Plan Review Stops For Permit 06050448 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2006-06-21 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-06-21 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2006-07-05 |
Time |
13:28 |
Sent To |
|
|
Notes |
2006-06-21 00:00:00 | FOR THIS PARCEL 74414224060020030 THE | | ADDRESS OF 7987 SANDHILL WAY E MUST BE | | USED UNDER THE OWNER OF NORTHERN PALM | | BEACH COUNTY IMPROV DISTRICT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2006-08-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-08-11 |
Time |
12:27 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-08-11 |
Time |
12:27 |
Sent To |
|
|
Notes |
2006-08-11 00:00:00 | PLANS STAMPED BY LUIS ON JULY 17TH | 2006-07-15 00:00:00 | NEEDS BLDG REVIEW AND STAMPING AS A | | STRUCTURAL SHEET FOR WALLS AND SLAB ARE | | ATTACHED TO PLANS, BUT NOT SIGNED, OR | | STAMPED BY REVIEWER. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2006-07-05 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2006-07-05 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2006-07-05 |
Time |
13:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-06-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-06-21 |
Time |
06:33 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-06-21 |
Time |
06:33 |
Sent To |
|
|
Notes |
2006-06-21 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2004 | | | | FROM PREVIOUS LIST, NOT ADDRESSED: | | | | 1.)PROVIDE ANCHORING INFORMATION TO | | COMPLY WITH FBC1606.1.3; STRUCTURAL | | MEMBERS AND SYSTEMS, AND COMPONENTS AND | | CLADDING IN A BUILDING OR STRUCTURE | | SHALL BE ANCHORED TO RESIST WIND-INDUCED | | OVERTURNING, UPLIFT AND SLIDING AND TO | | PROVIDE CONTINUOUS LOAD PATHS FOR THESE | | FORCES TO THE FOUNDATION.WHERE A | | PORTION OF THE RESISTANCE TO THESE | | FORCES IS PROVIDED BY DEAD LOAD, THE | | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | DURING A DESIGN WIND EVENT SHALL BE | | USED. | | | | 2.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 3.)AN INCORRECT ADDRESS WAS PROVIDED | | ON THE APPLICATION.PLEASE REVISE.THE | | CORRECT ADDRESS IS 7987 SANDHILL WAY E. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-05-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-05-24 |
Time |
07:32 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-05-24 |
Time |
07:37 |
Sent To |
|
|
Notes |
2006-05-24 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2004 | | | | 1.)PROVIDE ANCHORING INFORMATION TO | | COMPLY WITH FBC1606.1.3; STRUCTURAL | | MEMBERS AND SYSTEMS, AND COMPONENTS AND | | CLADDING IN A BUILDING OR STRUCTURE | | SHALL BE ANCHORED TO RESIST WIND-INDUCED | | OVERTURNING, UPLIFT AND SLIDING AND TO | | PROVIDE CONTINUOUS LOAD PATHS FOR THESE | | FORCES TO THE FOUNDATION.WHERE A | | PORTION OF THE RESISTANCE TO THESE | | FORCES IS PROVIDED BY DEAD LOAD, THE | | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | DURING A DESIGN WIND EVENT SHALL BE | | USED. | | | | 2.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 3.)AN INCORRECT PARCEL ID WAS PROVIDED | | ON THE APPLICATION.PLEASE REVISE. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2006-08-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-08-11 |
Time |
12:52 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-08-11 |
Time |
12:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2006-08-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-08-07 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-08-07 |
Time |
14:32 |
Sent To |
B |
|
Notes |
