Plan Review Stops For Permit 06050571
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2006-10-16 Cont ID  
Sent By mperson Date 2006-10-16 Time 08:49 Rev Time 0.33
Received By mperson Date 2006-10-16 Time 08:49 Sent To PC
Notes
2006-10-16 08:52:26REVISION: ADD ADDITIONAL PIPING FOR A 50,000 BTU GAS
 GRILL.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-09-22 Cont ID  
Sent By mperson Date 2006-09-22 Time 10:22 Rev Time 0.33
Received By mperson Date 2006-09-22 Time 10:22 Sent To PC
Notes
2006-09-22 00:00:00REVISION: CHANGE FROM 12" W.C. TO A 2LB
 SYSTEM WITH REGULATORS SET AT ALL INLETS
 GOING TO THE INTERIOR AND AT POOL HEATER
  
 ******PROVISO******
 409.4 MP REGULATORS VALVES: A LISTED
 VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-07-13 Cont ID  
Sent By mperson Date 2006-07-13 Time 09:17 Rev Time 0.33
Received By mperson Date 2006-07-13 Time 09:17 Sent To PC
Notes
2006-07-13 00:00:00NOTE: REFERENCE FIREPLACE PERMIT
 #05121184

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-05-19 Cont ID  
Sent By mperson Date 2006-05-19 Time 14:25 Rev Time 0.33
Received By mperson Date 2006-05-19 Time 14:25 Sent To PC
Notes
2006-05-19 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A GAS PERMIT:
  
 1. TYPE OF GAS, (LP OR NATURAL) THIS HAS
 TO BE INDICATED ON THE DRAWINGS.
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).(EXISTING
 SYSTEM MUST BE INDICATED ON DRAWING AND
 INDICATE THE POINT OF TIE IN FOR FIRE
 PLACE)
 4. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 17:22 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 17:19 Sent To G
Notes
2006-10-10 17:20:06TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-15 Cont ID  
Sent By adarroug Date 2006-09-15 Time 10:02 Rev Time 0.00
Received By adarroug Date 2006-09-15 Time 10:02 Sent To G
Notes
2006-09-15 00:00:00TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-07-07 Time 14:50 Rev Time 0.00
Received By adarroug Date 2006-07-07 Time 14:49 Sent To G
Notes
2006-07-07 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-19 Cont ID  
Sent By mperson Date 2006-05-19 Time 14:38 Rev Time 0.00
Received By mperson Date 2006-05-16 Time 14:56 Sent To  
Notes
2006-05-16 00:00:00TO "G" BOX