Plan Review Details - Permit 06041267
Plan Review Stops For Permit 06041267
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-27 Cont ID  
Sent By alange Date 2006-06-27 Time 11:14 Rev Time 0.50
Received By alange Date 2006-06-27 Time 11:04 Sent To  
Notes
2006-06-27 00:00:00REVISION... ROOF SCREEN
 REMOVEDOK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-15 Cont ID  
Sent By alange Date 2006-06-15 Time 16:00 Rev Time 1.50
Received By alange Date 2006-06-15 Time 16:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-12 Cont ID  
Sent By alange Date 2006-05-12 Time 08:17 Rev Time 1.50
Received By alange Date 2006-05-12 Time 08:17 Sent To  
Notes
2006-05-12 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 3.PRODUCT APPROVALS REQUIRED FOR
 EXTERIOR DOORS AND WINDOWS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 5.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 6.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 7.SHOW ELEVATION DETAIL OF RECEPTION
 COUNTER AREA.
  
 8.CONSTRUCTION TYPE SHOWN IS NOT
 CORRECT.
  
 9.INCLUDE A LIFE SAFTEY PLAN.
  
 10.SEPERATE ROOFING PERMIT REQUIRED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-12 Cont ID  
Sent By btrobaug Date 2006-06-12 Time 12:31 Rev Time 1.00
Received By btrobaug Date 2006-06-12 Time 09:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-04 Cont ID  
Sent By btrobaug Date 2006-05-04 Time 09:50 Rev Time 1.00
Received By btrobaug Date 2006-05-04 Time 07:53 Sent To  
Notes
2006-05-04 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE COMPLETE THE CODE SUMMARY ON
 SHEET 1.1. ALSO NOTE THAT THE REFERENCE
 TO THE "ELECTRICAL CODE BEING THE
 "LATEST EDITION " IS INCORRECT AS TH
 ESTATE OF FLORIDA IS CURRENTLY ENFORCING
 THE LAST ADOPTED EDITION WHICH IS 2002.
 THE CURRENT EDITION IS 2005.
  
 2} PROVIDE A LOAD CALCULATION PER
 ARTICLE 220 2002 NEC, INDICATE THE SIZE
 OF THE BUILDING SERVICE, AND SHOW THE
 CALCULATION FOR THIS PROJECT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-05-09 Cont ID  
Sent By mwennerg Date 2006-05-09 Time 09:46 Rev Time 0.00
Received By mwennerg Date 2006-05-09 Time 09:46 Sent To  
Notes
2006-05-09 00:00:00******APPROVED******
  
 1) IF SPACE IS EQUIPED WITH FIRE ALARM,
 DUCT SMOKE DETECTORS REQUIRED TO BE TIED
 INTO SYSTEM, AND INITIATE GENERAL ALARM
 IN ACCORDANCE WITH LOCAL REQUIREMENTS.
 IF NO FIRE ALARM SYSTEM, AUDIBLE/VISUAL
 DEVICES STILL REQUIRED FOR OCCUPANT
 NOTIFICATION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-25 Cont ID  
Sent By adarroug Date 2006-06-25 Time 17:23 Rev Time 0.00
Received By adarroug Date 2006-06-25 Time 17:23 Sent To B
Notes
2006-06-25 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-31 Cont ID  
Sent By adarroug Date 2006-05-31 Time 10:58 Rev Time 0.00
Received By adarroug Date 2006-05-31 Time 10:58 Sent To  
Notes
2006-06-14 00:00:006/14/06-MOVED FROM "BOB"#1 TO "ALANGE"
 DESK
2006-05-31 00:00:00TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-12 Cont ID  
Sent By alange Date 2006-05-12 Time 08:27 Rev Time 0.00
Received By alange Date 2006-05-01 Time 12:04 Sent To  
Notes
2006-05-01 00:00:00WAITING FOR "BOB"
 TO "BOB"#14

