Plan Review Details - Permit 06050544
Plan Review Stops For Permit 06050544
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-14 Cont ID  
Sent By shill Date 2006-06-14 Time 14:26 Rev Time 0.00
Received By shill Date 2006-06-14 Time 14:26 Sent To  
Notes
2006-06-14 00:00:00PROVISO - PROVIDE CONDO ASSOCIATION
 APPROVAL AT FIRST INSPECTION

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By shill Date 2006-05-31 Time 14:08 Rev Time 0.00
Received By shill Date 2006-05-31 Time 14:08 Sent To  
Notes
2006-05-31 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)CODE COMPLIANCE CANNOT BE
 DETERMINED DUE TO CONFLICTING
 INFORMATION IN THE PERMIT PACKAGE.
  
 YOU HAVE DECLARED WIND PRESSURES USING
 SOFTWARE; THESE PRESSURES APPEAR
 COMPLIANT.ON THE PRODUCT APPROVAL, YOU
 HAVE CIRCLED -31.2, WHICH IS TOO LOW FOR
 140MPH.
  
 YOU HAVE CIRCLED THE NUMBER -31.2 IN
 SEVERAL DIFFERENT PLACES, SHOWING TWO
 DIFFERENT EDGE DISTANCES AND TWO
 DIFFERENT FASTENERS.
  
 THE SPACING OF 12"/12" SPECIFIED ON THE
 SCHEDULE IS NOT COMPLIANT FOR ALL
 OPENINGS.SEE THE ANCHOR SPACING
 REQUIRED FOR -47.2.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 16:33 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 16:33 Sent To B
Notes
2006-06-08 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-31 Cont ID  
Sent By shill Date 2006-05-31 Time 14:27 Rev Time 0.00
Received By shill Date 2006-05-15 Time 15:19 Sent To  
Notes
2006-05-15 00:00:00TO "MISC" BOX#1