Plan Review Details - Permit 06040316
Plan Review Stops For Permit 06040316
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-29 Cont ID  
Sent By alange Date 2006-06-29 Time 15:31 Rev Time 0.00
Received By alange Date 2006-06-29 Time 15:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-27 Cont ID  
Sent By alange Date 2006-06-27 Time 08:20 Rev Time 0.50
Received By alange Date 2006-06-27 Time 08:20 Sent To  
Notes
2006-06-27 00:00:00DENIED
  
 1.SHOW GENERATOR SLAB DETAIL AND METHOD
 OF ATTACHMENT TO SLAB.
  
 2. FEES DUE SEE ATTACHED INVOICE.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-23 Cont ID  
Sent By alange Date 2006-05-23 Time 10:50 Rev Time 0.33
Received By alange Date 2006-05-23 Time 10:50 Sent To  
Notes
2006-05-23 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-21 Cont ID  
Sent By btrobaug Date 2006-06-21 Time 07:42 Rev Time 0.50
Received By btrobaug Date 2006-06-21 Time 07:12 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-24 Cont ID  
Sent By btrobaug Date 2006-04-24 Time 18:20 Rev Time 0.75
Received By btrobaug Date 2006-04-24 Time 17:51 Sent To M
Notes
2006-04-24 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT ALL EQUIPMENT
 SPECIFICATIONS, GENERATOR AND TRANSFER
 SWITCH. IF THESE SPECS ARE GENERIC BE
 SURE TO HIGHLIGHT OR OTHERWISE INDICATE
 THE MODELS INTENDED TO BE USD.
  
 2} THE PLANS ARE NOT CLEAR. ONE SHEET
 INDICATES 2-200 AMP DISCONNECTS, FROM
 THE GENERATOR, FEEDING ATS'S, ANOTHER
 SHOWS 2-200 AMP DISCONNECTS FROM A
 GUTTER FEEDING THEM, WITH THE GENERATOR
 SIDE FEED NOT SHOWN.AND ANOTHER SHEET
 SHOWING 3-100 AMP PANELS OR DISCONNECTS
 (PLAN DOESN'T SAY), NOT FEEDING
 ANYTHING, APPARANTLY FED FROM THE SAME
 GUTTER AS THE 2-200 AMP DISCONNECTS ON
 THE PREVIOUS PAGE.
  
 PLEASE SUBMIT A SITE PLAN SHOWING ALL
 THIS EQUIPMENT AND WHAT IT FEEDS.
  
 3} THE HEAT LOAD ISN'T IN THE LOAD CALC.
 PLEASE INCLUDE, IF SMALLER THAN THE
 CONDENERLOADS , PLEASE INDICATE SAME.
  
 4} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE VALUE, LABOR AND MATERIAL OF
 THE ENTIRE INSTALLATION, INCLUDING THE
 GENERATOR, PAD AND ATS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-06-21 Cont ID  
Sent By mperson Date 2006-06-21 Time 09:36 Rev Time 0.15
Received By mperson Date 2006-06-21 Time 09:36 Sent To B
Notes
2006-06-21 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-04-28 Cont ID  
Sent By mperson Date 2006-04-28 Time 11:35 Rev Time 0.15
Received By mperson Date 2006-04-28 Time 11:35 Sent To B
Notes
2006-04-28 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR GAS PERMIT:
  
 1. SEE ZONING COMMENT #1
 2. SEE ELECTRICAL COMMENTS #1 AND #4
 3. SEE MECHANICAL COMMENTS #1
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDERSUPERVISION OF K/STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-29 Cont ID  
Sent By adarroug Date 2006-06-29 Time 14:29 Rev Time 0.00
Received By adarroug Date 2006-06-29 Time 14:29 Sent To B
Notes
2006-06-29 00:00:00TO "ALANGE" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 11:32 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 11:32 Sent To E
Notes
2006-06-19 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 17:25 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 17:25 Sent To Z
Notes
2006-06-07 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 11:02 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 11:02 Sent To E
Notes
2006-04-21 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-23 Cont ID  
Sent By alange Date 2006-05-23 Time 10:51 Rev Time 0.00
Received By alange Date 2006-04-12 Time 14:55 Sent To  
Notes
2006-04-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-21 Cont ID  
Sent By tgordon Date 2006-06-21 Time 09:14 Rev Time 0.15
Received By tgordon Date 2006-06-21 Time 09:14 Sent To P
Notes
2006-06-21 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 A.8.2.3.1EXHAUST SYSTEMS SHOULD NOT
 TERMINATE UNDER STRUCTURES OR WHERE THE
 EXHAUST MIGHT BE DRAWN INTO THE
 VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE SETBACK, GENERATORS SHALL
 MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY
 STRUCTURES, I.E. FENCE, BUILDING,
 WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-27 Cont ID  
Sent By tgordon Date 2006-04-27 Time 08:21 Rev Time 0.15
Received By tgordon Date 2006-04-27 Time 08:21 Sent To P
Notes
2006-04-27 00:00:00*** DENIED ***
 1) PLANS MAY NOT BE DONE IN PENCIL.
  
 2) PLEASE SUBMIT SITE PLAN SHOWING
 PROPOSED LOCATION OF GENERATOR, SEE NOTE
 #3.
  
 3)GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
  
 4) SEE ELECTRICAL NOTE #4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status N Date 2006-06-21 Cont ID  
Sent By mperson Date 2006-06-21 Time 09:35 Rev Time 0.00
Received By mperson Date 2006-06-21 Time 09:35 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-04-28 Cont ID  
Sent By mperson Date 2006-04-28 Time 11:34 Rev Time 0.00
Received By mperson Date 2006-04-28 Time 11:34 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-06-16 Cont ID  
Sent By mmclean Date 2006-06-16 Time 16:32 Rev Time 0.00
Received By mmclean Date 2006-06-16 Time 16:31 Sent To I
Notes
2006-06-16 00:00:00NOTE: THE PROPOSED GENERATOR WILL BE
 22FT FROM SIDE PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-20 Cont ID  
Sent By mmclean Date 2006-04-20 Time 11:16 Rev Time 0.00
Received By mmclean Date 2006-04-20 Time 11:16 Sent To I
Notes
2006-04-20 00:00:00DENIED,
 1. THE PROPOSED GENERATOR MUST BE SHOWN
 ON TWO COPY OF CURRENT SURVEYS SHOWING
 THE SETBACK FROM PROPERTY LINE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720