Plan Review Details - Permit 06040232
Plan Review Stops For Permit 06040232
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-05-09 Cont ID  
Sent By alange Date 2006-05-09 Time 11:19 Rev Time 0.33
Received By alange Date 2006-05-09 Time 11:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-04-19 Cont ID  
Sent By btrobaug Date 2006-04-19 Time 12:32 Rev Time 1.00
Received By btrobaug Date 2006-04-19 Time 12:08 Sent To M
Notes
2006-04-19 00:00:00 
 SPOKE WITH KEVIN WHO WILL INCREASE THE
 VALUE TO INCLUDE THE GENERATOR AN DPAD
 LABOR AND MATERIAL WHEN PICKING UP
 PERMIT, OR RESUBMITTING IF PLANS FAIL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-04-24 Cont ID  
Sent By mperson Date 2006-04-24 Time 09:53 Rev Time 0.15
Received By mperson Date 2006-04-24 Time 09:53 Sent To B
Notes
2006-04-24 00:00:00NOTE: GAS PERMIT REQUIRED. GAS
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT
 APPLICATION. ALL GAS INSPECTIONS TO BE
 COMPLETE BEFORE FINAL GEN/RES
 INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-02 Cont ID  
Sent By adarroug Date 2006-06-02 Time 11:53 Rev Time 0.00
Received By adarroug Date 2006-06-02 Time 11:53 Sent To E
Notes
2006-06-02 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-23 Cont ID  
Sent By adarroug Date 2006-05-23 Time 15:41 Rev Time 0.00
Received By adarroug Date 2006-05-23 Time 15:41 Sent To Z
Notes
2006-05-23 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-14 Cont ID  
Sent By adarroug Date 2006-04-14 Time 09:21 Rev Time 0.00
Received By adarroug Date 2006-04-14 Time 09:21 Sent To E
Notes
2006-04-14 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-09 Cont ID  
Sent By alange Date 2006-05-09 Time 11:19 Rev Time 0.00
Received By alange Date 2006-04-10 Time 14:53 Sent To  
Notes
2006-04-10 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-05 Cont ID  
Sent By tgordon Date 2006-06-05 Time 11:34 Rev Time 0.20
Received By tgordon Date 2006-06-05 Time 11:34 Sent To  
Notes
2006-06-05 00:00:00 
 *** PROVISO ***
 PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 A.8.2.3.1EXHAUST SYSTEMS SHOULD NOT
 TERMINATE UNDER STRUCTURES OR WHERE THE
 EXHAUST MIGHT BE DRAWN INTO THE
 VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE SETBACK, GENERATORS SHALL
 MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY
 STRUCTURES, I.E. FENCE, BUILDING,
 WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-19 Cont ID  
Sent By tgordon Date 2006-04-19 Time 13:34 Rev Time 0.15
Received By tgordon Date 2006-04-19 Time 13:34 Sent To P
Notes
2006-04-19 00:00:00*** DENIED ***
 1) NEED TO PASS ZONING.
  
 2) GENERATOR EXHUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT BUILDING
 OPENS. PER 2004 FBC/M 401.5.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-04-24 Cont ID  
Sent By mperson Date 2006-04-24 Time 09:52 Rev Time 0.00
Received By mperson Date 2006-04-24 Time 09:52 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-06-01 Cont ID  
Sent By mmclean Date 2006-06-01 Time 15:37 Rev Time 0.00
Received By mmclean Date 2006-06-01 Time 15:37 Sent To I
Notes
2006-06-01 00:00:00APPROVING GENERATOR THAT WILL BE 3'6"
 FROM SIDE PROPERTY LINE

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-13 Cont ID  
Sent By mmclean Date 2006-04-13 Time 15:52 Rev Time 0.00
Received By mmclean Date 2006-04-13 Time 15:52 Sent To I
Notes
2006-04-13 00:00:00DENIED,
 1. MUST SHOW ON THE TWO COPY SURVEY THE
 SETBACK OF THE PROPOSED GENERATOR FROM
 THE SIDE PROPERTY LINE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720