Plan Review Stops For Permit 06041070 |
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2006-04-28 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-04-28 |
Time |
10:18 |
Rev Time |
0.45 |
Received By |
mperson |
Date |
2006-04-28 |
Time |
10:18 |
Sent To |
PC |
|
Notes |
2006-04-28 00:00:00 | | | | | ******PROVISO****** | | PER NFPA-96 SEC. 10.5.1, AND NFPA-1 SEC. | | 50.4.7.1: A READILY ACCESSIBLE MEANS FOR | | MANUAL ACTIVATION SHALL BE LOCATED | | BETWEEN 42 INCH AND 48 INCH ABOVE THE | | FLOOR, BE ACCESSIBLE IN THE EVENT OF A | | FIRE, BE LOCATED IN A PATH OF EGRESS, | | AND CLEARLY IDENTIFY THE HAZARD | | PROTECTED. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-04-28 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-04-28 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2006-04-27 |
Time |
11:20 |
Sent To |
|
|
Notes |
2006-04-27 00:00:00 | TO "G" BOX |
|
|
|