Plan Review Stops For Permit 06040316 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2006-06-29 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-06-29 |
Time |
15:31 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-06-29 |
Time |
15:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-06-27 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-06-27 |
Time |
08:20 |
Rev Time |
0.50 |
Received By |
alange |
Date |
2006-06-27 |
Time |
08:20 |
Sent To |
|
|
Notes |
2006-06-27 00:00:00 | DENIED | | | | 1.SHOW GENERATOR SLAB DETAIL AND METHOD | | OF ATTACHMENT TO SLAB. | | | | 2. FEES DUE SEE ATTACHED INVOICE. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-05-23 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-05-23 |
Time |
10:50 |
Rev Time |
0.33 |
Received By |
alange |
Date |
2006-05-23 |
Time |
10:50 |
Sent To |
|
|
Notes |
2006-05-23 00:00:00 | DENIED | | | | SHOW GENERATOR SLAB DETAIL AND METHOD OF | | ATTACHMENT TO SLAB. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2006-06-21 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2006-06-21 |
Time |
07:42 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2006-06-21 |
Time |
07:12 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-04-24 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2006-04-24 |
Time |
18:20 |
Rev Time |
0.75 |
Received By |
btrobaug |
Date |
2006-04-24 |
Time |
17:51 |
Sent To |
M |
|
Notes |
2006-04-24 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SUBMIT ALL EQUIPMENT | | SPECIFICATIONS, GENERATOR AND TRANSFER | | SWITCH. IF THESE SPECS ARE GENERIC BE | | SURE TO HIGHLIGHT OR OTHERWISE INDICATE | | THE MODELS INTENDED TO BE USD. | | | | 2} THE PLANS ARE NOT CLEAR. ONE SHEET | | INDICATES 2-200 AMP DISCONNECTS, FROM | | THE GENERATOR, FEEDING ATS'S, ANOTHER | | SHOWS 2-200 AMP DISCONNECTS FROM A | | GUTTER FEEDING THEM, WITH THE GENERATOR | | SIDE FEED NOT SHOWN.AND ANOTHER SHEET | | SHOWING 3-100 AMP PANELS OR DISCONNECTS | | (PLAN DOESN'T SAY), NOT FEEDING | | ANYTHING, APPARANTLY FED FROM THE SAME | | GUTTER AS THE 2-200 AMP DISCONNECTS ON | | THE PREVIOUS PAGE. | | | | PLEASE SUBMIT A SITE PLAN SHOWING ALL | | THIS EQUIPMENT AND WHAT IT FEEDS. | | | | 3} THE HEAT LOAD ISN'T IN THE LOAD CALC. | | PLEASE INCLUDE, IF SMALLER THAN THE | | CONDENERLOADS , PLEASE INDICATE SAME. | | | | 4} THE VALUE ON THE APPLICATION MUST | | INCLUDE THE VALUE, LABOR AND MATERIAL OF | | THE ENTIRE INSTALLATION, INCLUDING THE | | GENERATOR, PAD AND ATS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
N |
Date |
2006-06-21 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-06-21 |
Time |
09:36 |
Rev Time |
0.15 |
Received By |
mperson |
Date |
2006-06-21 |
Time |
09:36 |
Sent To |
B |
|
Notes |
2006-06-21 00:00:00 | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | BEFORE FINAL GEN/RES INSPECTION. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2006-04-28 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-04-28 |
Time |
11:35 |
Rev Time |
0.15 |
Received By |
mperson |
Date |
2006-04-28 |
Time |
11:35 |
Sent To |
B |
|
Notes |
2006-04-28 00:00:00 | ******DENIED****** | | REFERENCE: FBC-2004 FUEL GAS | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR PLAN REVIEW FOR GAS PERMIT: | | | | 1. SEE ZONING COMMENT #1 | | 2. SEE ELECTRICAL COMMENTS #1 AND #4 | | 3. SEE MECHANICAL COMMENTS #1 | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDERSUPERVISION OF K/STEVENS | | (561) 805-6721 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2006-06-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-06-29 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-06-29 |
Time |
14:29 |
Sent To |
B |
|
Notes |
2006-06-29 00:00:00 | TO "ALANGE" BOX/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2006-06-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-06-19 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-06-19 |
Time |
11:32 |
Sent To |
E |
|
Notes |
2006-06-19 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-06-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-06-07 |
Time |
17:25 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-06-07 |
Time |
17:25 |
Sent To |
