND PAPERWORK
 INCLUDED REFER TO WORK WHICH IS NOT
 WITHIN THE SCOPE OF A CCC LICENSE: FIRE
 SPRINKLERS, FIREPROOFING OF STRUCTURAL
 ELEMENTS, REPAIR OF WOOD FRAMING.THE
 PLANS WHICH YOU WILL SUBMIT SHOULD MAKE
 CLEAR THE SCOPE OF WORK UNDER THIS
 PERMIT APPLICATION.PROVIDE APPLICATION
 NUMBERS OF THE OTHER WORK ASSOCIATED
 WITH THIS PROJECT, OR APPLY UNDER A
 CONTRACTOR LICENSED TO OVERSEE ALL WORK
 REQUIRED.
  
  
 6.)AS NO PLANS WERE SUBMITTED, CODE
 COMPLIANCE CANNOT BE DETERMINED.BASED
 ON THE FORMULA ON THE PRODUCT APPROVAL,
 THIS PRODUCT DOES NOT MEET THE DESIGN
 PRESSURE LIMITATION FOR ZONES 2 AND 3
 FOR A ROOF 0- 10 DEGREES.
  
 7.)DESIGNER OF RECORD IS TO REVIEW THE
 PRODUCT APPROVALS, FBC*106.3.3.
  
 8.)IS THERE A WOOD DECK IN ADDITION TO
 THE WOOD FRAMING?EXISTING CONDITIONS
 ARE NOT CLEAR.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2006-08-05 Cont ID  
Sent By shill Date 2006-08-05 Time 15:10 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2006-08-05 00:00:00FIREPROOFING/SPRINKLERS ON A SEPARATE
 PERMIT; REROOF ONLY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-07-21 Cont ID  
Sent By mwennerg Date 2006-07-21 Time 14:51 Rev Time 0.00
Received By mwennerg Date 2006-07-21 Time 14:51 Sent To  
Notes
2006-07-21 00:00:00***DENIED***
  
 PLEASE SEE LAST FIRE REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-21 Cont ID  
Sent By mwennerg Date 2006-06-21 Time 12:58 Rev Time 0.00
Received By mwennerg Date 2006-06-21 Time 12:58 Sent To  
Notes
2006-06-21 00:00:00***DENIED***
  
 1) CONTRACT PROPOSAL INDICATES A TOTAL
 OF (24) FIRE SPRINKLER RELOCATIONS
 WITHIN THE SCOPE OF THIS PROJECT.
 SEPARATE SHOP DRAWINGS AND PERMIT IS
 REQUIRED. A (2) HOUR PRESSURE TEST SHALL
 BE DONE UNLESS THE SPRINKLER SYSTEM
 CAN'T BE ISOLATED. IF THAT CONDITION
 EXISTS, A LETTER STATING THIS WITH THE
 CODE EXCEPTION WILL BE REQUIRED AT THE
 BUREAU OF FIRE PREVENTION.
  
 2) PLEASE SEE BUILDING REVIEW COMMENT
 #11 IN REFERENCE TO THE APPROVED FIRE
 TESTING. PLEASE SUBMIT INFORMATION
 REGARDING HOW THIS TEST WILL BE
 APPLICABLE TO THIS PROJECT AS DIFFERENT
 MATERIALS PRODUCE DIFFERENT TEST
 RESULTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 12:50 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 12:50 Sent To B
Notes
2006-07-31 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-23 Cont ID  
Sent By adarroug Date 2006-06-23 Time 10:21 Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 10:21 Sent To B
Notes
2006-06-23 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 14:47 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 14:47 Sent To B
Notes
2006-06-07 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-22 Cont ID  
Sent By shill Date 2006-05-22 Time 10:44 Rev Time 0.00
Received By shill Date 2006-05-18 Time 15:30 Sent To  
Notes
2006-05-18 00:00:00TO "SHILL" DESK