Plan Review Details - Permit 06040474
Plan Review Stops For Permit 06040474
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-30 Cont ID  
Sent By amorse Date 2006-05-30 Time 15:35 Rev Time 0.50
Received By amorse Date 2006-05-30 Time 15:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-11 Cont ID  
Sent By amorse Date 2006-05-11 Time 08:37 Rev Time 0.00
Received By amorse Date 2006-05-11 Time 08:36 Sent To  
Notes
2006-05-11 00:00:00 
  
 DENIED
  
 1) PROVIDE BLDG. TYPE OF CONSTRUCTION
 AND OCCUPANCY TYPE AND LOAD OF BUILDOUT
 AREA.
  
 2) DRAWINGS SHALL STATE COMPLIANCE WITH
 2004 FBC
  
 3) ONE SET OF DRAWINGS IS MISSING
 ARCHITECTS SIGNATURE ON SEAL (SEE PAGE 4
 OF 5)
  
 4) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-07-18 Cont ID  
Sent By dpalmer Date 2006-07-18 Time 09:24 Rev Time 0.00
Received By dpalmer Date 2006-07-18 Time 08:32 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-06-27 Cont ID  
Sent By dpalmer Date 2006-06-27 Time 18:51 Rev Time 0.00
Received By dpalmer Date 2006-06-27 Time 18:51 Sent To PC
Notes
2006-06-27 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW/ PROVISO.
 NOTE #1 AND #2 REMAINS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-06-07 Cont ID  
Sent By dpalmer Date 2006-06-07 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2006-06-07 Time 18:58 Sent To  
Notes
2006-06-07 00:00:00************* PROVISO **************
  
 ** PLEASE KNOW, NO INSPECTIONS ARE TO BE
 DONE UNTIL THE BELOW NOTES ARE ADDESSED,
 SUBMITTED AND PASSED FOR REVIEW. REVISED
 PLANS WILL PAY REVISION FEES AND MUST BE
 ON JOBSITE BEFORE ANY SUCH INSPECTIONS.
  
 1) NOTE: PLEASE SEE PLANS REFLECT AND
 NOTE THE 2005 NFPA-101 WHEN WE ARE UNDER
 THE 2003 EDITION.
  
 2) NOTE: PLEASE SEE NOTE #2 FROM
 PREVIOUS REVIEW.
 PLEASE VERIFY LOAD ON EXISTING SERVICE
 WITH NEW LOADS ADDED.
 PLEASE SEE THE EXISTING LOAD SHOULD BE
 SHOWN WITH NEW LOADS BEING ADDED.
  
 220,220.35 ETC
 THESE MUST BE DONE AND ANY INSTALLATION
 OF ANY SERVICE EQUIPMENT BEFORE
 VERIFICATION OF SERVICE AND LOADS IS
 DONE AT THE CONTRACTORS OWN RISK AND CAN
 BE SUBJECT TO REMOVAL AND REPLACEMENT OF
 NEWER OR LARGER SERVICE EQUIPMENT
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-06-01 Cont ID  
Sent By dpalmer Date 2006-06-01 Time 12:05 Rev Time 0.00
Received By dpalmer Date 2006-06-01 Time 12:05 Sent To  
Notes
2006-06-01 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE NOTE #2 FROM
 PREVIOUS REVIEW.
 PLEASE VERIFY LOAD ON EXISTING SERVICE
 WITH NEW LOADS ADDED.
 PLEASE SEE THE EXISTING LOAD SHOULD BE
 SHOWN WITH NEW LOADS BEING ADDED.
  
 220,220.35 ETC
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2006-05-26 Time   Rev Time 0.00
Received By btrobaug Date 2006-05-26 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-09 Cont ID  
Sent By dpalmer Date 2006-05-09 Time 13:03 Rev Time 0.00
Received By dpalmer Date 2006-05-09 Time 12:15 Sent To  
Notes
2006-05-09 00:00:00* UNSAT *
  
 1) NOTE: PLEASE NOTE ON PLANS FOR "NO
 STORAGE" IN ELECTRICAL ROOM WHICH IS
 BEING SHOWN AS A CLOSET.
 PLEASE SEE 110.26,240.24,408.7
  
 2) NOTE: PLEASE PROVIDE SIZE AND LOAD ON
 EXISTING SERVICE..
 PLEASE SEE 220.35 FOR ALTERNATE METHOD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-06-02 Cont ID  
Sent By mwennerg Date 2006-06-02 Time 15:42 Rev Time 0.00
Received By mwennerg Date 2006-06-02 Time 15:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-05-15 Cont ID  
Sent By nmccray Date 2006-05-15 Time 10:41 Rev Time 0.00
Received By nmccray Date 2006-05-15 Time 10:35 Sent To  
Notes
2006-05-15 00:00:00******PROVISO**************************
 PLANS MEET AND COMPLIES WITH LIFE SAFETY
 CODES, BUT MUST COMPLY WITH THE OTHER
 TRADES REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-06 Cont ID  
Sent By adarroug Date 2006-07-06 Time 16:17 Rev Time 0.00
Received By adarroug Date 2006-07-06 Time 16:17 Sent To  
Notes
2006-07-19 00:00:00TO "COMM" BD#28-REV
 **ELECT. SHEETS PULLED BY CONTRACTOR PER
 DVP NOTES.ONLY NEEDS MECH AND PLUMB.
 ADARROUGH
  
