Plan Review Details - Permit 06050448
Plan Review Stops For Permit 06050448
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-06-21 Cont ID  
Sent By lursu Date 2006-06-21 Time 16:58 Rev Time 0.00
Received By lmartine Date 2006-07-05 Time 13:28 Sent To  
Notes
2006-06-21 00:00:00FOR THIS PARCEL 74414224060020030 THE
 ADDRESS OF 7987 SANDHILL WAY E MUST BE
 USED UNDER THE OWNER OF NORTHERN PALM
 BEACH COUNTY IMPROV DISTRICT

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-11 Cont ID  
Sent By dpalmer Date 2006-08-11 Time 12:27 Rev Time 0.00
Received By dpalmer Date 2006-08-11 Time 12:27 Sent To  
Notes
2006-08-11 00:00:00PLANS STAMPED BY LUIS ON JULY 17TH
2006-07-15 00:00:00NEEDS BLDG REVIEW AND STAMPING AS A
 STRUCTURAL SHEET FOR WALLS AND SLAB ARE
 ATTACHED TO PLANS, BUT NOT SIGNED, OR
 STAMPED BY REVIEWER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-07-05 Cont ID  
Sent By lmartine Date 2006-07-05 Time 13:29 Rev Time 0.00
Received By lmartine Date 2006-07-05 Time 13:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-21 Cont ID  
Sent By shill Date 2006-06-21 Time 06:33 Rev Time 0.00
Received By shill Date 2006-06-21 Time 06:33 Sent To  
Notes
2006-06-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)AN INCORRECT ADDRESS WAS PROVIDED
 ON THE APPLICATION.PLEASE REVISE.THE
 CORRECT ADDRESS IS 7987 SANDHILL WAY E.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-24 Cont ID  
Sent By shill Date 2006-05-24 Time 07:32 Rev Time 0.00
Received By shill Date 2006-05-24 Time 07:37 Sent To  
Notes
2006-05-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)AN INCORRECT PARCEL ID WAS PROVIDED
 ON THE APPLICATION.PLEASE REVISE.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-08-11 Cont ID  
Sent By dpalmer Date 2006-08-11 Time 12:52 Rev Time 0.00
Received By dpalmer Date 2006-08-11 Time 12:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-08-07 Cont ID  
Sent By dpalmer Date 2006-08-07 Time 14:51 Rev Time 0.00
Received By dpalmer Date 2006-08-07 Time 14:32 Sent To B
Notes
2006-08-07 00:00:00*** UNSAT 4THR REVIEW **
  
 1) NOTE: PLEASE SEE THE MTS
 SPECIFICATIONS SUBMITTED ARE NOW
 COMPLETELY DIFFERENT FROM PLANS/RISER.
 PLEASE SEE RISER SHOWS A 250A MTS. WE
 NEED EITHER SPEC FOR A 250A MTS OR
 REVISE PLANS TO CORRLELATE WITH
 SUBMITTIALS.
 THIS WAS REQUESTED ON THREE PREVIOUS
 REVIEWS AND ONE REVIEW DONE WITH OUT
 PLANS BEING SUBMITTED.
 THIS OFFICE HAS SPOKE TO THE ELECTRICAL
 CONTRACTOR AND THE ELECTRICAL ENGINEER
 ON MORE THAN ONE OCCASION.
 PLEASE KNOW THIS OFFICE HAS ALSO LEFT
 TWO MESSAGES FOR THE ENGINEER ON THE
 OFFICE VOICE MAIL AND THE CELL PHONE
 VOICE MAIL.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 13:43 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 13:26 Sent To  
Notes
2006-07-15 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE NOTES ONE AND 6 FROM
 PREVIOUS REVIEW.
 PLEASE SEE THRESS SETS OF PLANS ARE
 BEING SUBMITTED, HOWEVER NOW ONLY TWO
 SETS OF SPECS ARE BEING SUBMITTED.
 PLEASE SEE SPECS FOR MTS HAS HAND TYPED
 NOTE ON MANUFACTURES SPECS/CUT SHEETS
 WHICH MENTIONS A OFF POSITION???
 RISER DOES NOT INDCIATE THIS AND SPECS
 FROM MANUFACTURE MAY NOT HAVE ITEMS
 TYPED AND ADDED TO SPEC WHICH DI NOT
 ORIGINATE FROM MANUFACTURE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-16 Cont ID  
Sent By dpalmer Date 2006-06-16 Time 18:14 Rev Time 0.00
Received By dpalmer Date 2006-06-16 Time 17:57 Sent To  
Notes
2006-06-16 00:00:00*** UNSAT 2ND REVIEW ***
  
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW AND SOME NEW COMMENTS.
 PLEASE SEE PREVIOUS REVIEW COMMENTS ARE
 TAKEN DIRECTLY FROM PREVIOUS REVIEW WITH
 NEW NOTES ADDED AT THE BOTTOM.
  
