Plan Review Details - Permit 06040063
Plan Review Stops For Permit 06040063
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-04 Cont ID  
Sent By jwitmer Date 2006-05-04 Time 07:58 Rev Time 1.11
Received By jwitmer Date 2006-05-04 Time 07:58 Sent To PC
Notes
2006-05-04 00:00:00REVIEWED FOR RESIST THE OVERTURNING
 EFFECT CAUSSED BY LATERAL FORCES,
 SECTION 1609.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-10 Cont ID  
Sent By jwitmer Date 2006-04-10 Time 16:54 Rev Time 1.11
Received By jwitmer Date 2006-04-10 Time 16:02 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-08-06 Cont ID  
Sent By dpalmer Date 2006-08-06 Time 09:46 Rev Time 0.00
Received By dpalmer Date 2006-08-06 Time 09:26 Sent To PC
Notes
2006-08-06 00:00:00** PROVISO **
  
 *** PLANS REDLINED **
  
 ** PLEASE SEE REVISIONS ARE FOR VE OF
 CONDUCTORS ONLY.
 PLEASE SEE NOTES BELOW WHICH WERE
 REDLINED ON 6/18/06 HAS NOT YET BEEN
 VERIFIED BY THIS OFFICE.
  
  
 MAIN SWITCH GEAR AND ATS TO BE VERIFIED
 IN THE FIELD FOR COMPLIANCE PERNEC
 230.76, 230.79, 230.72 225.31-225.39.
 EQUIPMENT SHALL ALSO BE ALL LISTED BY A
 NRTL AND CONTAIN ALL SUCH LISTINGS.
  
 ** LISTINGS OF THE EQUIPMENT CAN NOT BE
 VERIFIED BASED ON SUBMITTIALS AND PLANS.
 E-MAILS AND INFORMATION FROM BOTH
 ENGINEERS ARE ON FILE AS RECORD.
 INSTALLATION OF THIS EQUIPMENT IS AT
 CONTRACTORS OWN RISK UNTIL ALL
 REQUIRMENTS LISTED ABOVE ARE MET AND
 VERIFIED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-06-18 Cont ID  
Sent By dpalmer Date 2006-06-18 Time 13:00 Rev Time 0.00
Received By dpalmer Date 2006-06-18 Time 12:57 Sent To PC
Notes
2006-06-18 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE ONLY SUBMIT REVISED
 PAGES AND SHEETS RELEVANT TO NEW
 PROPOSED CONDUCTORS.
 PLEASE SEE MANY OTHER SHEETS WERE
 SUBMITTED FOR FUEL, STRUCTURAL ETC.
  
 IF CONTRACTOR WANTS TO REMOVE ALL OTHER
 SHEETS THAT DO NOT APPLY, THEN THE
 ELECTRICAL CAN BE SUBMITTED WITHOUT A
 FEE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-06-02 Cont ID  
Sent By dpalmer Date 2006-06-02 Time 17:39 Rev Time 0.00
Received By dpalmer Date 2006-06-02 Time 17:39 Sent To PC
Notes
2006-06-02 00:00:00*** PLANS REDLINED **
  
  
 MAIN SWITCH GEAR AND ATS TO BE VERIFIED
 IN THE FIELD FOR COMPLIANCE PERNEC
 230.76, 230.79, 230.72 225.31-225.39.
 EQUIPMENT SHALL ALSO BE ALL LISTED BY A
 NRTL AND CONTAIN ALL SUCH LISTINGS.
  
 ** LISTINGS OF THE EQUIPMENT CAN NOT BE
 VERIFIED BASED ON SUBMITTIALS AND PLANS.
 E-MAILS AND INFORMATION FROM BOTH
 ENGINEERS ARE ON FILE AS RECORD.
 INSTALLATION OF THIS EQUIPMENT IS AT
 CONTRACTORS OWN RISK UNTIL ALL
 REQUIRMENTS LISTED ABOVE ARE MET AND
 VERIFIED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-05-16 Cont ID  
Sent By dpalmer Date 2006-05-16 Time 19:27 Rev Time 0.00
Received By dpalmer Date 2006-05-16 Time 19:23 Sent To  
Notes
2006-05-16 00:00:00** UNSAT ON HOLD **
  
  
 1) NOTE: PLEASE SEE SPECS SUBMITTED DO
 NOT SHOW OR INDICATE THE NEX GEAR AS
 MENTIONED IN THE RESPONSE LTR. THE SPEC
 SUBMITTED SHOWS EQUIPMENT RATED FOR A
 NEMA 1 LOCATION AND NO BRKRS OR MANUAL
 MEANS OF DISCONNECT IS SHOWN.
 PLEASE SEE 230.76,230.79, 110.27 ETC.
  
