Plan Review Details - Permit 06050484
Plan Review Stops For Permit 06050484
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By jwitmer Date 2006-05-31 Time 12:28 Rev Time 0.55
Received By jwitmer Date 2006-05-31 Time 12:28 Sent To  
Notes
2006-05-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06050484
 ADD: 1101 S FLAGLER DR BLDG "F"
 CONT: RALPH DELLA-PIETRA, INC.
 TEL: (561)745-8555
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) DISCREPANCY PERMIT APPLICATION
 DESCRIBES THE REMOVAL OF 5/8" CDX
 PLYWOOD AND ADDING 5/8" PLYWAOOD
 SHEATHING WHEREAS THE PLANS ONLY
 INDICATE "REMOVAL" OF PLYWOOD, NO
 MENTION OF REPLACEMENT, WHAT ABOUT SHEER
 WALLS?
  
 3) SHEET A-3 IS MISSING INFORMATION ON
 WIRE LATH:
 2510.3 INSTALLATION.
 INSTALLATION OF THESE MATERIALS SHALL BE
 IN COMPLIANCE WITH ASTM C 926 AND ASTM C
 1063.
 A) TYPE OF LATH,& WEIGHT
 B) FASTENER& SPACING
  
 4) DETAIL @ WINDOWS & DOORS.
  
 5) A-3 DISCREPANCY, SOFFITS THERE ARE
 (2) NOTES ONE FOR 3/8" EXT GRADE PLYWOOD
 FOR SOFFIT THE OTHER IS TO REMOVE AND
 STUCCO SOFFIT. PROVIDE TYPE OF LATH FOR
 SOFFITS, (24" C/C)?
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-11 Cont ID  
Sent By dpalmer Date 2006-06-11 Time 08:17 Rev Time 0.00
Received By dpalmer Date 2006-06-11 Time 08:17 Sent To  
Notes
2006-06-11 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE THE PERMIT
 APPLICATION(S) MENTIONS ELECTRICAL WORK
 BEING DONE AND IN SCOPE OF WORK.
 PLEASE PROVIDED DETAIL FOR AREA AND
 PROPOSED REMOVAL OF ELECTRICAL
 CONDUITS/LTS ETC.
 215.5
 THIS DETAIL CAN BE TYPICAL IF ALL
 BUILDINGS ARE THE SAME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-06-16 Cont ID  
Sent By mcarsill Date 2006-06-16 Time 11:30 Rev Time 0.00
Received By mcarsill Date 2006-06-16 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-26 Cont ID  
Sent By tgordon Date 2006-06-26 Time 09:50 Rev Time 0.00
Received By tgordon Date 2006-06-12 Time 08:04 Sent To  
Notes
2006-06-12 00:00:00TO "COMM" BD#21

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-26 Cont ID  
Sent By tgordon Date 2006-06-26 Time 09:50 Rev Time 0.02
Received By tgordon Date 2006-06-26 Time 09:50 Sent To  
Notes
***NONE***