  
 ******** UNSAT *********
  
 1) NOTE:NOTE #1 NO, PLEASE SEE ONLY
 ONE COPY OF SPEC/MANUFACTURES CUT SHEETS
 WERE SUBMITTED FOR THE GENERATORS. NO
 SPECS/CUT SHEETS WERE SUBMITTED FOR THE
 MTS, ATS, FUEL TANK.???
 PLEASE SEE SOME ITEMS FOR CODE
 COMPLIANCE CAN NOT BE VERIFIED AT THIS
 TIME.
 ** PLEASE KNOW, TWO COPIES OF ALL MUST
 BE SUBMITTED. THREE COMPLETE SETS MAY BE
 SUBMITTED, HOWEVER ONLY TWO ARE
 REQUIRED. UP TO THREE SETS WILL BE
 STAMPED.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR GENERATOR, ATS ,
 MTS AND SUB BASE FUEL TANK.
 PLEASE KNOW, ALL MUST INDICATE LISTING
 FROM A NRTL.
 215.5
  
 2) NOTE: NOTE #2 OK,HOWEVER PLEASE STILL
 SEE INFORMATION FOR TANK(S) HAVE NOT
 BEEN SUBMITTED.
  
 3) NOTE: OK
  
 4) NOTE: OK
  
 5) NOTE: OK..
  
 6) NOTE: NOTE #6, NO, RISER DOES NOT
 SHOW THIS AND SPECS WERE NOT SUBMITTED.
 RESPONSE MENTIONS CIRCUIT BRKR, YET THIS
 BREAKE RIS SHOWN FROM THE RECEPTS WHICH
 IS CLEAR AND OK. PLEASE SEE HOWEVER IF
 SYSTEM IS SET UP ON AN AUTOMATIC
 TRANSFER A MANUAL MEANS OF DISCONNECT
 SHALL BE REQUIRED FOR FEEDERS COMING
 FROM GEN.
  
  
 ** PREVIOUS NOTE **
 PLEASE SEE THE MTS MUST CONTAIN
 A "OFF" POSITION AS THE MEANS OF
 DISCONNECT REQUIRED FOR POWER COMING
 FROM THE GEN. THE BRKR ON THE INSIDE OF
 THE GEN CAN NOT BE THE DISCONNECT MEANS
 FOR POWER IN EM CONDITIONS.
 225.31-225.39.
  
 7) NOTE: OK, AS LT POLE WAS REMOVED FROM
 PLANS.
  
 *** NEW NOTE**
  
 8) NOTE: PLEASE SEE BUILDING NOTE AS
 FOOTER/WALL/ENCLOSURE/SLAB DETAIL
 SUBMITTED DOES NOT CONTAIN ANY
 SIGNATURE,DATE OR SEAL BY THE DESIGNER
 OF RECORD.
 PLEASE SEE FS 471.025,481.221
 FAC 61G15-23.002
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY COMMENTS OR
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-16 Cont ID  
Sent By dpalmer Date 2006-05-16 Time 19:03 Rev Time 0.00
Received By dpalmer Date 2006-05-16 Time 18:31 Sent To  
Notes
2006-05-16 00:00:00******** UNSAT *********
  
 1) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR GENERATOR, ATS ,
 MTS AND SUB BASE FUEL TANK.
 PLEASE KNOW, ALL MUST INDICATE LISTING
 FROM A NRTL.
 215.5
  
 2) NOTE: PLEASE CORRELATE PLANS
 SUBMITTED. PLEASE SEE ONE SET INDICATES
 A 100 GAL TANK, AND THE OTHER 500 GAL
 TANK??
  
 3) NOTE: PLEASE SEE PLANS SHALL
 REFERENCE THE CURRENT CODES IN EFFECT
 AS, THE "LATEST EDITION" MAY NOT BE
 ADOPTED AT THIS TIME.
 WORK, PER 2002 NFPA-70, 2002 NFPA-110
 2004 FBC.
  