 PLEASE KNOW, CALLED THE ENGINEER OF
 RECORD, AND HE IS TO SEND
 INFORMATION/SPECS VIA E-MAIL ASAP.
  
 PLANS ARE UNDER "P" IN THE LARGE BINS ON
 HOLD PENDING SPECS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-03 Cont ID  
Sent By dpalmer Date 2006-05-03 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2006-05-03 Time 16:43 Sent To M
Notes
2006-05-03 00:00:00*** UNSAT ***
  
  
 ** PLEASE SEE MOST COMMENTS FROM FIRST
 REVIEW HAVE BEEN ADDRESSED, HOWEVER
 PLEASE SEE NOTESBELOW.
  
 1) NOTE: PLEASE SEE PREVIOUS COMMENT
 WHICH REQUESTED CLARIFICATION OFTHE
 APS CONTAINING A MANUAL MEANS OF
 DISCONNECT LOCATED ON THE OUTSIDE OF
 EQUIPMENT RATED FOR THE LOAD SERVED.
 THE RESPONSE ONLY MENTIONED THE TRANSFER
 SWITCH CONTAIN MOLDED CASE BRKRS FOR
 MANUAL DISCONNECT, HOWEVER SPECS
 SUBMITTED DO NOT CORRELATE WITH THIS.
 PLEASE ALSO CLARIFYON THE OUTSIDE OF
 EQUIPMENT WITHOUT EXPOSURE OF LIVE
 PARTS.
 110.27,230.76,230.79
  
 2) NOTE: PLEASE SEE PREVIOUS COMMENT
 WITH RESPECT TO LOAD ON GENERATOR, WHICH
 RESPONSE MENTIONS TO SEE A DETAIL ON E-3
 FOR LOAD SHEDDING.
 THIS IS OK AND IS PERMITTED, HOWEVER
 DETAIL MENTIONS TO SEE E-6 FOR LOAD
 SHEDDING , HOWEVERNO SYSTEM DETAIL OR
 HOW THESE LOADS ARE BEING SHEDDED.
 PLEASE INDICATE EQUIPMENT BEING
 INSTALLED.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE WHICH
 REQUESTED REFERENCE TO NFPA-110 2002.
 RESPONSE MENTIONS GEN DOES NOT FALL
 UNDER NFPA-110.
 PLEASE SEE FBC 2702.1 WHICH REQUIRES
 "STAND-BY" SYSTEMS TO ALSO BE INSTALLED
 PER NFPA-110.
  
 4) NOTE: PLEASE SEE PREVIOUS COMMENT
 WHICH REQUESTED TO INDICATE THE OCP AT
 GENERATOR. PLEASE SEE RESPONSE MENTIONS
 "SELF PROTECTED RELAY" ??
 PLEASE INDICATE THE OCP AT GEN.
 215.5
  
 5) NOTE: PLEASE SEE COMMENT ONE, WHICH
 REQUESTED FOR VALUE FOR COMPLETE SCOPE
 OF WORK TO BE UPDATED. THE RESPINSE
 MENTIONS $137K, HOWEVER THIS WAS NOT
 DONE WHEN PLANS WERE RESUBMITTED,
 THEVALUE HAS SINCE BEEN INCREASED AND
 FEES ARE DUEAND MUST BE PAID BEFORE
 RESUBMITTING PLANS.
 108.3 FBC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-05 Cont ID  
Sent By dpalmer Date 2006-04-05 Time 12:40 Rev Time 0.00
Received By dpalmer Date 2006-04-05 Time 07:01 Sent To FIRE
Notes
2006-04-05 00:00:00***********UNSAT *************
  
 1) NOTE:PLEASE ADJUST VALUE FOR
 COMPLETE SCOPE OF WORK BEING APPLIED
 FOR. PLEASE KNOW, THAT VALUE SHALL BE
 ALL LABOR AND MATERIALS EVEN IF
 MATERIALS ARE OWNER SUPPLIED. PLEASE SEE
 VALUE FOR LABOR AND INSTALLATION IS WAY
 LOW FOR SCOPE PF WORK. PLEASE SEE FBC
 2004, ADMINISTRATIVE CODE SECTION 108.3
 AS ADOPTED BY THE CITY OF WEST PALM
 BEACH.
  
