Plan Review Details - Permit 06040937
Plan Review Stops For Permit 06040937
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-28 Cont ID  
Sent By alange Date 2006-08-28 Time 09:15 Rev Time 0.00
Received By alange Date 2006-08-28 Time 09:15 Sent To  
Notes
2006-08-28 00:00:00DENIED
  
 INSUFFICIENT INFORMATION SUBMITTED FOR
 AN EXTERIOR WALL REVISION.PLANS
 REQUIRED.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-07-06 Cont ID  
Sent By alange Date 2006-07-06 Time 08:43 Rev Time 0.00
Received By alange Date 2006-07-06 Time 08:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-24 Cont ID  
Sent By alange Date 2006-05-24 Time 14:55 Rev Time 0.00
Received By alange Date 2006-05-24 Time 14:50 Sent To  
Notes
2006-05-24 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.PRODUCT APPROVALS REQUIRED FOR
 TRANSOM WINDOW.
  
 3.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 4.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 5.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 6.SHOW AN ELEVATION OF RECEPTION
 COUNTER SO COMPLIANCE CAN BE CHECKED
 WITH 11-7.2 OF THE 2004 FBC.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-28 Cont ID  
Sent By dpalmer Date 2006-06-28 Time 18:29 Rev Time 0.00
Received By dpalmer Date 2006-06-28 Time 18:08 Sent To  
Notes
2006-06-28 00:00:00** REDLINED**
  
 PLANS MENTIONS, 2005 NEC, WHEREAS WE ARE
 UNDER 2002.
  
 MISSING EQUIPMENT GROUNDING CONDUCTOR
 FROM MAINS TO SUB PANELS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-17 Cont ID  
Sent By dpalmer Date 2006-05-17 Time 19:29 Rev Time 0.00
Received By dpalmer Date 2006-05-17 Time 18:25 Sent To  
Notes
2006-05-17 00:00:00****** UNSAT *******
  
 1) NOTE: PLEASE SUBMIT PLANS DONE BY A
 MIN OF AN ARCHITECT PER FS 481.229 FOR
 VALUE AND SCOPE OF WORK OVER $25,000.
  
 2) NOTE: PLEASE PROVIDE THE RISER
 DIAGRAM, AS PLANS SEEM TO SHOW TWO
 DIFFERENT METERS ??. THIS IS BEING SHOWN
 AS A SINGLE OCCUPANCY BUILDING AND NO
 "FIRE WALL" SEPARATION IS PRESENT ON
 PLANS. PLEASE KNOW, ONLY ONE SERVICE
 WILL BE PERMITTED AND ALL MAINS SHALL BE
 GROUPED. 230.2,230.70,230.72
  
 3) NOTE: PLEASE SEE 517 AND INDICATE
 LOCATIONS AND WIRING METHODS AS SET
 FORTH IN THE 2002 NEC AND LS CODE.
 PLEASE SEE ALL OTHER COMMENTS FROM OTHER
 TRADES WHICH MAY ALSO AFFECT THIS.
  
 4)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF ALL EM/EXT LTS.
  
 5) NOTE: PLEASE SEE THE MIN OCP AND AWG
 FOR EXISTING AHU'S SHALL BE ADJUSTED
 EVEN IF EXISITNG. PLEASE SEE
 424.3B,240.4,310.16 10KW, #8 AND 50A
 OCP.
  
 6) NOTE: PLEASE SUPPLY LOAD CALCUALTIONS
 PER 220.3,220.10,220.11,220.13 ETC.
 PLEASE SEE 215.3,230.42 FOR ALL
 CONTINUOUS LOADS TO BE SHOWN AT 125%.
  
 7) NOTE: PLANS SHALL CONTAIN THE CURRENT
 CODES UNDER ADOPTION BY THE STATE OF
 FLORIDA.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72 ETC.
  
 8) NOTE: PLEASE SEE BUIDLIGN REVIEW
 COMMENTS FOR REQUIRED "STATEMENT" ON
 PLANS FOR THE DESIGN PROFESSIONAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-03 Cont ID  
Sent By mwennerg Date 2006-07-03 Time 10:19 Rev Time 0.00
Received By mwennerg Date 2006-07-03 Time 10:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-25 Cont ID  
Sent By mwennerg Date 2006-05-25 Time 15:27 Rev Time 0.00
Received By mwennerg Date 2006-05-25 Time 15:27 Sent To  
Notes
2006-05-25 00:00:00***DENIED***
  
 1) PLANS SHOWS SMOKE ALARMS. IS THIS NEW
 OR EXISTING CONDITION? PLEASE INDICATE
 THE CODE REFERENCE BEING USED FOR
 ISTALLATION OF SMOKE ALARMS.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHER IS
 REQUIRED.
  
