Plan Review Details - Permit 06031554
Plan Review Stops For Permit 06031554
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-08 Cont ID  
Sent By jgomez Date 2006-05-08 Time 11:23 Rev Time 0.50
Received By jgomez Date 2006-05-08 Time 07:44 Sent To PC
Notes
2006-05-08 00:00:00PERMIT UNDER "T". JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-31 Cont ID  
Sent By jgomez Date 2006-03-31 Time 12:31 Rev Time 0.50
Received By jgomez Date 2006-03-31 Time 12:31 Sent To  
Notes
2006-03-31 00:00:00BUILDING REVIEW CHECKLIST:
 1- FLAT ROOF SYSTEM: ACCORDING TO THE
 POLYGLASS DADE COUNTY NOA LIMITATION #7
 SUBMITTEDNEED TO PROVIDE CALCULATIONS
 FOR PERIMETER AND CORNER AREAS ENHANCED
 FASTENERS. CALCULATIONS MUST BE DONE AND
 SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER,
 REGISTERED ARCHITECT OR REGISTERED ROOF
 CONSULTANT. PROVIDE SUCH CALCULATIONS
 DONE BY EITHER ONE OF THE LISTED PEOPLE
 ABOVE.
  
 2- FLORIDA PRODUCT APPROVAL FOR RIDGE
 VENT IS MISSING THE TECHNICAL
 INFORMATIONTHAT WAS SUBMITTED FOR
 FLORIDA APPROVAL. ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE WAS
 SUBMITTED. GO TO THE DCA WEBSITE
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 COMPLETE INFORMATION. RE-SUBMIT COMPLETE
 INFORMATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712