Plan Review Details - Permit 06041193
Plan Review Stops For Permit 06041193
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-13 Cont ID  
Sent By lmartine Date 2007-02-13 Time 18:25 Rev Time 0.00
Received By lmartine Date 2007-02-13 Time 18:25 Sent To  
Notes
2007-02-13 18:26:34APPROVED BY J. WITMER ON 1/19/07 , SEE PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-19 Cont ID  
Sent By jwitmer Date 2006-09-19 Time 11:52 Rev Time 0.77
Received By jwitmer Date 2006-09-19 Time 11:52 Sent To  
Notes
2006-09-19 00:00:00PERMIT: 06041193
 ADD: 410 EVERNIA ST
 CONT: MEISNER ELECTRIC
 TEL: (561)278-8362
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
 1) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By jwitmer Date 2006-05-31 Time 07:34 Rev Time 0.77
Received By jwitmer Date 2006-05-31 Time 07:34 Sent To  
Notes
2006-05-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06041193
 ADD: 410 EVERNIA ST
 CONT: MEISNER ELECTRIC
 TEL: (561)278-8362
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
 1) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 2)PROVIDE PLANS ENOUGH TO VERIFY
 LOCATION OF GENERATOR VERSES BUILDING
 OPENINGS WINDOWS, DOORS OR SOFFIT TYPE
 VENTS, ETC.
  
 MECHANICAL CODE
 804.3.4 HORIZONTAL TERMINATIONS.
 HORIZONTAL TERMINATIONS SHALL COMPLY
 WITH THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO
 WALKWAYS, THE TERMINATION OF MECHANICAL
 DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3
 FEET (914 MM) ABOVE ANY FORCED AIR INLET
 LOCATED WITHIN 10 FEET (3048 MM).
 3.THE VENT SYSTEM SHALL TERMINATE
 AT LEAST 4 FEET (1219 MM) BELOW, 4 FEET
 (1219 MM) HORIZONTALLY FROM OR 1 FOOT
 (305 MM) ABOVE ANY DOOR, WINDOW OR
 GRAVITY AIR INLET INTO THE BUILDING.
 4.THE VENT TERMINATION POINT SHALL
 NOT BE LOCATED CLOSER THAN 3 FEET (914
 MM) TO AN INTERIOR CORNER FORMED BY TWO
 WALLS PERPENDICULAR TO EACH OTHER.
 5.THE VENT TERMINATION SHALL NOT BE
 MOUNTED DIRECTLY ABOVE OR WITHIN 3 FEET
 (914 MM) HORIZONTALLY FROM AN OIL TANK
 VENT OR GAS METER.
 6.THE BOTTOM OF THE VENT
 TERMINATION SHALL BE LOCATED AT LEAST 12
 INCHES (305 MM) ABOVE FINISHED GRADE.
  
 804.3.5 VERTICAL TERMINATIONS.
 VERTICAL TERMINATIONS SHALL COMPLY WITH
 THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO
 WALKWAYS, THE TERMINATION OF MECHANICAL
 DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3
 FEET (914 MM) ABOVE ANY FORCED AIR INLET
 LOCATED WITHIN 10 FEET (3048 MM).
 3.WHERE THE VENT TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF
 STRUCTURE, THE TERMINATION POINT SHALL
 BE LOCATED AT LEAST 3 FEET (914 MM) FROM
 SUCH STRUCTURE.
 4.THE VENT SHALL TERMINATE AT LEAST
 4 FEET (1219 MM) BELOW, 4 FEET (1219 MM)
 HORIZONTALLY FROM, OR 1 FOOT (305 MM)
 ABOVE ANY DOOR, WINDOW OR GRAVITY AIR
 INLET FOR THE BUILDING.
 5.A VENT CAP SHALL BE INSTALLED TO
 PREVENT RAIN FROM ENTERING THE VENT
 SYSTEM.
 6.THE VENT TERMINATION SHALL BE
 LOCATED AT LEAST 3 FEET (914 MM)
 HORIZONTALLY FROM ANY PORTION OF THE
 ROOF STRUCTURE.
  
 501.2 OUTDOOR DISCHARGE.
  
 THE AIR REMOVED BY EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED
 OUTDOORS AT A POINT WHERE IT WILL NOT
 CAUSE A NUISANCE AND FROM WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE
 EXHAUSTED INTO AN ATTIC OR CRAWL SPACE
  