 3) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 4) WHAT CONDITION EXISTS THAT WILL
 PREVENT THE CLOSET DOOR IF IN OPEN
 POSITION FROM NOT OBSTRUCTING MEANS OF
 EGRESS TO THE SECOND EXIT?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 14:56 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 14:56 Sent To B
Notes
2006-08-16 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-27 Cont ID  
Sent By adarroug Date 2006-06-27 Time 08:35 Rev Time 0.00
Received By adarroug Date 2006-06-27 Time 08:35 Sent To  
Notes
2006-06-27 00:00:00TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-30 Cont ID  
Sent By adarroug Date 2006-05-30 Time 08:34 Rev Time 0.00
Received By rbrown Date 2006-04-24 Time 12:40 Sent To  
Notes
2006-05-22 00:00:00MOVED TO "BOB"#16
2006-05-11 00:00:00TO "COMM" BD#22
2006-04-24 00:00:00WAITING ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-05-30 Cont ID  
Sent By tgordon Date 2006-05-30 Time 14:46 Rev Time 0.25
Received By tgordon Date 2006-05-30 Time 14:46 Sent To  
Notes
2006-05-30 00:00:00*** PROVISO ***
 1)BALANCED RETURN AIR.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE. PER 2004
 FBC/R M1602.4 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-06-30 Cont ID  
Sent By pschmitz Date 2006-06-30 Time 10:34 Rev Time 0.00
Received By pschmitz Date 2006-06-30 Time 10:34 Sent To  
Notes
2006-06-30 00:00:00RE SUB
  
 SHT. 6.1 PROVISO:
  
 3) SHT 6.1 PLUMBING NOTES. #15 REFERENCE
 AIR CHAMBERS. TO COMPLY WITH ASSE 1010.
 SEE SEC 604.9 WATER HAMMER ARRESTORS.
  
 4) SHT 3.1SHOW LOCATION OF WATER
 HEATER, PROVIDE A DETAIL TO SHOW
 COMPLIANCE OF SEC 604.7 FOR THERMAL
 EXPANSION.
  
 5) SHT 6.1 WATER RISER. SEC 606.1 (4)
 LOCATION OF FULLY OPEN VALVES.
 SOV REQUIRED ON THE TOP OF EVERY WATER
 DOWN FEED PIPE.
  
 6) SHT 6.1 WATER RISER, SHOW LOCATION OF
 BACK FLOW PREVENTER AS REQUIRED BY
 LOCAL ORDINANCE #2853-95

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-27 Cont ID  
Sent By pschmitz Date 2006-05-27 Time 12:05 Rev Time 0.00
Received By pschmitz Date 2006-05-27 Time 12:05 Sent To  
Notes
2006-05-27 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1)SEE OTHER PLAN REVIEW COMMENTS,
 THAT MAY EFFECT PLUMBING PLAN REVIEW.
  
 2) SHT 3.1 LOUNGE SINK SEC 11-4.24
  
 11-4.24 SINKS.
 11-4.24.1 GENERAL.
 SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.24.
 11-4.24.2 HEIGHT.
 SINKS SHALL BE MOUNTED WITH THE COUNTER
 OR RIM NO HIGHER THAN 34 INCHES (865 MM)
 ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE.
 KNEE CLEARANCE THAT IS AT LEAST 27
 INCHES (685 MM) HIGH, 30 INCHES (760 MM)
 WIDE, AND 19 INCHES (485 MM) DEEP SHALL
 BE PROVIDED UNDERNEATH SINKS.
 11-4.24.4 DEPTH.
 EACH SINK SHALL BE A MAXIMUM OF 6?
 INCHES (165 MM) DEEP.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES
 BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485
 MM) UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED UNDER
 SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED SO AS TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER SINKS.
 11-4.24.7 FAUCETS.
 FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE,
 TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED
 MECHANISMS ARE ACCEPTABLE DESIGNS.
  
 3) SHT 6.1 PLUMBING NOTES. #15 REFERENCE
 AIR CHAMBERS. TO COMPLY WITH ASSE 1010.
 SEE SEC 604.9 WATER HAMMER ARRESTORS.
  
 4) SHT 3.1SHOW LOCATION OF WATER
 HEATER, PROVIDE A DETAIL TO SHOW
 COMPLIANCE OF SEC 604.7 FOR THERMAL
 EXPANSION.
  
 5) SHT 6.1 WATER RISER. SEC 606.1 (4)
 LOCATION OF FULLY OPEN VALVES.
 SOV REQUIRED ON THE TOP OF EVERY WATER
 DOWN FEED PIPE.
  
 6) SHT 6.1 WATER RISER, SHOW LOCATION OF
 BACK FLOW PREVENTER AS REQUIRED BY
 LOCAL ORDINANCE #2853-95
  
 END OF COMMENTS QUESTIONS 561- 805-6692