Plan Review Details - Permit 06050601
Plan Review Stops For Permit 06050601
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-27 Cont ID  
Sent By alange Date 2006-06-27 Time 13:34 Rev Time 0.33
Received By alange Date 2006-06-27 Time 13:34 Sent To G
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-12 Cont ID  
Sent By alange Date 2006-06-12 Time 13:39 Rev Time 0.33
Received By alange Date 2006-06-12 Time 13:39 Sent To  
Notes
2006-06-12 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-06-02 Cont ID  
Sent By btrobaug Date 2006-06-02 Time 12:16 Rev Time 0.50
Received By btrobaug Date 2006-06-02 Time 12:16 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-06-02 Cont ID  
Sent By mperson Date 2006-06-02 Time 15:13 Rev Time 0.15
Received By mperson Date 2006-06-02 Time 15:13 Sent To B
Notes
2006-06-02 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-27 Cont ID  
Sent By adarroug Date 2006-06-27 Time 09:31 Rev Time 0.00
Received By adarroug Date 2006-06-27 Time 09:31 Sent To B
Notes
2006-06-27 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 12:40 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 12:40 Sent To Z
Notes
2006-06-21 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-31 Cont ID  
Sent By adarroug Date 2006-05-31 Time 14:31 Rev Time 0.00
Received By adarroug Date 2006-05-31 Time 14:31 Sent To E
Notes
2006-05-31 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-12 Cont ID  
Sent By alange Date 2006-06-12 Time 13:39 Rev Time 0.00
Received By alange Date 2006-05-16 Time 14:31 Sent To  
Notes
2006-05-16 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-02 Cont ID  
Sent By mperson Date 2006-06-02 Time 15:12 Rev Time 0.00
Received By mperson Date 2006-06-02 Time 15:12 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-06-25 Cont ID  
Sent By mmclean Date 2006-06-25 Time 13:55 Rev Time 0.00
Received By mmclean Date 2006-06-25 Time 13:55 Sent To I
Notes
2006-06-25 00:00:00NOTE:
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 11FT FROM PROPERTY LINE
 (SIDE) & 8FT FROM REAR SETBACK.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-05-30 Cont ID  
Sent By mmclean Date 2006-05-30 Time 16:27 Rev Time 0.00
Received By mmclean Date 2006-05-30 Time 16:27 Sent To I
Notes
2006-05-30 00:00:00DENIED,
 1. THE PROPOSED GENERATOR MUST BE 5FT
 FROM THE SIDE PROPERTY LINE.
  
 NOTE: GENERATOR CAN ONLY ENCROACH 4FT
 INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720