Plan Review Details - Permit 06040497
Plan Review Stops For Permit 06040497
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-04-17 Cont ID  
Sent By tgordon Date 2006-04-14 Time 12:06 Rev Time 1.00
Received By btrobaug Date 2006-04-17 Time 15:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-04-14 Cont ID  
Sent By mwennerg Date 2006-04-14 Time 14:11 Rev Time 0.00
Received By mwennerg Date 2006-04-14 Time 14:11 Sent To  
Notes
2006-04-14 00:00:00******APPROVED******
  
 1) PLEASE PROVIDE SIGNAGE OUTSIDE THE
 DOMESTIC WATER PUMP ROOM, INDICATING CO
 CONTROL PANELS INSIDE.
  
 2) A FUNCTION TEST WILL BE REQUIRED UPON
 INSTALLATION OF EQUIPMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-17 Cont ID  
Sent By btrobaug Date 2006-04-17 Time 16:44 Rev Time 0.00
Received By btrobaug Date 2006-04-14 Time 09:14 Sent To PC
Notes
2006-04-14 00:00:00TO "M" BOX--EXPIDITED PERMIT--

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-04-17 Cont ID  
Sent By pkrauss Date 2006-04-17 Time 10:32 Rev Time 0.00
Received By pkrauss Date 2006-04-17 Time 10:32 Sent To E
Notes
2006-04-17 00:00:00PROVISO:
 PLANS INDICATE LOW LEVEL ANNUNCIATION
 AT 25 PPM & HIGH LEVEL AT 100 PPM.PER
 2004 FMC 404.1 INDICATES 25 PPM AS A
 MAXIMUM, THEREFORE THE LOW LEVEL SHOULD
 BE SET AT A LEVEL LOWER THAN 25 PPM AND
 THE HIGH LEVEL SHOULD BE SET AT 25 PPM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-04-14 Cont ID  
Sent By tgordon Date 2006-04-14 Time 11:56 Rev Time 1.30
Received By tgordon Date 2006-04-14 Time 12:06 Sent To FIRE
Notes
2006-04-14 00:00:00AN ADDITIONAL PERMIT REQUIRED FOR DUCTS
 AND FANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.