Plan Review Details - Permit 06041025
Plan Review Stops For Permit 06041025
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-23 Cont ID  
Sent By shill Date 2006-05-23 Time 16:24 Rev Time 0.00
Received By shill Date 2006-05-18 Time 08:53 Sent To  
Notes
2006-05-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.)THE PLANS ARE TO BE SIGNED,
 FAC61G1-16 (AS WELL AS PREVIOUS
 DISCUSSIONS WITH THE FLORIDA BOARD OF
 ARCHITECTS).IF YOU FEEL THAT A STAMP
 IS THE EQUIVALENT OF A SIGNATURE AND IS
 ACCEPTABLE, PLEASE PROVIDE A LETTER
 STATING SUCH AND IT WILL BE FORWARDED TO
 THE BOARD FOR THEIR OPINION.OTHERWISE,
 PLEASE SIGN ALL SHEETS (MICHAEL KYLE
 HART, AR01605).
  
 3.)DECLARE THE LEVEL OF ALTERATION,
 FBC EB 301.
  
 4.)CONSTRUCTION TYPE, A1.1 AND FIRE
 PROTECTION CRITERIA DECLARE TYPE II.
 THIS SHOULD BE TYPE IIA OR TYPE IIB,
 FBC6.
  
 5.)ARCHITECTURAL KEYNOTES, A5.1 DO NOT
 INCLUDE 5 AND 6.CODE COMPLIANCE CANNOT
 BE DETERMINED AS SCOPE OF WORK IS NOT
 CLEAR.
  
 6.)M0.1 REFERS TO INCORRECT BUILDING
 CODES.FOR EXAMPLE, FBC2003 IS NOT (AND
 NEVER WAS) THE GOVERNING CODE.CHECK
 ALL REFERENCES AND REVISE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-17 Cont ID  
Sent By dpalmer Date 2006-05-17 Time 19:58 Rev Time 0.00
Received By dpalmer Date 2006-05-17 Time 19:51 Sent To  
Notes
2006-05-17 00:00:00***** UNSAT ******
  
 1) NOTE: PLEASE SEE BUIDLIGN REVIEW
 COMMENTS AS THE SCOPE OF WORK MAY BE
 REQUIRED TO BE UNDER A GC.
 PLEASE ALSO SEE AS THE MECHANICAL
 CONTRACTOR'S APPLICATION IS ATTACHED,
 THE VAULE FOR THE ENTIRE SCOPE OF WORK
 UNDER THE "PRIME PERMIT" SHALL BE
 INCLUSIVE OF ALL TRADES.
 FBC 108.3
  
 2) NOTE: PLEASE COORELATE ALL CODES ON
 ELECTRICAL SHEETS WITH THE CURRENT CODES
 REFLECTED ON THE ARCHITECTURAL SHEETS.
 PLEASE SEE CODES REF IE: SFBC 1997, 1999
 NFPA-72, ETC.
 PLEASE ADJUST.
  
 3) NOTE: PLEASE SEE BOTH MECHNICAL AND
 ELECTRICAL ENGINEERED SHEETS AS THE
 "SEALED", ARE NO LONGER IN USE OR
 ACCEPTABLE PER FAC 61G15-23.001.
 PLEASE KNOW, AS OF FEB 04, THE FBPE'S
 CHANGED SUCH RULING AS TO ADOPT THAT ALL
 SEALS SHALL NO LONGER CONTAIN THE
 WORDING "CERTIFICATE" AND ALL SEALS MUST
 CONTAIN THE WORDING OF "LICENSE". PLEASE
 KNOW, AN EXTENSION WAS GRANTED TO DEC
 31ST, 2005, HOWEVER ALL PERMIT
 APPLICATIONS, PLANS AFTER SUCH DATE
 SHALL CONTAIN THE NEW UPDATED SEALS.
  
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By mwennerg Date 2006-05-31 Time 15:05 Rev Time 0.00
Received By mwennerg Date 2006-05-31 Time 15:05 Sent To  
Notes
2006-05-31 00:00:00***DENIED***
  
 1) PLEASE NOTE THAT CODE REFERENCING IS
 INCONSISTENT THROUGHOUT PLANS. PLEASE BE
 SURE TO REFERENCE THE ADOPTED CODE AND
 CORRULATE ON ALL SHEETS.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL.
 SEPARATE PERMIT MAY BE REQUIRED FOR FIRE
 ALARM REMODEL DEPENDING ON THE AMOUNT OF
 DEVICES WITHIN THIS SCOPE OF WORK.
  
 3) PLEASE PROVIDE FURTHER EXPLANATION
 REGARDING NOTE ON LIFE SAFETY PLAN THAT
 REFERENCES A FULLY SPRINKLERED
 AGREEMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-09 Cont ID  
Sent By adarroug Date 2006-06-06 Time 16:19 Rev Time 0.00
Received By adarroug Date 2006-04-25 Time 14:31 Sent To  
Notes
2006-06-12 00:00:006/12/06-FROM "COMM" BD TO "P" BOX
2006-05-11 00:00:00TO "COMM" BD#52
2006-04-25 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-06 Cont ID  
Sent By hmoser Date 2006-06-06 Time 16:50 Rev Time 0.00
Received By hmoser Date 2006-06-06 Time 16:50 Sent To  
Notes
2006-06-06 00:00:00PLAN DENIED
 1) PLANS NOT COMPLETE MISSING DUCT
 SIZE,EQUIPMENT SCHEDULE,FRESH AIR
 CALCULATIONS AND ENERGY CALCULATIONS
 2) PLEASE SEE ELECTRICAL NOTE # 3
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***