Plan Review Details - Permit 06040702
Plan Review Stops For Permit 06040702
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-15 Cont ID  
Sent By amorse Date 2006-08-15 Time 12:18 Rev Time 0.00
Received By amorse Date 2006-08-15 Time 12:18 Sent To PC
Notes
2006-08-15 00:00:00 

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-12 Cont ID  
Sent By amorse Date 2006-07-12 Time 10:42 Rev Time 0.00
Received By amorse Date 2006-07-12 Time 10:41 Sent To PC
Notes
2006-07-12 00:00:00 
  
  
 DENIED
  
 PREVIOUS NOTES NOT ADDRESSED:
  
 6) PRODUCT APPROVAL FOR BUILT UP ROOFING
 DOES NOT ALLOW FOR ENHANCED FASTENING IN
 THE PERIMETER AND CORNER ZONES (SEE
 LIMITATION #9) AS SUCH THIS PRODUCT WILL
 NOT BE ACCEPTABLE (NOT ADDRESSED)
  
 7) NOTE #5, SHT.1 STATES REPLACEMENT OF
 DOORS,FRAMES AND HARDWARE. PLEASE MARK
 NOA'S WITH DOOR TYPE USED, FRAME
 ATTACHMENT METHOD AND PROVIDE HARDWARE
 SCHEDULE (NOTE 5 STATES AL SERIES,
 PRODUCT APPROVAL D18 & E18) CLARIFY
  
 9) NOTE #17, SHT.1 HC STALL WILL NOT
 MEET THE REQUIREMENTS FOR CLEAR FLOOR
 SPACE, LAVATORY ENCROACHES ON THE
 REQUIRED FLOOR SPACE FOR THE WATER
 CLOSET (SEE FIG. 30E IN CHAPTER 11 FBC)
 ( WILL NOT MEET FIXTURE COUNT, PROVIDE
 OCCUPANT LOAD FOR AREA)
  
 10) THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
 ( NEEDS APPROVAL OF DESIGNER OF RECORD)
 ***************************************
  
 1) NOTE #9 SPECIFIES PGT WINDOWS NOT
 SHUTTERS AS SUBMITTED PRODUCT APPROVALS
  
 2) NOTE #11 RECONDITIONING OF OLD
 SHUTTER OR NEW ?
  
 3) SHUTTER NOA DOES NOT HAVE ATTACHMENT
 METHOD TO WOOD FRAMING, ONLY CONCRETE
 ATTACHMENT IS CONSIDERED
  
 4) PROVIDE EXISTING FLOOR PLAN LAYOUT
  
  
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH
 ADMINISTATIVE AMMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-09 Cont ID  
Sent By amorse Date 2006-05-09 Time 11:59 Rev Time 2.00
Received By amorse Date 2006-05-09 Time 11:59 Sent To  
Notes
2006-05-09 00:00:00 
  
 DENIED
  
 1) PROVIDE WIND DESIGN CRITERIA PER
 1603.1.4 FBC. SHOW COMPONENT AND
 CLADDING DESIGN PRESSURES TO DOORS AND
 WINDOWS
  
 2) PROVIDE FRAMING DETAILS THAT SHOW
 ATTACHMENT/STRAPPING OF NEW DOUBLE 2X12
 HEADERS AND SILLS ETC. ON PRESSBOX
  
 3) PROVIDE PLAN VIEW OF PRESSBOX SHOWING
 WINDOW LAYOUT, GIVE SIZES AND AMOUNT OF
 WINDOWS, WILL THEY BE FRAMED
 INDIVIDUALLY OR USE PGT MULLIONS.
  
 4) NO PRODUCT APPROVALS WERE SUBMITTED
 FOR WINDOWS OR MULLIONS IF USED.
  
 5) PRODUCT APPROVAL FOR ROLL UP DOOR WAS
 SUBMITTED, WHERE IS THIS PRODUCT BEING
 USED? IT IS NOT ON DRAWINGS. ALSO IF
 PRODUCT IS TO BE INCORPORATED INTO
 DRAWING NEW UPDATED NOA WILL BE REQUIRED
 AS THIS ONE HAS EXPIRED
  
 6) PRODUCT APPROVAL FOR BUILT UP ROOFING
 DOES NOT ALLOW FOR ENHANCED FASTENING IN
 THE PERIMETER AND CORNER ZONES (SEE
 LIMITATION #9) AS SUCH THIS PRODUCT WILL
 NOT BE ACCEPTABLE
  
 7) NOTE #5, SHT.1 STATES REPLACEMENT OF
 DOORS,FRAMES AND HARDWARE. PLEASE MARK
 NOA'S WITH DOOR TYPE USED, FRAME
 ATTACHMENT METHOD AND PROVIDE HARDWARE
 SCHEDULE
  
 8) NOTE #6, SHT.1 STATES REPLACEMENT OF
 TOILET PARTIONS WITH PLASTIC MATERIAL
 BUT DRAWING SHOWS U-BLOCK WALLS WITH HCM
 DOOR AS IN NOTE #5 PLEASE CLARIFY
  
 9) NOTE #17, SHT.1 HC STALL WILL NOT
 MEET THE REQUIREMENTS FOR CLEAR FLOOR
 SPACE, LAVATORY ENCROACHES ON THE
 REQUIRED FLOOR SPACE FOR THE WATER
 CLOSET (SEE FIG. 30E IN CHAPTER 11 FBC)
  