2006-08-07 00:00:00 | *** UNSAT 4THR REVIEW ** | | | | 1) NOTE: PLEASE SEE THE MTS | | SPECIFICATIONS SUBMITTED ARE NOW | | COMPLETELY DIFFERENT FROM PLANS/RISER. | | PLEASE SEE RISER SHOWS A 250A MTS. WE | | NEED EITHER SPEC FOR A 250A MTS OR | | REVISE PLANS TO CORRLELATE WITH | | SUBMITTIALS. | | THIS WAS REQUESTED ON THREE PREVIOUS | | REVIEWS AND ONE REVIEW DONE WITH OUT | | PLANS BEING SUBMITTED. | | THIS OFFICE HAS SPOKE TO THE ELECTRICAL | | CONTRACTOR AND THE ELECTRICAL ENGINEER | | ON MORE THAN ONE OCCASION. | | PLEASE KNOW THIS OFFICE HAS ALSO LEFT | | TWO MESSAGES FOR THE ENGINEER ON THE | | OFFICE VOICE MAIL AND THE CELL PHONE | | VOICE MAIL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2006-07-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-07-15 |
Time |
13:43 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-07-15 |
Time |
13:26 |
Sent To |
|
|
Notes |
2006-07-15 00:00:00 | ** UNSAT ** | | | | 1) NOTE: PLEASE SEE NOTES ONE AND 6 FROM | | PREVIOUS REVIEW. | | PLEASE SEE THRESS SETS OF PLANS ARE | | BEING SUBMITTED, HOWEVER NOW ONLY TWO | | SETS OF SPECS ARE BEING SUBMITTED. | | PLEASE SEE SPECS FOR MTS HAS HAND TYPED | | NOTE ON MANUFACTURES SPECS/CUT SHEETS | | WHICH MENTIONS A OFF POSITION??? | | RISER DOES NOT INDCIATE THIS AND SPECS | | FROM MANUFACTURE MAY NOT HAVE ITEMS | | TYPED AND ADDED TO SPEC WHICH DI NOT | | ORIGINATE FROM MANUFACTURE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-06-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-06-16 |
Time |
18:14 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-06-16 |
Time |
17:57 |
Sent To |
|
|
Notes |
2006-06-16 00:00:00 | *** UNSAT 2ND REVIEW *** | | | | | | ** PLEASE SEE SOME COMMENTS FROM | | PREVIOUS REVIEW AND SOME NEW COMMENTS. | | PLEASE SEE PREVIOUS REVIEW COMMENTS ARE | | TAKEN DIRECTLY FROM PREVIOUS REVIEW WITH | | NEW NOTES ADDED AT THE BOTTOM. | | | | | | ******** UNSAT ********* | | | | 1) NOTE:NOTE #1 NO, PLEASE SEE ONLY | | ONE COPY OF SPEC/MANUFACTURES CUT SHEETS | | WERE SUBMITTED FOR THE GENERATORS. NO | | SPECS/CUT SHEETS WERE SUBMITTED FOR THE | | MTS, ATS, FUEL TANK.??? | | PLEASE SEE SOME ITEMS FOR CODE | | COMPLIANCE CAN NOT BE VERIFIED AT THIS | | TIME. | | ** PLEASE KNOW, TWO COPIES OF ALL MUST | | BE SUBMITTED. THREE COMPLETE SETS MAY BE | | SUBMITTED, HOWEVER ONLY TWO ARE | | REQUIRED. UP TO THREE SETS WILL BE | | STAMPED. | | | | ** PREVIOUS NOTE ** | | PLEASE SUBMIT ALL MANUFACTURES | | SPECS/CUT SHEETS FOR GENERATOR, ATS , | | MTS AND SUB BASE FUEL TANK. | | PLEASE KNOW, ALL MUST INDICATE LISTING | | FROM A NRTL. | | 215.5 | | | | 2) NOTE: NOTE #2 OK,HOWEVER PLEASE STILL | | SEE INFORMATION FOR TANK(S) HAVE NOT | | BEEN SUBMITTED. | | | | 3) NOTE: OK | | | | 4) NOTE: OK | | | | 5) NOTE: OK.. | | | | 6) NOTE: NOTE #6, NO, RISER DOES NOT | | SHOW THIS AND SPECS WERE NOT SUBMITTED. | | RESPONSE MENTIONS CIRCUIT BRKR, YET THIS | | BREAKE RIS SHOWN FROM THE RECEPTS WHICH | | IS CLEAR AND OK. PLEASE SEE HOWEVER IF | | SYSTEM IS SET UP ON AN AUTOMATIC | | TRANSFER A MANUAL MEANS OF DISCONNECT | | SHALL BE REQUIRED FOR FEEDERS COMING | | FROM GEN. | | | | | | ** PREVIOUS NOTE ** | | PLEASE SEE THE MTS MUST CONTAIN | | A "OFF" POSITION AS THE MEANS OF | | DISCONNECT REQUIRED FOR POWER COMING | | FROM THE GEN. THE BRKR ON THE INSIDE OF | | THE GEN CAN NOT BE THE DISCONNECT MEANS | | FOR POWER IN EM CONDITIONS. | | 225.31-225.39. | | | | 7) NOTE: OK, AS LT POLE WAS REMOVED FROM | | PLANS. | | | | *** NEW NOTE** | | | | 8) NOTE: PLEASE SEE BUILDING NOTE AS | | FOOTER/WALL/ENCLOSURE/SLAB DETAIL | | SUBMITTED DOES NOT CONTAIN ANY | | SIGNATURE,DATE OR SEAL BY THE DESIGNER | | OF RECORD. | | PLEASE SEE FS 471.025,481.221 | | FAC 61G15-23.002 | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY COMMENTS OR | | QUESTIONS, PLEASE DO NOT HESITATE IN | | CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-05-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-05-16 |
Time |
19:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-05-16 |
Time |
18:31 |
Sent To |
|
|
Notes |