2006-07-06 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-25 Cont ID  
Sent By adarroug Date 2006-06-25 Time 17:20 Rev Time 0.00
Received By adarroug Date 2006-06-25 Time 17:20 Sent To E
Notes
2006-06-25 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-24 Cont ID  
Sent By adarroug Date 2006-05-24 Time 18:48 Rev Time 0.00
Received By adarroug Date 2006-05-24 Time 18:48 Sent To  
Notes
2006-05-24 00:00:00TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-12 Cont ID  
Sent By adarroug Date 2006-05-12 Time 18:45 Rev Time 0.00
Received By rbrown Date 2006-04-17 Time 09:00 Sent To  
Notes
2006-05-10 00:00:00MOVED TO "BOB"#6
2006-05-03 00:00:00TO "COMM" BD#49
2006-04-17 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-01 Cont ID  
Sent By tgordon Date 2006-08-01 Time 14:05 Rev Time 0.35
Received By tgordon Date 2006-08-01 Time 14:05 Sent To  
Notes
2006-08-01 00:00:00REVISION TO MECH. PLANS PAGE 4.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-31 Cont ID  
Sent By tgordon Date 2006-05-31 Time 14:03 Rev Time 0.20
Received By tgordon Date 2006-05-31 Time 14:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-11 Cont ID  
Sent By tgordon Date 2006-05-11 Time 10:44 Rev Time 0.20
Received By tgordon Date 2006-05-11 Time 10:44 Sent To  
Notes
2006-05-11 00:00:00*** DENIED ***
 1) PAGE 4 MECHANICAL PLAN IS MISSING THE
 SIGNATURE OF THE ARCHITECT AT HIS SEAL
 ON ONE SET OF PLANS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2006-06-07 Cont ID  
Sent By jleech Date 2006-06-07 Time 09:58 Rev Time 0.00
Received By jleech Date 2006-06-07 Time 09:58 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2006-05-12 Cont ID  
Sent By jleech Date 2006-05-12 Time 09:50 Rev Time 0.00
Received By jleech Date 2006-05-12 Time 09:50 Sent To  
Notes
2006-05-12 00:00:00DENIED;
 1. ADD NOTE, VACUUM AND COMPRESSOR
 PIPING TO BE DONE BY A LICENSED MED-GAS
 CONTRACTOR PERMIT REQUIRED.
 2.SUBMIT MANUFACTURE'S INSTALLATION
 INFORMATION FOR COMPRESSOR AND VACUUM
 PUMP.
 3.VACUUM EXUST TO THE OUTSIDE, NFPA 99C
 2002 ADITION, SEC.5.3.3.6.4.1.
 4.SHOW VENTALATION TO EQUIPMENT ROOM,
 OTHER THAN A/C DROP SEC.5.3.3.3.3.
 5.PVC FITTINGS SHALL BE PRESSURE
 SEC.5.3.10.3.4.
 6. AIR LINES TO BE BRAZED. SEC.
 5.3.10.3.1
 6.CLEANOUTS REQUIRED ON VACUUM PIPING
 PER SEC.5.3.10.10.3.
 MED-GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-08-08 Cont ID  
Sent By pschmitz Date 2006-08-08 Time 15:14 Rev Time 0.00
Received By pschmitz Date 2006-08-08 Time 15:14 Sent To  
Notes
2006-08-08 00:00:008-8-06
 PHONE CONSERVATION WITH JEFF FISHER
 REQUESTING ME TO CHANGE SCOPE OF
 WORK REVISIOIN,FROM A WATER RISER TO A
 SANITARY RISER.
 THIS WILL PASS PLUMBING PLAN REVIEW.

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-08-05 Cont ID  
Sent By pschmitz Date 2006-08-05 Time 06:08 Rev Time 0.00
Received By pschmitz Date 2006-08-05 Time 06:08 Sent To  
Notes
2006-08-05 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
  
 1) REVISION SCOPE OF WORK STATES.
 PLUMBING - WATER RISER AS BUILT WHICH
 SHOULD BE ATTACHED TO SHT 3 OF 5
  
 SUBMITTAL IS A SANITARY RISER NOT A
 WATER RISER.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-06-07 Cont ID  
Sent By jleech Date 2006-06-07 Time 09:58 Rev Time 0.00
Received By jleech Date 2006-06-07 Time 09:58 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-12 Cont ID  
Sent By jleech Date 2006-05-12 Time 09:33 Rev Time 0.00
Received By jleech Date 2006-05-12 Time 09:33 Sent To  
Notes
2006-05-12 00:00:00DENIED;
 1.FRONTAL APPROACH REQUIRED FOR BREAK
 SINK. FBC-2004 CHAPTER 11 SECTIONS
 11-4.24.2 HIGHT, .3 KNEE CLEARANCE, .4
 DEPTH, .5 CLEAR FLOOR SPACE .6 EXPOSED
 PIPES, AND .7 FAUCET. SHOW DETAIL ON
 PLANS.
 2.AUTOCLAVE WASTE TO BE INDIRECTLY
 WASTED TO THE BUILDING DRAIN FBC-2004
 PLUMBING SEC. 713.3.
 3.HOT WATER REQUIRED AT DENTAL LAVS.
 SEC. 607.1.
 4.AIR ADMITANCE VALVES MUST COMPLY WITH
 SEC. 917.3.1 ONLY FOUR BRANCH INTERVALS
 FROM THE TOP OF STACK. (HOW MANY FLOORS
 ABOVE OFFICE?)
 5.PLEASE SIZE WATER PIPE PER APPENDIX E.
 (SERVICE SIZE SEAMS TOO SMALL)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695