Plan Review Details - Permit 06040218
Plan Review Stops For Permit 06040218
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-15 Cont ID  
Sent By shill Date 2006-05-15 Time 08:32 Rev Time 0.00
Received By shill Date 2006-05-12 Time 12:26 Sent To  
Notes
2006-05-15 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.THE NOC MUST
 INCLUDE THE LEGAL DESCRIPTION, FS713.13.
  
 2.)THE SITE PLAN SHOWS A PROPOSED
 CHURCH, SURVEY SHOWS THE CHURCH AS
 EXISTING.CLARIFY SCOPE OF WORK.
  
 3.)SEE FBC11-4.1(1)(A).THIS SECTION
 AFFECTS SOME OF THE COMMENTS BELOW.
  
 4.)THE ACCESSIBLE PARKING DETAIL IS TO
 COMPLY WITH CITY OF WEST PALM BEACH
 STANDARDS, SEE ATTACHED.
  
 5.)SHOW THE ACCESSIBLE ROUTE
 FBC11-4.1.2(2).SHOW WIDTH AND SLOPE.
  
 6.)SHOW THE ACCESSIBLE ENTRANCES.
 COMPLIANCE WITH FBC11-4.6.2 CANNOT BE
 DETERMINED WITHOUT THIS INFORMATION.
  
 7.)PROVIDE WIDTH OF THE ACCESSIBLE
 PARKING SPACES, FBC11-4.6.2.
  
 8.)SEE FBC11-4.6.2(1), SHOW 44IN
 ACCESSIBLE ROUTE.
  
 9.)SEE FBC11-4.6.2(1), THE ACCESSIBLE
 PARKING SPACE TO THE SOUTH, PASSENGER
 MUST WALK BEHIND A PARKED CAR.REVISE.
  
 10.)SHOW THE WIDTH OF THE PARKING
 ACCESS AISLES AND SHOW HOW THEY CONNECT
 TO AN ACCESSIBLE ROUTE, FBC11-4.6.3.
  
 11.)SHOW MAX CROSS SLOPE OF PARKING
 SPACES, FBC11-4.6.3.
  
 12.)NO SIGNAGE IS SHOWN.SEE
 FBC11-4.6.4 AND SHOW COMPLIANCE.
  
 13.)SEE FS481.229.THIS IMPROVEMENT
 INVOLVING ACCESSIBILITY DOES NOT FALL
 UNDER ANY OF THE EXEMPTIONS TO
 ARCHITECTURE.
  
 14.)SEE FS471.003.IT IS NOT CLEAR
 HOW THE STRUCTURAL ELEMENT OF THE 6?
 HIGH BLOCK WALL IS EXEMPT FROM
 PROFESSIONAL ENGINEERING.
  
 15.)IRRIGATION AND DRAINAGE HAVE BEEN
 CHECKED ON THE PERMIT APPLICATION, BUT
 NO PLANS WERE PROVIDED.NOTE THAT NO
 PLUMBING REVIEW HAS BEEN DONE AS NO
 PLUMBING INFORMATION WAS PROVIDED.
 SEPARATE PERMIT WITH SEPARATE PLANS
 REQUIRED.PLEASE REMOVE FROM THE PERMIT
 APPLICATION.
  
 16.)PROVIDE WIND DESIGN CRITERIA
 FBC1603.1.4.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2006-05-04 Cont ID  
Sent By dpalmer Date 2006-05-04 Time 17:34 Rev Time 0.00
Received By dpalmer Date 2006-05-04 Time 17:34 Sent To  
Notes
2006-05-04 00:00:00NO ELECTRICAL SUBMITTED FOR SITE
 LIGHTING /PARKING LOT LIGHTING.
  
 NO ELECTRICAL CONT SIGNED ON.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2006-05-30 Time   Rev Time 0.50
Received By   Date 2006-05-30 Time   Sent To L
Notes
2006-05-30 00:00:001.DRAINAGE CALCULATIONS INDICATINGON
 SITE RETENTION FOR WATER QUALITY
 TREATMENT, AND PRE VS. POST DEVELOPMNET
 DISCHARGE MUST BE SUBMITTED.
  
 2. PLEASE SUBMIT PLANS FOR PROPOSED
 DRAINAGE DESIGN.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-18 Cont ID  
Sent By shill Date 2006-05-30 Time 14:58 Rev Time 0.00
Received By shill Date 2006-04-17 Time 12:04 Sent To  
Notes
2006-05-30 00:00:00PLANS FILED UNDER 'K'
2006-05-25 00:00:005/25/06-TAKEN FROM "COMM" BD AND ROUTED
 TO "ENG"
2006-05-03 00:00:00TO "COMM" BD#21
2006-04-17 00:00:00WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 1 Status F Date 2006-05-23 Cont ID  
Sent By eschneid Date 2006-05-23 Time 16:28 Rev Time 0.00
Received By eschneid Date 2006-05-23 Time 16:28 Sent To  
Notes
2006-05-23 00:00:001) THE BROADWAY MIXED USE DISTRICT
 REGULATIONS REQUIRE THAT WHEN PERMITS
 EXCEED $10,000 IN VALUE, THE LANDSCAPE
 ON-SITE IS REQUIRED TO BE BROUGHT INTO
 CONFORMITY WITH THE CURRENT CODE.
  
 2) NO LANDSCAPE PLAN SUBMITTED.
  
 3) THE PARKING LOTS (LAYOUT AND
 LANDSCAPING) DO NOT CONFORM TO THE
 ZONING AND LAND DEVELOPMENT CODE
 DIMENSIONAL REQUIREMENTS.
  
 A) NO PARKING DETAILS INCLUDED.
  
 B) THE PARKING SPACES IN THE SOUTHERN
 PARKING AREA ARE NOT DEEP ENOUGH FOR THE
 ANGLES AS SHOWN.
  
 C) THE PARKING AILSES ARE NOT WIDE
 ENOUGH.
  
 4) THE DATA TABLE AND THE PARKING TABLE
 HAVE NUMEROUS MISTAKES.
  