2006-05-31 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06041193 |
| ADD: 410 EVERNIA ST |
| CONT: MEISNER ELECTRIC |
| TEL: (561)278-8362 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| 1) GENERATOR SLAB & ANCHOR REQUIREMENT |
| PLEASE PROVIDE SIZE OF GENERATOR(WXL), |
| PLUS PROVIDE PLANS WITH THE INFORMATION |
| DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| FASTENER, AND THE MINIMUM EDGE DISTANCE |
| THE DEVICE REQUIRES WITHOUT LOAD |
| REDUCTION. |
| SECOND, PROVIDE INFORMATION ON THE |
| SLAB, THICKNESS, WIDTH AND LENGTH, IF |
| WIREMESH, FIBER MESH OR IF STEEL REBAR |
| WILL BEUSED. |
| THE NEW SLAB AND HOLD DOWN DETAILS: |
| 104.2.1* ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA |
| SHALL BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. |
| |
| 2)PROVIDE PLANS ENOUGH TO VERIFY |
| LOCATION OF GENERATOR VERSES BUILDING |
| OPENINGS WINDOWS, DOORS OR SOFFIT TYPE |
| VENTS, ETC. |
| |
| MECHANICAL CODE |
| 804.3.4 HORIZONTAL TERMINATIONS. |
| HORIZONTAL TERMINATIONS SHALL COMPLY |
| WITH THE FOLLOWING REQUIREMENTS: |
| 1.WHERE LOCATED ADJACENT TO |
| WALKWAYS, THE TERMINATION OF MECHANICAL |
| DRAFT SYSTEMS SHALL BE NOT LESS THAN 7 |
| FEET (2134 MM) ABOVE THE LEVEL OF THE |
| WALKWAY. |
| 2.VENTS SHALL TERMINATE AT LEAST 3 |
| FEET (914 MM) ABOVE ANY FORCED AIR INLET |
| LOCATED WITHIN 10 FEET (3048 MM). |
| 3.THE VENT SYSTEM SHALL TERMINATE |
| AT LEAST 4 FEET (1219 MM) BELOW, 4 FEET |
| (1219 MM) HORIZONTALLY FROM OR 1 FOOT |
| (305 MM) ABOVE ANY DOOR, WINDOW OR |
| GRAVITY AIR INLET INTO THE BUILDING. |
| 4.THE VENT TERMINATION POINT SHALL |
| NOT BE LOCATED CLOSER THAN 3 FEET (914 |
| MM) TO AN INTERIOR CORNER FORMED BY TWO |
| WALLS PERPENDICULAR TO EACH OTHER. |
| 5.THE VENT TERMINATION SHALL NOT BE |
| MOUNTED DIRECTLY ABOVE OR WITHIN 3 FEET |
| (914 MM) HORIZONTALLY FROM AN OIL TANK |
| VENT OR GAS METER. |
| 6.THE BOTTOM OF THE VENT |
| TERMINATION SHALL BE LOCATED AT LEAST 12 |
| INCHES (305 MM) ABOVE FINISHED GRADE. |
| |
| 804.3.5 VERTICAL TERMINATIONS. |
| VERTICAL TERMINATIONS SHALL COMPLY WITH |
| THE FOLLOWING REQUIREMENTS: |
| 1.WHERE LOCATED ADJACENT TO |
| WALKWAYS, THE TERMINATION OF MECHANICAL |
| DRAFT SYSTEMS SHALL BE NOT LESS THAN 7 |
| FEET (2134 MM) ABOVE THE LEVEL OF THE |
| WALKWAY. |
| 2.VENTS SHALL TERMINATE AT LEAST 3 |
| FEET (914 MM) ABOVE ANY FORCED AIR INLET |
| LOCATED WITHIN 10 FEET (3048 MM). |
| 3.WHERE THE VENT TERMINATION IS |
| LOCATED BELOW AN ADJACENT ROOF |
| STRUCTURE, THE TERMINATION POINT SHALL |
| BE LOCATED AT LEAST 3 FEET (914 MM) FROM |
| SUCH STRUCTURE. |
| 4.THE VENT SHALL TERMINATE AT LEAST |
| 4 FEET (1219 MM) BELOW, 4 FEET (1219 MM) |
| HORIZONTALLY FROM, OR 1 FOOT (305 MM) |
| ABOVE ANY DOOR, WINDOW OR GRAVITY AIR |
| INLET FOR THE BUILDING. |
| 5.A VENT CAP SHALL BE INSTALLED TO |
| PREVENT RAIN FROM ENTERING THE VENT |
| SYSTEM. |
| 6.THE VENT TERMINATION SHALL BE |
| LOCATED AT LEAST 3 FEET (914 MM) |
| HORIZONTALLY FROM ANY PORTION OF THE |
| ROOF STRUCTURE. |
| |
| 501.2 OUTDOOR DISCHARGE. |
| |
| THE AIR REMOVED BY EVERY MECHANICAL |
| EXHAUST SYSTEM SHALL BE DISCHARGED |
| OUTDOORS AT A POINT WHERE IT WILL NOT |
| CAUSE A NUISANCE AND FROM WHICH IT |
| CANNOT AGAIN BE READILY DRAWN IN BY A |
| VENTILATING SYSTEM. AIR SHALL NOT BE |
| EXHAUSTED INTO AN ATTIC OR CRAWL SPACE |
| |
| 401.5 OPENING LOCATION. |
| OUTDOOR AIR EXHAUST AND INTAKE OPENINGS |
| SHALL BE LOCATED A MINIMUM OF 10 FEET |
| (3048 MM) FROM LOT LINES OR BUILDINGS ON |
| THE SAME LOT. WHERE OPENINGS FRONT ON A |
| STREET OR PUBLIC WAY, THE DISTANCE SHALL |
| BE MEASURED TO THE CENTERLINE OF THE |
| STREET OR PUBLIC WAY. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| |
| |