 10) THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 11) CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 LOCATION,NATURE, AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 PER 106.1.1 FBC* (PROVIED LEGIBLE NOA'S
 THESE MUST BE READABLE FOR FIELD
 INSPECTIONS)
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH
 ADMINISTATIVE AMMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-15 Cont ID  
Sent By btrobaug Date 2006-08-14 Time 18:08 Rev Time 1.00
Received By btrobaug Date 2006-08-14 Time 16:18 Sent To P
Notes
2006-08-14 00:00:00 
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-10 Cont ID  
Sent By btrobaug Date 2006-07-10 Time 11:28 Rev Time 0.50
Received By btrobaug Date 2006-07-10 Time 11:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-21 Cont ID  
Sent By btrobaug Date 2006-04-21 Time 15:57 Rev Time 0.50
Received By btrobaug Date 2006-04-21 Time 14:53 Sent To  
Notes
2006-04-21 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE #4 CU PER 250.66 FOR 3/0 SERVICE
 ENTRANCE CONDUCTORS.
  
 2} THE CONTINUOUS LOADS IN THE PANEL
 SCHEDULE MUST BE CALCULATED @ 125% PER
 210.20(A).
  
 3} PLEASE COMPLETE THE INFORMATION IN
 THE PANEL SPECIFICATION SECTION.
  
 IF THERE AER ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/805-6731

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-11 Cont ID  
Sent By mcarsill Date 2006-07-11 Time 09:17 Rev Time 0.00
Received By mcarsill Date 2006-07-11 Time 09:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-09 Cont ID  
Sent By mwennerg Date 2006-05-09 Time 13:56 Rev Time 0.00
Received By mwennerg Date 2006-05-09 Time 13:56 Sent To  
Notes
2006-05-09 00:00:00******DENIED******
  
  
 1) STAIRS SHALL COMPLY WITH FBC AND NFPA
 101, SECTION 7.2.2.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS
 REQUIRED. PLEASE SHOW LOCATION(S) ON
 FLOOR PLANS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 13:16 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 13:16 Sent To E
Notes
2006-08-14 00:00:00TO "BTROBAUG" DESK/RESUB--EXPEDITED
 PERMIT--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-10 Cont ID  
Sent By adarroug Date 2006-07-10 Time 10:02 Rev Time 0.00
Received By adarroug Date 2006-07-10 Time 10:02 Sent To E
Notes
2006-07-10 00:00:00TO "BTROBAUG" DESK/RESUB--EXPEDITED
 PERMIT"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-05-09 Time   Rev Time 0.00
Received By adarroug Date 2006-04-19 Time 16:17 Sent To  
Notes
2006-04-19 00:00:00TO "BOB"#6-EXPIDITED PLAN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-08-15 Cont ID  
Sent By btrobaug Date 2006-08-15 Time 15:59 Rev Time 0.00
Received By jleech Date 2006-08-15 Time 07:27 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-07-10 Cont ID  
Sent By jleech Date 2006-07-10 Time 14:25 Rev Time 0.00
Received By jleech Date 2006-07-10 Time 14:25 Sent To I
Notes
2006-07-10 00:00:00DENIED;
 1.(NOT ADDRESSED) OLD NOT 1.WATER HAMMER
 ARRESTORSTO BE USED PER. FBC-2004
 PLUMBING SEC. 604.9, AND ARE TO BE
 INSTALLED PER MANUFACTURE'S
 SPECIFICATIONS, AS CLOSE TO THE SORCE OF
 HAMMER AS POSSIBLE.
 2.(OLD NOTE #3) PLUMBING FIXTURE
 SCHEDULE WAS CHANGED TO REFERENCE HIGH
 LOW DRINKING FOUNTAIN BUT DRAWINGS OF
 DRINKING FOUNTAIN AND RISER DIAGRAM
 STILL SHOW SINGLE FOUNTAIN. A NOTE WILL
 WORK "HI-LOW DRINKING FOUNTAIN" ON PAGE
 1 AND 6.
 3.WATER RISER DIAGRAM IS MISSING
 STUBOUTS FOR 4 TOILETS AND TWO LAVS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-24 Cont ID  
Sent By jleech Date 2006-04-24 Time 09:36 Rev Time 0.00
Received By jleech Date 2006-04-24 Time 09:36 Sent To  
Notes
2006-04-24 00:00:00DENIED;
 1.WATER HAMMER ARRESTORS TO BE USED PER.
 FBC-2004 PLUMBING SEC. 604.9, AND TO BE
 INSTALLED PER MANUFACTURE'S
 SPECIFICATIONS, AS CLOSE TO THE SOURCE
 OF HAMMER AS POSSIBLE.
 2.WATER RISER DIAGRAM NOTE "A" (ADD TO
 NOTE), PROTECTIVE COATING REQUIRED TO
 PROTECT COPPER FROM CORROSION.
 3.DRINKING FOUNTAIN TO COMPLY WITH
 FBC-2004 CHAPTER 11 SEC. 11-4.1.3(10(A.
 HIGH LOW FOUNTAIN REQUIRED .
 4.SHOW DETAIL OF FIXTURES IN HANDICAP
 STALLS @TOILET 18" OFF WALL, FIG. 28 AND
 LAVATORY TO BE 5" OFF WALL, FIG. 32.
 FLUSH VALVES PER SEC. 416.5.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695