 2) NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 FOR
 REQUIRED TITLE BLOCKS REQUIRED ON ALL
 SAID SHEETS SIGNED, AND SEALED BY THE
 ENGINEER OF RECORD.
 TITLE BLOCKS ARE TO BE ON ALL SHEETS.
 PLEASE KNOW, THIS COMMENTS IS FOR ALL
 TRADES AND FOR ALL REVIEWS WHETHER OR
 NOT COMMENT(S) ARE MADE BY OTHER
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE SPECS SUBMITTED FOR
 APS/ ATS DO NOT INDICATE THE REQUIRED
 MEANS OF DISCONNECT AS REQUIRED BY
 230.76,230.79,225.31-39.
 PLEASE SEE A MANUAL MEANS OF DISCONNECT
 COULD NOT BE LOCATED RATED FOR THE LOAD
 SERVED ON THE OUTSIDE OF EQUIPMENT
 SUBMITTED.
  
 4) NOTE: PLEASE CORRELATE SPECS/
 MANUFACTURES CUT SHEETS AND PLANS.
 PLEASE SEE ONE SHOWS 3000A AND THE
 3200A'S, ARE THESE THE SAME?AS MANY
 LOCATIONS ON PLANS MENTIONS 3000A'S.
 215.5
  
 5) NOTE: PLEASE CLARIFY WHY THE NEW MAIN
 AND OCP52 MUT IS MENTIONED AS BEING
 SET ABOVE EXISTING MAINS. PLEASE CLARIFY
 AS THIS EQUIPMENT IS NOW BECOMING THE
 NEW SERVICE MAIN(S) AND SHOULD BE
 PROVIDING THE MAX OCP FOR EACH OF THE
 EXISTING MAINS AND CONDUCTORS.
 215.5,240.4,,310.16 ETC
  
 6) NOTE: PLEASE SEE LOADS PROVIDED ON
 LOAD SUMMARY FROM THE 12 MONTH READING
 INDICATES A LOAD HIGHER THAN THE MAX
 RATING OD SAID GENERATOR. PLEASE PROVIDE
 LOAD SHEDDING DETAIL FOR LOADS TO BE
 SHEDDED AND THE NEW LOADS INTENDED ONCE
 THE MININUM DE-RATING HAS TAKEN PLACE.
 215.5,702.5,220.35
  
 7) NOTE:PLEASE SEE PLANS SHALL
 INDICATE THE CURRENT CODES IN EFFECT FOR
 INSTALLATION AS FOLLOWS.
 2002 NFPA-70, 2002 NFPA-110.
  
 8) NOTE: PLEASE SPECIFY IF GENERATOR IS
 A SEPARATELY DERIVED SYSTEM OR NOT.
 PLEASE SEE E-2 WHICH LENDS TO THE GEN
 WINDINGS BEING TAPPED FOR NEW GROUNDING
 ELECTRODE SYSTEM AND GROUNDING DETAIL ON
 E-5 DOES NOT INDICATE AS A NEW GROUNDING
 ELECTRODE SYSTEM.
 THE SPEC FOR THE APS/ ATS DO NOT SEEM TO
 INDICATE THE SWITCHING OF THE GROUNDED/
 NEUTRAL CONDUCTOR.
 250.30, 250.24 ETC.
  
 9) NOTE: PLEASE SEE THE APS/ATS IS
 BECOMING THE NEW FIRST MEANS OF
 DISCONNECT HOWEVER THE NEW GROUNDING
 ELECTRODE SYSTEMS DOE NOTE SEEM TO
 COMPLETE AS PER 250.50.
 PLEASE SEE GROUNDING DETAIL MENTIONS NEW
 SLAB STEEL WHICH IS OK, HOWEVER DOES NOT
 INDICATE A MIN OF 20' IN DIRECT CONTACT
 WITH THE EARTH.
 PLEASE KNOW, THE SLABS BEING POURED AS
 MENTIONED TO THIS OFFICE ARE BEING
 INSTALLED OVE RTHE EXISTING SITE
 SLAB/CONCRETE PARKING/ BACK OF BLDG
 AREA.
 THESE NEW SLAB/STEEL ATTACHMENTS DO NOT
 MEET THE MIN REQUIREMENTS. PER
 250.50,250.52, 250.104
 IF SLAB STEEL IS ONLY BEING BONDED ,
 THEN PLEASE INDICATE.
 PLEASE COMPLETE GROUNDING ELECTRODE
 SYSTEM(S) AND BONDING FOR ALL AS ABOVE.
  
