Plan Review Details - Permit 06050627
Plan Review Stops For Permit 06050627
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-25 Cont ID  
Sent By mawillia Date 2006-07-25 Time 11:43 Rev Time 0.00
Received By mawillia Date 2006-07-25 Time 11:43 Sent To  
Notes
2006-07-25 00:00:00*** APPROVED ***
  
 APPROVED AND ACCEPTED NEW CALCULATIONS
 FOR MINIMUM SAFETY MARGIN

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-21 Cont ID  
Sent By mwennerg Date 2006-06-21 Time 13:57 Rev Time 0.00
Received By mwennerg Date 2006-06-21 Time 13:57 Sent To  
Notes
2006-06-21 00:00:00***DENIED***
  
 1) CALCULATION SHEETS INDICATE A SAFETY
 MARGIN OF 4.928 PSI. PLEASE NOTE THAT A
 MINIMUM SAFETY MARGIN OF 5 IS REQUIRED
 IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-25 Cont ID  
Sent By adarroug Date 2006-06-21 Time 11:12 Rev Time 0.00
Received By adarroug Date 2006-05-17 Time 15:26 Sent To  
Notes
2006-05-17 00:00:00TO "F" BOX