Plan Review Details - Permit 06050047
Plan Review Stops For Permit 06050047
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-09 Cont ID  
Sent By lmartine Date 2007-03-09 Time 14:19 Rev Time 0.00
Received By lmartine Date 2007-03-07 Time 18:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-23 Cont ID  
Sent By amorse Date 2006-06-23 Time 15:35 Rev Time 0.75
Received By amorse Date 2006-06-23 Time 15:35 Sent To PC
Notes
2006-06-23 00:00:00 
 DENIED
  
 1) PROVIDE WINDOW AND DOOR SIZE FOR
 REQUIRED MAX ALLOWED IN NOA'S
  
 2) PROVIDE PRODUCT APPROVAL FOR WINDOW
 MULLIONS BE AWARE THAT SIMONTON WINDOWS
 NOA HAS MAX LENGTH OF 74"
  
 3) PROVIDE GLASS TYPE FOR WINDOWS, NOT
 ALL TYPES WILL MEET DESIGN PRESSURES
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-12 Cont ID  
Sent By amorse Date 2006-05-12 Time 15:47 Rev Time 0.75
Received By amorse Date 2006-05-12 Time 15:47 Sent To  
Notes
2006-05-12 00:00:00 
  
 DENIED
  
 1) ENGINEER SHALL SIGN, SEAL & DATE
 SHEETS AND SHALL ALSO LEGIBLY INDICATE
 NAME, ADDRESS & LICENCE NUMBER PER
 61G15-23.002(2) FAC
  
 2) PROVIDE PROOF OF OWNERSHIP (DEED, TAX
 BILL, ETC.) PAPA AND OUR SYSTEM HAS
 OWNER OF PROPERTY AS ZAHAVA INC.
  
 3) SCOPE OF WORK DOES NOT PROVIDE ENOUGH
 DETAIL OF WORK TO BE PERFORMED. SUBMIT
 DRAWINGS THAT ADEQUATELY SHOWS WORK THAT
 WILL BE UNDERTAKEN. REQUIRE DETAILS ON
 EXTERIOR WALL CONSTRUCTION AND WINDOW
 OPENING SIZES FOR DESIGN PRESSURES,
 WILLTHEY NEED A BUCK DETAIL, IF ENTRY
 DOOR IS REPLACED SIZE & PRODUCT APPROVAL
 IS REQUIRED. ALSO SCOPE OF WORK DOES NOT
 COVER ANY RECONFIGURATION OF WALLS ETC
 IN UNIT OR REMOVAL OR WORK ON FIRE
 SEPARATION WALL. ALL THIS WORK IS BETTER
 REPRESENTED WITH DRAWINGS
  
 4) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-21 Cont ID  
Sent By btrobaug Date 2006-06-21 Time 19:54 Rev Time 0.50
Received By btrobaug Date 2006-06-21 Time 19:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By btrobaug Date 2006-05-08 Time 17:19 Rev Time 0.50
Received By btrobaug Date 2006-05-08 Time 17:14 Sent To  
Notes
2006-05-08 00:00:00 
 PLEASE SUBMIT PLANS FOR THE PORTION OF
 THE UNIT BEING "REWIRED".
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-06-26 Cont ID  
Sent By nmccray Date 2006-06-26 Time 10:40 Rev Time 0.00
Received By nmccray Date 2006-06-26 Time 10:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-15 Cont ID  
Sent By nmccray Date 2006-05-15 Time 14:22 Rev Time 0.00
Received By nmccray Date 2006-05-15 Time 13:39 Sent To  
Notes
2006-05-15 00:00:00**********DENIED***************
  
 1) SHALL COMPLY NFPA 101 LIFE SAFETY
 CODE, 2003 EDITION, CHAPTER 30 NEW
 APARTMENT BUILDINGS.
  
 2) DEMOLITION, RENOVATION AND
 CONSTRUCTION SHALL COMPLY WITH NFPA 241.
  
 3) PLEASE SUBMIT PLANS SHOWING EXISTING
 AND NEW SMOKE DETECTORS.
  
 4) THE INTERIOR FINISH FOR WALLS AND
 CEILINGS COMPLYING WITH SECTION 10.2
 SHALL BE CLASS A, CLASS B, OR CLASS C.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-21 Cont ID  
Sent By adarroug Date 2007-06-21 Time 09:11 Rev Time 0.00
Received By adarroug Date 2007-06-21 Time 09:11 Sent To E
Notes
2007-06-21 09:12:27TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-13 Cont ID  
Sent By adarroug Date 2007-01-13 Time 13:36 Rev Time 0.00
Received By adarroug Date 2007-01-13 Time 13:36 Sent To B
Notes
2007-01-13 13:37:20TO "LMARTINEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 11:44 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 11:44 Sent To  
Notes
2006-06-21 00:00:00WAITING FOR "BOB"
 TO "BOB"#17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-15 Cont ID  
Sent By adarroug Date 2006-05-15 Time 11:44 Rev Time 0.00
Received By rbrown Date 2006-05-02 Time 12:31 Sent To  
Notes
2006-05-06 00:00:00TO "BOB"15
2006-05-02 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-23 Cont ID  
Sent By tgordon Date 2006-06-23 Time 10:23 Rev Time 0.30
Received By tgordon Date 2006-06-23 Time 10:23 Sent To  
Notes
2006-06-23 00:00:00*** PROVISO ***
 1) PROVIDE AN AUXILIARY DRAIN PAN UNDER
 AHU, PER 2004 FBC/R M1411.3.1 .
 2) PROVIDE BALANCE RETURN AIR FOR
 BEDROOMS,PER 2004 FBC/R M1602.4 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-09 Cont ID  
Sent By tgordon Date 2006-05-09 Time 10:57 Rev Time 0.20
Received By tgordon Date 2006-05-09 Time 10:56 Sent To  
Notes
2006-05-09 00:00:00*** DENIED ***
 1) PLEASE SUBMIT PLANS FOR REVIEWTO
 SHOW WHAT A/C MECHANICAL WORK IS TO BE
 DONE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-06-24 Cont ID  
Sent By pschmitz Date 2006-06-24 Time 14:06 Rev Time 0.00
Received By pschmitz Date 2006-06-24 Time 14:05 Sent To  
Notes
2006-06-24 00:00:00PROVISO:
 REPLACE EXISTING FIXTURES ONLY.
 NOTE #6 REFERENCE TO AIR CHAMBERS
 DELETED.
 SEC 604.9 WATER HAMMER ARRESTORS ADDED
 TO NOTE #6.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-15 Cont ID  
Sent By jleech Date 2006-05-15 Time 15:16 Rev Time 0.00
Received By jleech Date 2006-05-15 Time 15:16 Sent To  
Notes
2006-05-15 00:00:00DENIED;
 SUBMIT A PLAN SHOWING THE SCOPE OF
 PLUMBING WORK TO BE DONE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695