 10) NOTE: PLEASE SEE FEEDER CONDUITS,
 NEW AND EXISTING. THERE IS NOW A CHANGE
 IN CONDUCTOR SIZES FORTHE GROUNDED
 NEUTRAL CONDUCTOR. PLEASE PROVIDE LOAD
 CALCS FOR NEW DOWN SIZING OR INSTALL AS
 SHOWN ON ORIG WITH FULL SIZE NEUTRAL.
 220.22, 215.5
  
 11) NOTE: PLEASE CORRELATE ALL CONDUITS,
 FEEDERS AND SERVICE ENTRANCE CONDUITS.
 PLEASE SEE THE NUMBER OF CONDUITS FOR 6A
 AND 6B ARE DIFFERENET ON MORE THAN ONE
 SHEET. PLEASE SEE 6A IS SHOWN AS 5
 SETS,6 SETS AND 7 SETS, AS WELL AS 6B
 BEING SHOWN AS 4 SETS AND 6 SETS.
 PLEASE VERIFY ALL OF THESE AS IT DOES
 SEEM THAT THE NUMBER OF CONDUITS TO THE
 EXISTING SERVICE WOULD BE INCREASED.
 215.5
  
 12) NOTE: PLEASE SEE SETS OF CONDUITS
 AND FEEDERS DOD NOT SEEM TO INDICATE
 THEW NEW REQUIRED "EQUIPMENT GROUNDING
 CONDUCTOR" TO TEH EXISITING MAINS. THESE
 ARE NO LONGER THE FIRST MENAS OF
 DISCONNECT AND THE GROUNDING
 DETAIL/RISER ON E-5 MENTIONS THE
 DISCONNECT OF THE BONDING JUMPER,
 HOWEVER THE CONDUITS/FEEDERS DONOT
 SHOW THE EQUIPMENT GROUNDING CONDUCTORS
 PER 250.110,250.122,250.24B
 215.5
  
 13) NOTE: PLEASE INDICATE OCP AT
 GENERATOR. PLEASE ALSO SEE 445.13 FOR
 MIN SIZING WHICH MAY BE AFFECTED.
 CONDUCTORS AT 115%?
  
 14) NOTE: PLEASE SEE LEGEND ON E-3 WHICH
 MENTIONS THE "PINK HIGH-LIGHTED LINES"
 AS WIRING BY OTHERS", HOWEVER PLEASE SEE
 4.1 WHICH SHOWS THIS SAME HIGH-LIGHTED
 LINE AS A FENCE BY OTHERS?
 215.5
  
 15) NOTE: PLEASE SEE NOTE #4 ON E-1,
 WHICH MENTIONS "STANDY" MODE, THIS SEEMS
 TO BE A MISPRINT FOR THE INTENDED
 "STAND-BY" MODE".
 215.5
  
 16) NOTE:PLEASE SUBMIT A MIN OF TWO
 COPIES FOR ALL PLANS SPECS. IF THREE ARE
 DESIRED TO BE STAMPED, PLEASE SUBMIT
 THREE COMPLETE SETS.
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO THE COMPLETED SETS FOR
 REVIEW AND STAMPING BEFORE RESUBMITTING.
 PLANS.
  
 17) NOTE: PLEASE KNOW, IT IS KNOWN TO
 THIS OFFICE THAT THERE IS AN EXISTING
 GENERATOR AT THIS STORE LOCATION,
 HOWEVER NO INFORMATION FOR THIS IS
 INDICATED. PLEASE SHOW LOCATION AND HOW
 THIS SYSTEM IS OR IS NOT TIED INTO THE
 NEW SERVICE.
 215.5
  
 18) NOTE: PLEASE PROVIDE THE GPH USEAGE
 OF GENERATOR FOR LOADS INTENDED. PLEASE
 KNOW, A 1000 GAL TANK IS BEING SHOWN,
 WHICH LENDS TO LESS THAN 24HRS OF
 OPERTATION? IS THIS CORRECT?
 THIS IS ONLY A NOTE,AS AN OPTIONAL
 STAND-BY LEVEL 2 SYSTEMS DOES NOT
 REQUIRED ANY MIN HRS OF OPERATION.
  