2006-05-16 00:00:00 | ******** UNSAT ********* | | | | 1) NOTE: PLEASE SUBMIT ALL MANUFACTURES | | SPECS/CUT SHEETS FOR GENERATOR, ATS , | | MTS AND SUB BASE FUEL TANK. | | PLEASE KNOW, ALL MUST INDICATE LISTING | | FROM A NRTL. | | 215.5 | | | | 2) NOTE: PLEASE CORRELATE PLANS | | SUBMITTED. PLEASE SEE ONE SET INDICATES | | A 100 GAL TANK, AND THE OTHER 500 GAL | | TANK?? | | | | 3) NOTE: PLEASE SEE PLANS SHALL | | REFERENCE THE CURRENT CODES IN EFFECT | | AS, THE "LATEST EDITION" MAY NOT BE | | ADOPTED AT THIS TIME. | | WORK, PER 2002 NFPA-70, 2002 NFPA-110 | | 2004 FBC. | | | | 4) NOTE: PLEASE CLARIFY FEED TO THE 250A | | DISC FOR MTS SHOWING 3- 200A RECEPTS?? | | THE THREE RECEPTS ARE UNCLEAR. PLEASE | | ALSO SEE ALL DISCONNECTS, MAINS ETC ARE | | SHOWN AS 250A'S, YET THESE RECEPTS ARE | | SHOWN AS 200A'S? | | PLEASE SEE THE LOADS SHOWN SEEM TO BE | | OVER THE RATINGS OF THE 200A RECEPT? | | 215.5 | | | | 5) NOTE: PLEASE VERIFY TAPPED CONDUCTORS | | AS SHOWN PER 240.21, LENGTH? | | PLEASE SEE 450.3 FOR MAX OCP AT 125%. | | WHEN THE OCP DOES NOT CORRELATE, IT IS | | PERMITTED TO GO TO THE NEXT STANDARD | | SIZE PER 240.6. (25A'S). | | SHOWS 40A'S. | | | | 6) NOTE: PLEASE SEE THE MTS MUST CONTAIN | | A "OFF" POSITION AS THE MEANS OF | | DISCONNECT REQUIRED FOR POWER COMING | | FROM THE GEN. THE BRKR ON THE INSIDE OF | | THE GEN CAN NOT BE THE DISCONNECT MEANS | | FOR POWER IN EM CONDITIONS. | | 225.31-225.39. | | | | 7) NOTE: PLEASE SEE BLDG REVIEW, AS THE | | WIND LOAD CALCUALTIONS ARE REQUIRED AT | | THIS TIME FOR NEW LT POLE(S). | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY COMMENTS OR | | QUESTIONS, PLEASE DO NOT HESITATE IN | | CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2006-06-19 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2006-06-19 |
Time |
13:00 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2006-06-19 |
Time |
13:00 |
Sent To |
|
|
Notes |
2006-06-19 00:00:00 | 1. FUEL TANK IS TO COMPLY WITH | | APPROPRIATE NFPA STANDARDS SINCE IT WILL | | CONTAIN FUEL AND THE GENERATOR WILL REST | | ON TOP OF IT. UL LISTING WILL BE | | REQUIRED. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER | | 804-4709 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-05-19 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-05-19 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-05-19 |
Time |
11:27 |
Sent To |
|
|
Notes |
2006-05-19 00:00:00 | ***DENIED*** | | | | 1) PLEASE SUBMIT ALL REQUIRED | | MANUFACTURER SPEC SHEETS. SEE ELECTRICAL | | REVIEW NOTE #1. | | | | 2) IN ADDITION TO APPLICABLE BUILDING | | CODES, WORK SHALL COMPLY WITH NFPA 110, | | STANDARD FOR EMERGENCY AND STANDBY | | SYSTEMS. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
1 |
Status |
N |
Date |
2006-06-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-06-01 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-06-01 |
Time |
10:36 |
Sent To |
|
|
Notes |
2006-06-01 00:00:00 | SUB-BASE FUEL TANK NO FUEL LINES TO BE | | RUN ACCORDING TO THE PLANS. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2006-06-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-06-01 |
Time |
07:30 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-06-01 |
Time |
07:30 |
Sent To |
|
|
Notes |
2006-06-01 00:00:00 | GAS PERMIT NOT REQUIRED - GENERATOR IS | | DIESEL POWERED. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2006-08-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-08-11 |
Time |
08:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-08-11 |
Time |
08:59 |
Sent To |
E |
|
Notes |
2006-08-11 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2006-08-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-08-07 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-08-07 |
Time |
14:28 |
Sent To |
E |
|
Notes |
2006-08-07 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2006-07-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-07-13 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-07-13 |
Time |
14:50 |
Sent To |
|
|
Notes |
2006-07-13 00:00:00 | TO "COMM" BD#13-EXPEDITED PERMIT- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-06-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-06-14 |