Z |
|
Notes |
2006-06-07 00:00:00 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-04-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-04-21 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-04-21 |
Time |
11:02 |
Sent To |
E |
|
Notes |
2006-04-21 00:00:00 | TO "GEN-RES" "E" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-05-23 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-05-23 |
Time |
10:51 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-04-12 |
Time |
14:55 |
Sent To |
|
|
Notes |
2006-04-12 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2006-06-21 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-06-21 |
Time |
09:14 |
Rev Time |
0.15 |
Received By |
tgordon |
Date |
2006-06-21 |
Time |
09:14 |
Sent To |
P |
|
Notes |
2006-06-21 00:00:00 | *** PROVISO *** | | 1) PER 2004 FBC, FUEL GAS - POWERED | | EQUIPMENT - PERMANENTLY INSTALLED | | EQUIPMENT POWERED BY INTERNAL COMBUSTION | | ENGINES SHALL BE INSTALLED IN ACCORDANCE | | WITH MANUFACTURE'S INSTALLATION | | INSTRUCTIONS AND NFPA 37. | | | | NFPA 37 INSTALLATION & USE OF STATIONARY | | COMBUSTION ENGINES & GAS TURBINES: | | 4.1.4ENGINES (GENERATORS) LOCATED | | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM | | OPENINGS IN WALLS & AT LEAST 5 FT FROM | | STRUCTURES HAVING COMBUSTIBLE WALLS.A | | MINIMUM CLEARANCE IS NOT REQUIRED WHEN | | (1) THE ADJACENT WALL HAS A MINIMUM FIRE | | RESISTANCE RATING OF 1 HOUR OR (2) THE | | WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF | | NON-COMBUSTIBLE MATERIALS, AND IT HAS | | BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | MATERIALS OUTSIDE THE ENCLOSURE. | | A.8.2.3.1EXHAUST SYSTEMS SHOULD NOT | | TERMINATE UNDER STRUCTURES OR WHERE THE | | EXHAUST MIGHT BE DRAWN INTO THE | | VENTILATION INTAKES. | | | | 2004 FMC 804.3.5 #3, WHERE THE | | TERMINATION IS LOCATED BELOW AN ADJACENT | | ROOF STRUCTURE, THE TERMINATION POINT | | SHALL BE LOCATED AT LEAST 3 FT FROM THE | | ROOF STRUCTURE. | | | | PLEASE NOTE, WHILE ZONING ALLOWS | | MECHANICAL EQUIPMENT TO ENCROACH 4 FT | | INTO THE SETBACK, GENERATORS SHALL | | MAINTAIN THE REQUIRED ABOVE MENTIONED | | CLEARANCES TO THE ADJACENT PROPERTY | | STRUCTURES, I.E. FENCE, BUILDING, | | WINDOWS, DOORS, OR OPENINGS. | | | | PROVIDE MANUFACTURE'S INSTALLATION | | INSTRUCTIONS AT THE JOBSITE FOR THE | | FIELD INSPECTOR. | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-04-27 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-04-27 |
Time |
08:21 |
Rev Time |
0.15 |
Received By |
tgordon |
Date |
2006-04-27 |
Time |
08:21 |
Sent To |
P |
|
Notes |
2006-04-27 00:00:00 | *** DENIED *** | | 1) PLANS MAY NOT BE DONE IN PENCIL. | | | | 2) PLEASE SUBMIT SITE PLAN SHOWING | | PROPOSED LOCATION OF GENERATOR, SEE NOTE | | #3. | | | | 3)GENERATOR EXHUST MUST BE TEN FEET AWAY | | FROM ANY BUILDING OPENINGS (WINDOWS, | | DOORS, ROOF & EAVE VENTS), AND TEN FEET | | AWAY FROM ADJECENT BUILDING OPENS. PER | | 2004 FBC/M 401.5.1 . | | | | 4) SEE ELECTRICAL NOTE #4. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2006-06-21 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-06-21 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2006-06-21 |
Time |
09:35 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2006-04-28 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-04-28 |
Time |
11:34 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2006-04-28 |
Time |
11:34 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2006-06-16 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-06-16 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-06-16 |
Time |
16:31 |
Sent To |
I |
|
Notes |
2006-06-16 00:00:00 | NOTE: THE PROPOSED GENERATOR WILL BE | | 22FT FROM SIDE PROPERTY LINE. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2006-04-20 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-04-20 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-04-20 |
Time |
11:16 |
Sent To |
I |
|
Notes |
2006-04-20 00:00:00 | DENIED, | | 1. THE PROPOSED GENERATOR MUST BE SHOWN | | ON TWO COPY OF CURRENT SURVEYS SHOWING | | THE SETBACK FROM PROPERTY LINE. | | | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|