Plan Review Details - Permit 06040807
Plan Review Stops For Permit 06040807
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-15 Cont ID  
Sent By alange Date 2006-06-15 Time 14:34 Rev Time 1.00
Received By alange Date 2006-06-15 Time 14:34 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-22 Cont ID  
Sent By alange Date 2006-05-22 Time 13:37 Rev Time 1.25
Received By alange Date 2006-05-22 Time 13:37 Sent To  
Notes
2006-05-22 00:00:00DENIED
  
  
 1.PRODUCT APPROVALS REQUIRED FOR TARCO
 ROOFING UNDERLAYMENT.ONLY STATE
 PRODUCT APPROVAL SUBMITTED.
  
 2.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 3.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-25 Cont ID  
Sent By btrobaug Date 2006-09-25 Time 17:43 Rev Time 0.50
Received By btrobaug Date 2006-09-25 Time 16:41 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-19 Cont ID  
Sent By btrobaug Date 2006-06-19 Time 16:17 Rev Time 0.75
Received By btrobaug Date 2006-06-19 Time 15:32 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-05-12 Cont ID  
Sent By btrobaug Date 2006-05-12 Time 12:09 Rev Time 0.50
Received By btrobaug Date 2006-05-12 Time 11:33 Sent To P
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-04-19 Cont ID  
Sent By ptjomsto Date 2006-04-19 Time 16:04 Rev Time 0.00
Received By ptjomsto Date 2006-04-19 Time 16:04 Sent To  
Notes
2006-04-19 00:00:00HISTORIC APPROVED 4/19/06 BY J PAPA

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 08:58 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 08:58 Sent To P
Notes
2006-06-12 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-06 Cont ID  
Sent By adarroug Date 2006-06-06 Time 14:47 Rev Time 0.00
Received By adarroug Date 2006-06-06 Time 14:47 Sent To Z
Notes
2006-06-06 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 11:46 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 11:46 Sent To E
Notes
2006-05-11 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-22 Cont ID  
Sent By alange Date 2006-05-22 Time 13:37 Rev Time 0.00
Received By alange Date 2006-04-21 Time 11:33 Sent To  
Notes
2006-04-21 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-05-16 Cont ID  
Sent By tgordon Date 2006-05-16 Time 14:25 Rev Time 0.25
Received By tgordon Date 2006-05-16 Time 14:25 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-06-15 Cont ID  
Sent By mperson Date 2006-06-15 Time 15:55 Rev Time 0.33
Received By mperson Date 2006-06-15 Time 15:55 Sent To E
Notes
2006-06-15 00:00:00NOTE: ART LANGE FOUND REVISED SHEETS 3/3
 FOR PLUMBING REVIEW SEPERATE FROM PRINTS
 PLUMBING REVIEW PASSED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-06-13 Cont ID  
Sent By mperson Date 2006-06-13 Time 08:28 Rev Time 0.33
Received By mperson Date 2006-06-13 Time 08:28 Sent To B
Notes
2006-06-13 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING IS STILL REQUIRED FOR
 PLUMBING PLAN REVIEW:
  
 1.THERE HAS BEEN NO ATTEMPT TO CORRECT
 THE ISOMETRIC PLUMBING RISER DIAGRAM ON
 SHEET 3/3, UNTIL THESE CHANGES HAVE BEEN
 MET PERMIT CAN NOT BE ISSUED.
 2. CHANGE UNDER SINK VENT TO READ AIR
 ADMITTANCE VALVE PER FBC-2004 PLUMBING
 SECTION 917, SEE CORRECTED DRAWING ON
 SHEET 3/3 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
 3. PER CHAPTER 1, SECTION 106.1.1: THE
 SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. SHEET 3/3
 FLOOR PLAN INDICATES TWO 2" PVC UNDER
 SINK VENTS WHICH SHOULD BE INDICATED AS
 AIR ADMITTANCE VALVES (A.A.V.) AND RISER
 DIAGRAM INDICATES ONE AIR ADMITTANCE
 VALVE (A.A.V.) PLEASE CORRELATE DRAWING
 FOR RESUBMITTAL.
 4.CLEANOUTS ARE REQUIRED AT THE BASE OF
 WASTE STACKS AND NEAR THE JUNCTION OF
 THE BUILDING DRAIN AND THE BUILDING
 SEWER, PER FBC-2004 PLUMBING, SECTION
 708.3.4 AND SECTION 708.3.5. THE
 ISOMETRIC PLUMBING RISER DIAGRAM NEEDS
 TO INDICATE THE CLEANOUTS, PLEASE SEE
 CORRECTED DRAWING IN RED INK FOR
 REFERENCE FOR RESUBMITTAL.
 5.NOTE: A PLUMBING PERMIT WILL BE
 REQUIRED FOR THE PLUMBING WORK INDICATED
 ON DRAWINGS, PLUMBING CONTRACTOR SHALL
 REFERENCE PERMIT #06040807 WHEN PLUMBING
 PERMIT IS APPLIED FOR.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-16 Cont ID  
Sent By mperson Date 2006-05-16 Time 11:29 Rev Time 0.45
Received By mperson Date 2006-05-16 Time 11:29 Sent To M
Notes
2006-05-16 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING, CITY OF
 WEST PALM BEACH AMENDMENTS TO FBC-2004,
 CHAPTER 1, ADMINISTRATION.
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1. CHANGE UNDER SINK VENT TO READ AIR
 ADMITTANCE VALVE PER FBC-2004 PLBG. SEC.
 917.
 2. PER CHAPTER 1, SEC. 106.1.1: SANITARY
 PLBG. RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. SHEET 3/3 FLOOR PLAN
 INDICATES TWO 2" PVC UNDER SINK VENTS
 WHICH SHOULD BE AIR ADMITTANCE VALVES
 AND THE RISER DIAGRAM INDICATES ONE AIR
 ADMITTANCE VALVE (A.A.V.) PLEASE
 CORRELATE DRAWING
 3. CLEANOUTS REQUIRED AT BASE OF WASTE
 STACKS AND NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER,
 PER FBC-2004 PLBG, SEC. 708.3.4 AND SEC.
 708.3.5. THE ISOMETRIC PLBG. RISER
 DIAGRAM NEEDS TO INDICATE THE CLEANOUTS,
 PLEASE SEE CORRECTED PLBG. SHEET 3/3 AND
 CORRECT DRAWINGS BY DESIGN PROFESSIONAL
 AND RESUBMIT.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 2 Status P Date 2006-06-10 Cont ID  
Sent By mmclean Date 2006-06-10 Time 14:58 Rev Time 0.00
Received By mmclean Date 2006-06-10 Time 14:58 Sent To I
Notes
2006-06-10 00:00:00PROPOSED ADDITION ONLY

Review Stop Z ZONING
Rev No 1 Status F Date 2006-05-09 Cont ID  
Sent By mmclean Date 2006-05-09 Time 15:31 Rev Time 0.00
Received By mmclean Date 2006-05-09 Time 15:31 Sent To I
Notes
2006-05-09 00:00:00DENIED,
 1. MUST SHOW THE PROPOSED ADDITION ON
 TWO COPY OF CURRENT SURVEY WITH SETBACKS
 (SIDES)
 2. MUST PROVIDE THE SETBACK OF THE
 ADDITION FROM THE 1 STORY EXISTING
 STRUCTURE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720