 401.5 OPENING LOCATION.
 OUTDOOR AIR EXHAUST AND INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET
 (3048 MM) FROM LOT LINES OR BUILDINGS ON
 THE SAME LOT. WHERE OPENINGS FRONT ON A
 STREET OR PUBLIC WAY, THE DISTANCE SHALL
 BE MEASURED TO THE CENTERLINE OF THE
 STREET OR PUBLIC WAY.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-11 Cont ID  
Sent By dpalmer Date 2007-01-11 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2007-01-11 Time 15:30 Sent To  
Notes
2007-01-11 16:35:21SHEETS AS SUBMITTED ARE FOR GENERATOR PERMIT ONLY, NO
 REVIEW FOR ANY OTHER ELECTRICAL ITEMS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-15 Cont ID  
Sent By dpalmer Date 2006-09-15 Time 20:28 Rev Time 0.00
Received By dpalmer Date 2006-09-15 Time 19:58 Sent To  
Notes
2006-09-15 00:00:00**** UNSAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE THAT THE PROPOSED
 250 GAL SUB BASE FUEL TANK DOES NOT MEET
 THE MIN REQUIRED FOR 8HRS OF OPERATION
 REQUIRED FOR FIRE PUMP AND ALL OTHER
 REQUIRED SYSTEMS FOR THEIR LOADS AT
 100%.
 PLEASE SEE NFPA-20 6.2.2
 THE FUEL SUPPLY CAPACITY SHALL BE
 SUFFICIENT TO PROVIDE 8 HOURS OF FIRE
 PUMP OPERATION AT 100 PERCENT OF THE
 RATED PUMP CAPACITY IN ADDITION TO THE
 SUPPLY REQUIRED FOR OTHER DEMANDS.
  
 2) NOTE: PLEASE SEE THAT THIS IS A
 "THRESHOLD" PROJECT AND THREE SETS OF
 PLANS AND ALL SUBMITTIALS ARE REQUIRED
 FOR REVIEW AND STAMPING. 2001 FBC
 104.2.1, 104.2.1.2 ADIMINISTRATIVE
 SECTION AS ADOPTED BY THE CITY OF WEST
 PALM BEACH.
  
 ** PLEASE SEE THIS WAS NOTED ON PREVIOUS
 REVIEW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-02 Cont ID  
Sent By dpalmer Date 2006-06-02 Time 13:35 Rev Time 0.00
Received By dpalmer Date 2006-06-02 Time 13:07 Sent To  
Notes
2006-06-02 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE SPECS INDICATE 510KW
 GEN AND PLANS INDICATE 500KW?? PLEASE
 CORRELATE AND CLARIFY.
  
 2) NOTE: PLEASE BE SURE THE ENGINEER OF
 RECORD SIGNS PLANS AS ON RECORD WITH THE
 CITY OF WEST PALM BEACH.
  
 3) NOTE: PLEASE PROVIDE INFORMATION FOR
 FUEL CONSUMTION OF GEN AND MIN FUEL
 SUPPLY FOR 8HRS OF 100% LOAD OF FIRE
 PUMP AND OTHER ASSOCIATED EM LOADS AT
 100% .
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-02-13 Cont ID  
Sent By mawillia Date 2007-02-13 Time 09:23 Rev Time 0.00
Received By mawillia Date 2007-02-13 Time 09:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-10-18 Cont ID  
Sent By mwennerg Date 2006-10-18 Time 15:39 Rev Time 0.00
Received By mwennerg Date 2006-10-18 Time 15:39 Sent To  
Notes
2006-10-18 15:47:59***DENIED***
  
 1) PLEASE SEE ELECTRICAL COMMENT (1) IN REFERENCE TO
 FUEL SUPPLY REQUIREMENTS IN ACCORDANCE WITH NFPA 20.
  
 2) WORK SHALL COMPLY WITH NFPA 110. PLEASE PROVIDE
 ACKNOWLEDGEMENT AS THIS COMMENT IS FROM THE FIRST FIRE
 REVIEW.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By mwennerg Date 2006-06-22 Time 12:54 Rev Time 0.00
Received By mwennerg Date 2006-06-22 Time 12:53 Sent To  
Notes
2006-06-22 00:00:00***DENIED***
  
 1) WORK SHALL COMPLY WITH NFPA 110,
 STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS.
  
 2) PLEASE PROVIDE PLANS INDICATING
 LOCATIONS AND DISTANCES OF GENERATOR
 EXHAUSTING TO BUILDING OPENINGS AND
 MEANS OF EGRESS.
  