  
 *** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-04-05 Cont ID  
Sent By mwennerg Date 2006-04-05 Time 15:51 Rev Time 0.00
Received By mwennerg Date 2006-04-05 Time 15:51 Sent To  
Notes
2006-04-05 00:00:00******PROVISO******
  
 1) WORK TO COMPLY WITH NFPA 110.
  
 2) PLEASE ILLUSTRATE DISTANCES TO
 OPENINGS AND ANY MEANS OF EGRESS IN
 REGARDS TO FUEL EXHAUSTING.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status P Date 2006-05-04 Cont ID  
Sent By pkrauss Date 2006-05-04 Time 07:37 Rev Time 0.00
Received By pkrauss Date 2006-05-04 Time 07:37 Sent To  
Notes
2006-05-04 00:00:00SUB-BASE FUEL TANK/SELF CONTAINED

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2006-04-05 Cont ID  
Sent By pkrauss Date 2006-04-05 Time 21:19 Rev Time 0.00
Received By pkrauss Date 2006-04-05 Time 21:19 Sent To  
Notes
2006-04-05 00:00:00DENIED:
 PLEASE PROVIDE INFORMATION ON THE FUEL
 PIPING AND FILL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-04-06 Cont ID  
Sent By dpalmer Date 2006-04-06 Time 06:57 Rev Time 0.00
Received By dpalmer Date 2006-04-06 Time 06:59 Sent To  
Notes
2006-04-06 00:00:00NO GAS REVIEW NEED. NONE LP/NG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 10:34 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 10:34 Sent To E
Notes
2006-07-31 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 16:38 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 16:38 Sent To E
Notes
2006-06-14 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 16:26 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 16:26 Sent To  
Notes
2006-04-21 00:00:005/3/06-TO DPALMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-10 Cont ID  
Sent By jwitmer Date 2006-04-10 Time 16:54 Rev Time 0.00
Received By jwitmer Date 2006-04-04 Time 08:19 Sent To  
Notes
2006-04-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06040063
 ADD: 828 SOUTHERN BLVD
 CONT: POWER SECURE INC
 TEL: (919)556-3056
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1606.4 EVERY STRUCTURE SHALL BE DESIGNED
 TO RESIST THE OVERTURNING EFFECTS CAUSED
 BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND AND
 SECTION 1610 FOR LATERAL SOIL LOADS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
2006-04-04 00:00:00PLAN ROUTED TO MICHELLE MC LEAN FOR
 REVIEW. PLANS TO COME BACK TO DVP WHEN
 COMPLETED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-04 Cont ID  
Sent By pkrauss Date 2006-05-04 Time 07:36 Rev Time 0.00
Received By pkrauss Date 2006-05-04 Time 07:36 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-05 Cont ID  
Sent By pkrauss Date 2006-04-05 Time 21:05 Rev Time 0.00
Received By pkrauss Date 2006-04-05 Time 21:05 Sent To  
Notes
2006-04-05 00:00:00DENIED:
  
 1.PLEASE INDICATE DISTANCES TO
 OPENINGS AND ANY FRESH AIR INTAKES PER
 2004 FMC 401.5.1.
  
 2.PLEASE PROVIDE INFORMATION AND
 DETAIL FOR ANCHORING PER 2004 FMC
 301.13.
  
 3.PLEASE PROVIDE INFORMATION FOR THE
 FUEL OIL PIPING AND FILL PIPING.SHOW
 COMPLIANCE WITH NFPA 37, 54 AND 110.
  
 4.PROVIDE CAPACITY OF THE FUEL STORAGE
 TANK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-04-06 Cont ID  
Sent By dpalmer Date 2006-04-06 Time 06:58 Rev Time 0.00
Received By dpalmer Date 2006-04-06 Time 06:59 Sent To  
Notes
2006-04-06 00:00:00NO PLUMB REVIEW NEEDED. FUEL TYPE
 DIESEL.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-04 Cont ID  
Sent By mmclean Date 2006-04-04 Time 14:41 Rev Time 0.00
Received By mmclean Date 2006-04-04 Time 14:41 Sent To E
Notes
***NONE***