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-07-25 Cont ID  
Sent By pkrauss Date 2006-07-25 Time 14:08 Rev Time 0.00
Received By pkrauss Date 2006-07-25 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-01 Cont ID  
Sent By tgordon Date 2006-06-01 Time 08:03 Rev Time 0.25
Received By tgordon Date 2006-06-01 Time 08:03 Sent To  
Notes
2006-06-01 00:00:00RE-STAMP MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-05-04 Cont ID  
Sent By tgordon Date 2006-05-04 Time 12:20 Rev Time 0.30
Received By tgordon Date 2006-05-04 Time 12:20 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2006-06-12 Cont ID  
Sent By jleech Date 2006-06-12 Time 07:27 Rev Time 0.00
Received By jleech Date 2006-06-12 Time 07:27 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2006-05-05 Cont ID  
Sent By jleech Date 2006-05-05 Time 14:27 Rev Time 0.00
Received By jleech Date 2006-05-05 Time 14:27 Sent To  
Notes
2006-05-05 00:00:00DENIED;
 NO INFORMATION;
 1.SHOW MEDICAL GAS SYSTEM IN DETAIL.
 RISER DIAGRAM REQUIRED FOR VACUUM SYSTEM
 AND OXYGEN LINE. SIZE PIPES, LIST
 MATERIAL TYPE, SPECIFY WARNING SYSTEM TO
 BE USED. OXYGEN LINES TO BE PURGED WHEN
 BRAZING.
 2.SHOW DETAILOF VACUUM PUMP EQUIPMENT TO
 COMPLY WITH NFPA 99C 2002 EDITION FIG.
 5.3.3.6(A) THRU (D).
 3.(ADD NOTE) MED-GAS UNDER SEPARATE
 PERMIT APPLICATION BY CERTIFIED MEDICAL
 GAS CONTRACTOR.
 4.LABLE MECHANICAL ROOM DOOR PER
 SEC.5.3.3.1.6. ( ADD NOTE TO PLANS)
 5.SHOW SIZE AND NUMBER OF OXYGEN
 CYLINDERS TO BE INSTALLED AND HOW THEY
 WILL BE SECURED.
 MED-GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-06-12 Cont ID  
Sent By jleech Date 2006-06-12 Time 07:27 Rev Time 0.00
Received By jleech Date 2006-06-12 Time 07:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-05 Cont ID  
Sent By jleech Date 2006-05-05 Time 13:57 Rev Time 0.00
Received By jleech Date 2006-05-05 Time 13:57 Sent To  
Notes
2006-05-05 00:00:00DENIED;
 1.PAGE 8.2 ELEVATION #5 BREAK SINK TO
 COMPLY WITH FBC-2004 CHAPTER 11 SEC.
 11-4.23.3 KNEE CLEARANCE, 27"HIGH 30"
 WIDE AND 19" DEEP FOR FRONTAL APPROACH.
 11-4.24.6 RAP EXPOSED PIPES, 11-4.23.7
 LEVER OPERATED FAUCET REQUIRED. (SHOW
 DETAIL).
 2.SANITARY AND WATER ISOMETRIC DIAGRAMS
 SHOW P-9 SINKS IN ROOMS 104, 105, 107,
 AND 108. FLAT DRAWING SHOWS P-2.
 DISCRIPTION OF P-9 REQUIRED ON DRAWINGS.
 3.SHOW TOTAL OCCUPENCY FOR COMPLIANCE TO
 FBC-2004 PLUMBING TABLE 403.1(2B).
 4.A DRINKING FOUNTAIN IS REQUIRED. SHALL
 COMPLY WITH SECTION 410 AND
 ACCESSIBILITY CODE SEC. 11-4.1.3(10).
 SHOW DETAIL ON DRAWING.
 5.A WASTE AND VENT BRANCH IS REQUIRED
 FOR VACUUM EQUIPMENT SEC. 713.7.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  