 3) MORE DETAILS REQUIRED FOR FUEL TANK.
 SUBMITTAL PACKET INDICATES SUB-BASE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-10-17 Cont ID  
Sent By pkrauss Date 2006-10-17 Time 07:09 Rev Time 0.00
Received By pkrauss Date 2006-10-17 Time 07:09 Sent To  
Notes
2006-10-17 07:10:21NO FUEL PIPING OR REMOTE TANK INSTALLED.PER
 MANUFACTURER'S SPECIFICATION, THIS IS A SUB-BASE FUEL
 TANK.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-06-23 Cont ID  
Sent By jleech Date 2006-06-23 Time 11:05 Rev Time 0.00
Received By jleech Date 2006-06-23 Time 11:05 Sent To  
Notes
2006-06-23 00:00:00THE GENERATOR IS FUILED BY DESAL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-08 Cont ID  
Sent By adarroug Date 2007-01-08 Time 09:51 Rev Time 0.00
Received By adarroug Date 2007-01-08 Time 09:51 Sent To  
Notes
2007-01-11 09:54:11TO "COMM" BD#29
2007-01-08 09:52:13WAITING FOR "COMM" BD-PLANS FOUND IN "F" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 10:17 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 10:17 Sent To  
Notes
2006-09-11 00:00:00TO "COMM" BD#61
2006-09-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-15 Cont ID  
Sent By   Date 2006-06-24 Time   Rev Time 0.00
Received By adarroug Date 2006-04-29 Time 15:04 Sent To  
Notes
2006-05-19 00:00:00TO "COMM' BD#8
2006-04-29 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2007-02-12 Cont ID  
Sent By rregueir Date 2007-02-12 Time 14:17 Rev Time 0.00
Received By rregueir Date 2007-02-01 Time 14:42 Sent To  
Notes
2007-02-12 14:15:29PLEASE SUBMIT MECHANICAL PORTIONS OF THIS PLAN AS A
 REVISION TO MASTER PERMIT # 04031591. THERE IS NO
 EXTERNAL OR UNDERGROUND FUEL TANK FOR THIS GENERATOR.
 THEREFORE THERE IS NO FILL PIPING. INTAKE AND EXHAUST
 FOR THIS GENERATOR ARE COVERED UNDER THE MASTER
 PERMIT.
  
 RONALD J REGUEIRO
 561-805-6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-10-17 Cont ID  
Sent By pkrauss Date 2006-10-16 Time 10:54 Rev Time 0.00
Received By pkrauss Date 2006-10-16 Time 10:54 Sent To  
Notes
2006-10-16 11:07:52PLEASE SUBMIT MECHANICAL PLANS AS A REVISION TO PERMIT
 04031591
  
 PLANS SUBMITTED APPEAR TO BE REVISIONS FOR THE
 MECHANICAL (HVAC) TO THE BUILDING & HAS NOTHING TO DO
 WITH THE GENERATOR PERTAINING TO MECHANICAL OR FUEL FOR
 THE GENERATOR.ALL VENTING TO THE DIESEL GENERATOR &
 THE GENERATOR ROOM SHALL BE SUBMITTED AS A REVISION TO
 PERMIT 04031591, AS THESE PLANS REFLECT THE ORIGINAL
 DESIGN.
  
 1.SUBMITTAL DATA FOR THE GENERATOR INDICATES SUB-BASE
 FUEL TANKWITH NO DAY TANK.THERE WILL BE NO FILL
 PIPING.
  
 2.PLEASE SUBMIT REVISIONS TO MUFFLER EXHAUST OR
 VENTILATION TO THE GENERATOR ROOM UNDER THE BUILDING
 PERMIT IN WHICH IT WAS ORIGINALLY REVIEWED.PLEASE
 NOTE, PLAN SHEET M2.01 INDICATES EXHAUST FROM THE
 GENERATOR ROOM IS TERMINATING INTO THE MAIN SWITCH GEAR
 ROOM.PER 2004 FMC 501.2, AIR REMOVED FROM EVERY
 EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS.502.1.3,
 EQUIPMENT ROOMMS THAT HOUSE SOURCES OFR NOXIOUS FUMES
 OR GASES, SHALL BE DESIGNED TO PREVENT SPREADING OF
 SUCH CONTAMINANTS TO OTHER OCCUPIED PARTS OF THE
 BUILDING.
  
  
 ************REVIEW IN PROGRESS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-24 Cont ID  
Sent By hmoser Date 2006-06-24 Time 06:58 Rev Time 0.00
Received By hmoser Date 2006-06-24 Time 06:58 Sent To  
Notes
2006-06-24 00:00:00PLAN DENIED
 NO MECHANICAL PLANS SHOWING LOCATION OF
 FUEL TANK,PIPING FROM FUELTANK TO
 GENERATOR. PLEASE REFER TO TABLE 1302.3
 FBC(M) 2004.PLEASE SEE BUILDING NOTES
 MECHANICAL CODE.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-23 Cont ID  
Sent By jleech Date 2006-06-23 Time 10:32 Rev Time 0.00
Received By jleech Date 2006-06-23 Time 10:32 Sent To  
Notes
2006-06-23 00:00:00NO PLUMBING THIS PLAN

Review Stop Z ZONING
Rev No 1 Status N Date 2006-10-19 Cont ID  
Sent By lmartine Date 2006-10-19 Time 11:14 Rev Time 0.00
Received By lmartine Date 2006-10-19 Time 11:14 Sent To  
Notes
2006-10-19 11:15:42REVIEW NOT REQUIRED PER ANNA MARIA.


Account Summary | Usage Policy | Privacy Policy