 4) NOTE: PLEASE CLARIFY FEED TO THE 250A
 DISC FOR MTS SHOWING 3- 200A RECEPTS??
 THE THREE RECEPTS ARE UNCLEAR. PLEASE
 ALSO SEE ALL DISCONNECTS, MAINS ETC ARE
 SHOWN AS 250A'S, YET THESE RECEPTS ARE
 SHOWN AS 200A'S?
 PLEASE SEE THE LOADS SHOWN SEEM TO BE
 OVER THE RATINGS OF THE 200A RECEPT?
 215.5
  
 5) NOTE: PLEASE VERIFY TAPPED CONDUCTORS
 AS SHOWN PER 240.21, LENGTH?
 PLEASE SEE 450.3 FOR MAX OCP AT 125%.
 WHEN THE OCP DOES NOT CORRELATE, IT IS
 PERMITTED TO GO TO THE NEXT STANDARD
 SIZE PER 240.6. (25A'S).
 SHOWS 40A'S.
  
 6) NOTE: PLEASE SEE THE MTS MUST CONTAIN
 A "OFF" POSITION AS THE MEANS OF
 DISCONNECT REQUIRED FOR POWER COMING
 FROM THE GEN. THE BRKR ON THE INSIDE OF
 THE GEN CAN NOT BE THE DISCONNECT MEANS
 FOR POWER IN EM CONDITIONS.
 225.31-225.39.
  
 7) NOTE: PLEASE SEE BLDG REVIEW, AS THE
 WIND LOAD CALCUALTIONS ARE REQUIRED AT
 THIS TIME FOR NEW LT POLE(S).
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY COMMENTS OR
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-06-19 Cont ID  
Sent By mcarsill Date 2006-06-19 Time 13:00 Rev Time 0.00
Received By mcarsill Date 2006-06-19 Time 13:00 Sent To  
Notes
2006-06-19 00:00:001. FUEL TANK IS TO COMPLY WITH
 APPROPRIATE NFPA STANDARDS SINCE IT WILL
 CONTAIN FUEL AND THE GENERATOR WILL REST
 ON TOP OF IT. UL LISTING WILL BE
 REQUIRED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-19 Cont ID  
Sent By mwennerg Date 2006-05-19 Time 11:27 Rev Time 0.00
Received By mwennerg Date 2006-05-19 Time 11:27 Sent To  
Notes
2006-05-19 00:00:00***DENIED***
  
 1) PLEASE SUBMIT ALL REQUIRED
 MANUFACTURER SPEC SHEETS. SEE ELECTRICAL
 REVIEW NOTE #1.
  
 2) IN ADDITION TO APPLICABLE BUILDING
 CODES, WORK SHALL COMPLY WITH NFPA 110,
 STANDARD FOR EMERGENCY AND STANDBY
 SYSTEMS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-06-01 Cont ID  
Sent By pkrauss Date 2006-06-01 Time 10:36 Rev Time 0.00
Received By pkrauss Date 2006-06-01 Time 10:36 Sent To  
Notes
2006-06-01 00:00:00SUB-BASE FUEL TANK NO FUEL LINES TO BE
 RUN ACCORDING TO THE PLANS.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-06-01 Cont ID  
Sent By kstevens Date 2006-06-01 Time 07:30 Rev Time 0.00
Received By kstevens Date 2006-06-01 Time 07:30 Sent To  
Notes
2006-06-01 00:00:00GAS PERMIT NOT REQUIRED - GENERATOR IS
 DIESEL POWERED.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 08:59 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 08:59 Sent To E
Notes
2006-08-11 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-07 Cont ID  
Sent By adarroug Date 2006-08-07 Time 14:28 Rev Time 0.00
Received By adarroug Date 2006-08-07 Time 14:28 Sent To E
Notes
2006-08-07 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-13 Cont ID  
Sent By adarroug Date 2006-07-13 Time 14:50 Rev Time 0.00
Received By adarroug Date 2006-07-13 Time 14:50 Sent To  
Notes
2006-07-13 00:00:00TO "COMM" BD#13-EXPEDITED PERMIT-

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 17:26 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 17:26 Sent To  
Notes
2006-06-14 00:00:00TO "COMM" BD#18--EXPEDITED PLANS--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-16 Cont ID  
Sent By adarroug Date 2006-05-16 Time 14:45 Rev Time 0.00
Received By adarroug Date 2006-05-16 Time 14:45 Sent To  
Notes
2006-05-16 00:00:00TO "COMM" BD#17---EXPEDITED PERMIT---

