Plan Review Details - Permit 06050232
Plan Review Stops For Permit 06050232
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-14 Cont ID  
Sent By shill Date 2006-06-14 Time 14:12 Rev Time 0.00
Received By shill Date 2006-06-14 Time 14:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By shill Date 2006-05-31 Time 16:49 Rev Time 0.00
Received By shill Date 2006-05-31 Time 16:49 Sent To  
Notes
2006-05-31 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)31.2 WAS CIRCLED ON THE PRODUCT
 APPROVAL SPECIFICATION.THIS PRESSURE
 IS TOO LOW FOR 140MPH, FBC TABLE
 1609.6B.
  
 2.)INDICATE ON THE PRODUCT APPROVAL OR
 ON THE INSTALLATION SCHEDULE WHICH
 CONNECTION TYPE YOU ARE USING AS NOT ALL
 OF THEM ARE COMPLIANT FOR THE ANCHOR
 SPACING YOU HAVE SPECIFIED (12"/12").

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 16:33 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 16:33 Sent To B
Notes
2006-06-08 00:00:00TO "SHILL "DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-31 Cont ID  
Sent By shill Date 2006-05-31 Time 16:55 Rev Time 0.00
Received By shill Date 2006-05-06 Time 16:36 Sent To  
Notes
2006-05-06 00:00:00TO "MISC" BOX#1