Plan Review Details - Permit 06050324
Plan Review Stops For Permit 06050324
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-10 Cont ID  
Sent By mjacobs Date 2006-05-10 Time 15:44 Rev Time 0.00
Received By mjacobs Date 2006-05-10 Time 15:39 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By mjacobs Date 2006-05-08 Time 13:49 Rev Time 0.00
Received By mjacobs Date 2006-05-08 Time 13:47 Sent To PC
Notes
2006-05-08 00:00:00 
 1) THE SYSTEM SELECTED STATES GENERAL
 LIMITATION #7. GENERAL LIMITATION #7
 REQUIRES CALCULATIONS PREPARED, SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER/ARCHITECT OR ROOF
 CONSULTANT. THE CALCULATION SHALL
 INDICATE HOW THE ROOF PRESSURES WILL
 MEET THE MINIUM REQUIRED PRESSURE OF
 89PSF IN ZONE '3'.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726