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-01 Cont ID  
Sent By pkrauss Date 2006-06-01 Time 10:45 Rev Time 0.00
Received By pkrauss Date 2006-05-10 Time 10:58 Sent To  
Notes
2006-05-10 00:00:00TO "Z" BOX--EXPEDITED PERMIT--

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-23 Cont ID  
Sent By tgordon Date 2006-06-23 Time 16:22 Rev Time 0.45
Received By tgordon Date 2006-06-23 Time 16:22 Sent To  
Notes
2006-06-23 00:00:00COMMENTS FROM LAST REVIEW 6-1-06 HAVE
 BEEN ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-01 Cont ID  
Sent By pkrauss Date 2006-06-01 Time 09:37 Rev Time 0.00
Received By pkrauss Date 2006-06-01 Time 09:37 Sent To  
Notes
2006-06-01 00:00:00DENIED:
  
 1.PER NFPA 110 CHAPTER 7 INSTALLATION
 OF EMERGENCY POWER SYSTEMS, SUB-SECTION
 7.4.1.1 & MANUFACTURE'S INSTALLATION
 INSTRUCTIONS, A RAISED FOUNDATION OR
 SLAB OF 6 INCHES OR MORE ABOVE FLOOR
 LEVEL WILL MAKE SERVICING EASIER.
  
 2.MANUFACTURE'S INSTALLATION
 INSTRUCTIONS INDICATE A MINIMUM OF 3
 FEET CLEARANCE ON ALL SIDES OF THE
 GENERATOR SET.PLEASE INDICATE ON THE
 PLAN CLEARANCE AROUND THE GENERATOR.
  
 3.THE MANUFACTURE SUBMITTAL & THE
 CONSTRUCTION PLANS INDICATE A 500 GALLON
 SUB-BASE FUEL TANK BUT THE ELECTRICAL
 SITE PLANS BY SMITH ENGINEERING
 CONSULTANTS, INC. INDICATE 100 GALLON
 SUB-BASE FUEL TANK.
  
 4.PLEASE INDICATE IF THIS WILL HAVE A
 REMOTE FILL.PLEASE INDICATE FUEL
 SERVICE AND ACCESS FOR FILL PIPING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6179 OR
 E-MAIL [email protected].

Review Stop Z ZONING
Rev No 3 Status P Date 2006-07-27 Cont ID  
Sent By lfranco Date 2006-07-27 Time 18:19 Rev Time 0.00
Received By lfranco Date 2006-07-27 Time 18:19 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-06-30 Cont ID  
Sent By lfranco Date 2006-06-30 Time 17:20 Rev Time 0.00
Received By lfranco Date 2006-06-30 Time 17:15 Sent To I
Notes
2006-06-30 00:00:00PLANNING AND ZONING: FAILED 5/16/06 AND
 6/30/06 - RESUBMITTAL
  
 COMMENTS ARE STILL OUTSTANDING FROM LAST
 SUBMITTAL ON 5/16/06
  
 1.PROVIDE RESPONSES IN WRITING.
  
 2.A MINOR AMENDMENT TO THE IBIS
 PLANNED DEVELOPMENT, MASTER PLAN IS
 REQUIRED. AN APPLICATION WILL NEED TO BE
 FILED TO THE PLANNING AND ZONING
 DEPARTMENT AND APPROVED PRIOR TO
 SIGN-OFF OF BLDG. PERMIT.
  
 SHOULD YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT:
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2006-05-16 Cont ID  
Sent By lfranco Date 2006-05-16 Time 14:13 Rev Time 0.00
Received By lfranco Date 2006-05-16 Time 14:13 Sent To I
Notes
2006-05-16 00:00:00PLANNING AND ZONING: FAILED
  
  
 1.PROVIDE RESPONSES IN WRITING.
  
 2.A MINOR AMENDMENT TO THE IBIS
 PLANNED DEVELOPMENT, MASTER PLAN IS
 REQUIRED. AN APPLICATION WILL NEED TO BE
 FILED TO THE PLANNING AND ZONING
 DEPARTMENT AND APPROVED PRIOR TO
 SIGN-OFF OF BLDG. PERMIT.
  
 SHOULD YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT:
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435