Plan Review Details - Permit 06040215
Plan Review Stops For Permit 06040215
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-03 Cont ID  
Sent By mjacobs Date 2006-05-03 Time 14:20 Rev Time 0.00
Received By mjacobs Date 2006-05-01 Time 18:03 Sent To  
Notes
2006-05-01 00:00:001)EXISTING BUILDING CODE 304.1 SCOPE.
 LEVEL 2 ALTERATIONS INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION
 OR ELIMINATION OF ANY DOOR OR WINDOW,
 THE RECONFIGURATION OR EXTENSION OF ANY
 SYSTEM, OR THE INSTALLATION OF ANY
 ADDITIONAL EQUIPMENT. LEVEL 2
 ALTERATIONS SHALL COMPLY WITH CH.5 AND
 CH.6.
  
 2) 605.4.2 DOOR SWING .
 IN THE WORK AREA AND IN THE EGRESS PATH
 FROM ANY WORK AREA TO THE EXIT
 DISCHARGE, ALL EGRESS DOORS SERVING AN
 OCCUPANT LOAD GREATER THAN 50 SHALL
 SWING IN THE DIRECTION OF EXIT TRAVEL.
 SEE EGRESS DOORS ON PAGES 2/6 AND 5/6.
 THE NEW FRENCH DOORS CANNOT SWING INTO
 THE DOOR LEADING FROM THE STAIR-WAY.
 THIS DESIGN WILL NOT MEET EGRESS
 REQUIREMENTS.FBC.1008.1.8.8/1008.1.9
  
 3) SHEET 2/6 SHOWS A NEW WALL AT THE END
 OF THE HALL WAY, HOWEVER, ON SHEETS E-2
 AND E-4 THE WALL IS NOT SHOWN. THE FLOOR
 LAY-OUT SHOULD SHOW THE SAME DESIGN ON
 EACH PAGE.
  
 4) WILL THE EXIT ACCESS ON THE SECOND
 FLOOR LEAD TO THE ROOF? PLEASE SHOW IF
 THERE IS A HALLWAY OR CORRIDOR LEADING
 TO THE STAIRWAY IS THERE A PANIC LATCH
 ON THE DOOR LEADING TO THE STAIRS? THAT
 PATH OF TRAVEL WHICH LEADS TO THE ROOF
 NEEDS MORE DETAILS.
 FBC.1008.1.8 DOOR OPERATIONS.
 EXCEPT AS SPECIFICALLY PERMITTED BY THIS
 SECTION EGRESS DOORS SHALL BE READILY
 OPENABLE FROM THE EGRESS SIDE WITHOUT
 THE USE OF A KEY OR SPECIAL KNOWLEDGE OR
 EFFORT.
  
 5) IS THERE A WORKING AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN THE
 BULDING?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-21 Cont ID  
Sent By btrobaug Date 2006-06-21 Time 15:07 Rev Time 0.75
Received By btrobaug Date 2006-04-19 Time 16:33 Sent To  
Notes
2006-04-20 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}ALL DEVICES AND SERVICE COMPONENTS
 INDICATE THEY ARE EXISTING. IF
 EVERYTHING ON THE PLAN IS EXISTING,
 PLEASE INDICATE WHAT IS TO BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-04-26 Cont ID  
Sent By mwennerg Date 2006-04-26 Time 15:14 Rev Time 0.00
Received By mwennerg Date 2006-04-26 Time 15:14 Sent To  
Notes
2006-04-26 00:00:00******DENIED******
  
 1) THE MAIN ENTRANCE DOORS SWING AGAINST
 THE DIRECTION OF TRAVEL. EXIT DOORS
 SERVING AN OCCUPANT LOAD OF 50 OR MORE
 SHALL SWING IN THE DIRECTION OF TRAVEL.
 NFPA 101, SECTION 7.2.1.4.2.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 3) PLEASE ILLUSTRATE THE MAXIMUM TRAVEL
 DISTANCES ON LIFE SAFETY SHEETS.
  
 4) PLEASE INDICATE THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 5) SECOND FLOOR LIFE SAFETY PLAN
 ILLUSTRATES PERSONS BEING DIRECTED
 ACROSS THE FIRST FLOOR ROOF TO STAIRS
 THAT AREN'T MARKED AN EXIT. PLEASE
 EXPLAIN RATIONALE.
  
 6) IS THIS BUILDING PROTECTED BY FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS?
  
 7) DOORS SERVING AREAS WITH OCCUPANT
 LOAD GREATER THAN 100 SHALL HAVE PANIC
 HARDWARE. IS THIS AN EXISTING CONDITION?
 NO DOOR SCHEDULE FOUND ON PLANS.
  
 8) WILL THE NEW FRENCH DOORS CONFLICT
 WITH THE EXISTING STAIR DOOR?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-21 Cont ID  
Sent By btrobaug Date 2006-06-21 Time 15:08 Rev Time 0.00
Received By btrobaug Date 2006-04-17 Time 12:22 Sent To PC
Notes
2006-04-21 00:00:004/21/06-PUT BACK ON BOB#15
2006-04-20 00:00:004/20/06-APPL. PUT ON HOLD AND SENT TO
 ADRIANNA MCKENZIE
2006-04-18 00:00:00TO "BOB"#15
2006-04-17 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-04-18 Cont ID  
Sent By tgordon Date 2006-04-18 Time 14:52 Rev Time 0.15
Received By tgordon Date 2006-04-18 Time 14:52 Sent To  
Notes
2006-04-18 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-24 Cont ID  
Sent By jleech Date 2006-04-24 Time 14:53 Rev Time 0.00
Received By jleech Date 2006-04-24 Time 14:53 Sent To  
Notes
2006-04-24 00:00:00DENIED;
 1.WOMANS BATHROOM FACILITIES DO NOT
 COMPLY WITH FBC-2004 PLUMBING TABLE
 403.1 #1 A-3. (WOMANS ROOM NOT SHOWN)
 MUST COMPLY WITH SEC403.2.
 2.DRINKING FOUNTAIN REQUIRED PER TABLE
 403.1. BOTTLE WATER CANNOT REPLACE THE
 FIRST DRINKING FOUNTAIN PER SEC. 410.1
 THE BOTTLE COOLER CAN BE USED ON THE 2ND
 FLOOR.
 3.WATER RISER DIAGRAM IS REQUIRED PER
 FBC-2004 CHAPTER 1, ADMINISTRATION CODE,
 SEC.106.3.5.1.3.
 4.SANITARY RISER DIAGRA, URINALS ARE NOT
 VENTED. THE 3" BUILDING DRAIN FROM THE
 URINAL TO THE W/C DRAIN IS REQUIRED TO
 BE 3" FOR VENTING SEE TABLE 909.3 WET
 VENT SIZING.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695