Plan Review Details - Permit 06040115
Plan Review Stops For Permit 06040115
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-05-22 Cont ID  
Sent By alange Date 2006-05-22 Time 16:43 Rev Time 0.50
Received By alange Date 2006-05-22 Time 16:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-23 Cont ID  
Sent By btrobaug Date 2006-05-23 Time 11:58 Rev Time 0.50
Received By btrobaug Date 2006-05-23 Time 11:58 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-12 Cont ID  
Sent By dpalmer Date 2006-04-12 Time 17:39 Rev Time 0.00
Received By dpalmer Date 2006-04-12 Time 17:39 Sent To Z
Notes
2006-04-12 00:00:00*******UNSAT *******
  
 1) NOTE: PLEASE INCLUDE LOCATIONS OF ALL
 SERVICE EQUIPMENT AS SHOWN ON RISER ON
 THE PROVIDED SITE LAYOUT. PLEASE SEE
 PLANS, AT CURRENT TIME ONLY INDICATE THE
 ATS ON THE OUTSIDE OF DWELLING.
 215.5
  
 2) NOTE: PLEASE SEE RISER SUBMITTED DOES
 NOT SHOW HOW THE SYSTEM WILL TRANSFER.
 PLEASE SEE LINE AND LOAD FROM MAIN TO
 THE PANEL BEING FED FROM GEN DO NOT GO
 THROUGHT THE ATS.
 215.5 PLEASE ADJUST RISER.
  
 3) NOTE: PLEASE SEE CONDUCTORS SHOWN AS
 3- #2/3'S?? PLEASE SEE 310.16 FOR MIN
 AGW SIZES AND ADJUST.
 215.5
  
 4) NOTE: PLEASE INCLUDE DISCONNECTING
 MEANS FROM GEN TO SSERVICE/ATS LOCATED
 ON HOUSE GROUPED WITH EXISTING MAINS.
 THIS DISCONNECTING MEANS IS NOT REQUIED
 TO CONTAIN OCP , ONLY DISC.
 225.31-225.39.
  
 5) NOTE: PLEASE INDICATE THE ATS BEING
 USED FROM SPECS.
 PLEASE INDICATE THE AIC RAITNG FOR ATS.
 NFPA-110, 6.5.2, NEC 110.9
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW., IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-04-28 Cont ID  
Sent By mperson Date 2006-04-28 Time 11:17 Rev Time 0.15
Received By mperson Date 2006-04-28 Time 11:17 Sent To B
Notes
2006-04-28 00:00:00NOTE: GAS PERMIT REQUIRED. GAS
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT
 APPLICATION. ALL GAS INSPECTIONS TO BE
 COMPLETE BEFORE FINAL GEN/RES
 INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-24 Cont ID  
Sent By adarroug Date 2006-04-24 Time 09:59 Rev Time 0.00
Received By adarroug Date 2006-04-24 Time 09:59 Sent To M
Notes
2006-04-24 00:00:00TO "GEN-RES" "M"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-22 Cont ID  
Sent By alange Date 2006-05-22 Time 16:43 Rev Time 0.00
Received By alange Date 2006-04-05 Time 16:32 Sent To  
Notes
2006-04-05 00:00:00TO "Z' BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-04-27 Cont ID  
Sent By tgordon Date 2006-04-27 Time 08:17 Rev Time 0.15
Received By tgordon Date 2006-04-27 Time 08:17 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-04-28 Cont ID  
Sent By mperson Date 2006-04-28 Time 11:17 Rev Time 0.00
Received By mperson Date 2006-04-28 Time 11:16 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-21 Cont ID  
Sent By mmclean Date 2006-04-21 Time 07:39 Rev Time 0.00
Received By mmclean Date 2006-04-21 Time 07:39 Sent To I
Notes
2006-04-21 00:00:00NOTE: GENERATOR CAN ONLY ENROACH 4FT
 INTO A SETBACK.


Account Summary | Usage Policy | Privacy Policy