Time |
17:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-06-14 |
Time |
17:26 |
Sent To |
|
|
Notes |
2006-06-14 00:00:00 | TO "COMM" BD#18--EXPEDITED PLANS-- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-05-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-05-16 |
Time |
14:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-05-16 |
Time |
14:45 |
Sent To |
|
|
Notes |
2006-05-16 00:00:00 | TO "COMM" BD#17---EXPEDITED PERMIT--- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-06-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-06-01 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-05-10 |
Time |
10:58 |
Sent To |
|
|
Notes |
2006-05-10 00:00:00 | TO "Z" BOX--EXPEDITED PERMIT-- |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2006-06-23 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-06-23 |
Time |
16:22 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2006-06-23 |
Time |
16:22 |
Sent To |
|
|
Notes |
2006-06-23 00:00:00 | COMMENTS FROM LAST REVIEW 6-1-06 HAVE | | BEEN ADDRESSED. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-06-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-06-01 |
Time |
09:37 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-06-01 |
Time |
09:37 |
Sent To |
|
|
Notes |
2006-06-01 00:00:00 | DENIED: | | | | 1.PER NFPA 110 CHAPTER 7 INSTALLATION | | OF EMERGENCY POWER SYSTEMS, SUB-SECTION | | 7.4.1.1 & MANUFACTURE'S INSTALLATION | | INSTRUCTIONS, A RAISED FOUNDATION OR | | SLAB OF 6 INCHES OR MORE ABOVE FLOOR | | LEVEL WILL MAKE SERVICING EASIER. | | | | 2.MANUFACTURE'S INSTALLATION | | INSTRUCTIONS INDICATE A MINIMUM OF 3 | | FEET CLEARANCE ON ALL SIDES OF THE | | GENERATOR SET.PLEASE INDICATE ON THE | | PLAN CLEARANCE AROUND THE GENERATOR. | | | | 3.THE MANUFACTURE SUBMITTAL & THE | | CONSTRUCTION PLANS INDICATE A 500 GALLON | | SUB-BASE FUEL TANK BUT THE ELECTRICAL | | SITE PLANS BY SMITH ENGINEERING | | CONSULTANTS, INC. INDICATE 100 GALLON | | SUB-BASE FUEL TANK. | | | | 4.PLEASE INDICATE IF THIS WILL HAVE A | | REMOTE FILL.PLEASE INDICATE FUEL | | SERVICE AND ACCESS FOR FILL PIPING. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6179 OR | | E-MAIL [email protected]. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2006-07-27 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2006-07-27 |
Time |
18:19 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2006-07-27 |
Time |
18:19 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2006-06-30 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2006-06-30 |
Time |
17:20 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2006-06-30 |
Time |
17:15 |
Sent To |
I |
|
Notes |
2006-06-30 00:00:00 | PLANNING AND ZONING: FAILED 5/16/06 AND | | 6/30/06 - RESUBMITTAL | | | | COMMENTS ARE STILL OUTSTANDING FROM LAST | | SUBMITTAL ON 5/16/06 | | | | 1.PROVIDE RESPONSES IN WRITING. | | | | 2.A MINOR AMENDMENT TO THE IBIS | | PLANNED DEVELOPMENT, MASTER PLAN IS | | REQUIRED. AN APPLICATION WILL NEED TO BE | | FILED TO THE PLANNING AND ZONING | | DEPARTMENT AND APPROVED PRIOR TO | | SIGN-OFF OF BLDG. PERMIT. | | | | SHOULD YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT: | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1435 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2006-05-16 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2006-05-16 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2006-05-16 |
Time |
14:13 |
Sent To |
I |
|
Notes |
2006-05-16 00:00:00 | PLANNING AND ZONING: FAILED | | | | | | 1.PROVIDE RESPONSES IN WRITING. | | | | 2.A MINOR AMENDMENT TO THE IBIS | | PLANNED DEVELOPMENT, MASTER PLAN IS | | REQUIRED. AN APPLICATION WILL NEED TO BE | | FILED TO THE PLANNING AND ZONING | | DEPARTMENT AND APPROVED PRIOR TO | | SIGN-OFF OF BLDG. PERMIT. | | | | SHOULD YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT: | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1435 |
|
|