Plan Review Details - Permit 06050037
Plan Review Stops For Permit 06050037
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-07 Cont ID  
Sent By rmcdouga Date 2006-06-07 Time 14:47 Rev Time 0.00
Received By rmcdouga Date 2006-06-07 Time 14:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-02 Cont ID  
Sent By rmcdouga Date 2006-05-02 Time 08:05 Rev Time 0.00
Received By rmcdouga Date 2006-05-02 Time 08:05 Sent To  
Notes
2006-05-02 00:00:00DENIED
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE
 BUILDING ON THE APPLICATION.
  
 2) CIRCLE THE FASTENING OPTION THAT YOU
 WILL USE ON SHEET 17 OF THE NOA FOR THE
 MODIFIED SYSTEM.
  
 3) THE PRESSURES LISTED FOR THE MODIFIED
 SYSTEM. WILL NOT MEET THE REQUIRED
 COMPONENT AND CLADDING WIND LOADS LISTED
 IN FBC TABLE 1609.6B. THEREFORE,
 ENHANCED FASTENING IS REQUIRED, SEE
 LIMITATION #7. LIMITATION #7 ON SHEET 20
 OF THE NOA REQUIRES THE CALCULATIONS FOR
 FASTENER DENSITIES TO BE DONE BY AN
 ENGINEER, ARCHITECT OR REGISTERED ROOF
 CONSULTANT. SUBMIT RAS 117 CALCULATIONS
 SIGNED AND SEALED BY AN ENGINEER,
 ARCHITECT OR REGISTERED ROOF CONSULTANT.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714