Plan Review Details - Permit 06031339
Plan Review Stops For Permit 06031339
Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2007-12-27 Cont ID  
Sent By jgomez Date 2007-12-27 Time 14:24 Rev Time 0.00
Received By jgomez Date 2007-12-27 Time 14:24 Sent To PC
Notes
2007-12-27 14:25:31BUILDING REVISION: NEW CUSTOM MADE WINDOWS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2007-11-13 Cont ID  
Sent By jgomez Date 2007-11-13 Time 11:38 Rev Time 0.00
Received By jgomez Date 2007-11-13 Time 07:43 Sent To PC
Notes
2007-11-13 12:03:28WINDOW SITE SPECIFIC PRODUCT APPROVAL BUILDING REVIEW
 CHECKLIST.
  
 1- ROBERT BROWN'S COMMENTS FOR PRODUCT APPROVAL PACKAGE
 SUBMITTED: SEE ATTACHED HANDWRITTEN NOTES.
 ENGINEER SIGNATUREMUST BE ORIGINAL IN ALL DRAWINGS AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE AND SEC.
 61G15-23.002 OF FLORIDAADMINISTRATIVE CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2007-07-09 Cont ID  
Sent By jgomez Date 2007-07-09 Time 12:45 Rev Time 0.00
Received By jgomez Date 2007-07-09 Time 12:40 Sent To PC
Notes
2007-07-09 12:55:16LOCAL PRODUCT APPROVAL CHECKLIST:
 1- COMMENTS FROM ROBERT BROWN REGARDING LOCAL PRODUCT
 APPROVAL:
 SHOP DRAWINGS SUBMITTED DON'T STATE THE FASTENER JOINT
 TYPE FOR THE JOINTS BETWEEN THE HORIZONTAL AND VERTICAL
 FRAME MEMBERS (5.5" X 1.75") OF THE WINDOWS.
 ENGINEERING ANALYSIS DOESN'T GIVE THAT INFORMATION
 EITHER.NEED TO PROVIDE THIS INFORMATION.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 *** IF YOU HAVE ANY QUESTIONS REGARDING THIS PRODUCT
 APPPROVAL,PLEASE CALLROBERT BROWN (LICENSE & PERMIT
 SERVICES MANAGER)AT (561)805-6652.
  
 2- SEE ATTACHED CHECKLIST DATED 5-31-07 FOR COMMENTS TO
 BE ADDRESED REGARDING THIS BUILDING REVISION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2007-06-01 Cont ID  
Sent By lmartine Date 2007-06-01 Time 10:30 Rev Time 0.00
Received By lmartine Date 2007-06-01 Time 10:30 Sent To  
Notes
2007-06-01 10:31:37REVISION FOR OVERLAY OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2007-05-31 Cont ID  
Sent By jgomez Date 2007-05-31 Time 15:53 Rev Time 0.00
Received By jgomez Date 2007-05-31 Time 07:46 Sent To B
Notes
2007-05-31 16:03:03*** PRODUCT APPROVALS SENT TO ROBERT BROWN'S DESK FOR
 LOCAL PRODUCT APPROVAL.
  
 BUILDING REVISION CHECKLIST:
 1- THIS IS A REVISION TO SCOPE OF WORK SPECIFIED ON
 ORIGINAL PERMIT APPLICATION NOT A SUBMITTAL.THEREFORE
 OWES $70.00.
  
 2- PRODUCT APPROVALS SENT TO ROBERT BROWN FOR
 APPROVAL.
  
 3- STORM SHUTTERS:REVISE INSTALLATION SCHEDULE TO
 INCLUDE THESE NEW WINDOWS.
  
 4- NEED TO UPDATE PERMIT VALUATION TO INCLUDE THIS
 ADDITIONAL WORK. FEES WILL BE CHARGED ACCORDINGLY. SEC.
 108.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-11-13 Cont ID  
Sent By jgomez Date 2006-11-13 Time 08:03 Rev Time 0.50
Received By jgomez Date 2006-11-13 Time 07:44 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status N Date 2006-11-13 Cont ID  
Sent By jgomez Date 2006-10-24 Time 09:28 Rev Time 0.00
Received By jgomez Date 2006-10-24 Time 09:28 Sent To  
Notes
2006-10-24 09:38:5710-24-06
 1- CALLED CONTRACTOR TO PICK UP SITE SPECIFIC PRODUCT
 APPROVAL COMMENTS FROM ROBERT BROWN (SEE ATTACHED HAND
 WRITTEN NOTES).
 2- RE-SUBMITTAL FEES ARE NOT DUE FOR PRODUCT APPROVAL
 RE-SUBMITTALS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2006-10-24 Cont ID  
Sent By jgomez Date 2006-10-19 Time 13:45 Rev Time 0.00
Received By jgomez Date 2006-10-19 Time 13:45 Sent To  
Notes
2006-10-19 13:46:20SENT TO ROBERT BROWN FOR WINDOWS AND DOOR LOCAL PRODUCT
 APPROVAL REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2006-10-18 Cont ID  
Sent By jgomez Date 2006-10-18 Time 08:40 Rev Time 0.50
Received By jgomez Date 2006-10-18 Time 08:40 Sent To  
Notes
2006-10-18 08:43:34MET WITH CONTRACTOR AND BUILDING REP. THEY CLARIFIED
 SCOPE OF WORK TO BE REPLACING DOORS, WINDOWS AND SIDING
 ONLY. THEY WERE TOLD THAT IF STRUCTURAL WALLS WILL NEED
 TO BE REPLACED, THEN THE PERMIT NEED IT TO BE REVISED
 AND STRUCTURAL INFORMATION WILL NEED TO BE PROVIDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-10-16 Cont ID  
Sent By jgomez Date 2006-10-16 Time 16:38 Rev Time 3.00
Received By jgomez Date 2006-10-16 Time 16:27 Sent To  
Notes
2006-10-16 17:10:20BUILDING REVIEW THIRD CHECKLIST:
  
 ***NOTE:
 CAPITAL LETTERS REFLECT ORIGINAL COMMENTS. LOWER CASE
 LETTERS REFLECT COMMENTS TO SUBMITTAL PACKAGE.
  
 1- PROVIDE COMPLETE SET OF STRUCTURAL DRAWINGS SHOWING
 STRUCTURAL WORK TO BE PERFORMED WITH COMPLETE
 SPECIFICATIONS AND DETAILSTHAT COMPLY WITH SECTION
 1609 OF FBC 2004 AND EXISTING BUILDINGS 2004 CODE.
  
 *** NO DONE. STRUCTURAL DRAWINGS WERE NOT SUBMITTED.
 THERE IS NOT INFORMATION GIVEN FOR REPLACING FRAMING
 AND SIDING.
 ***THERE IS ONE DRAWING SUBMITTED, BUT IT DOESN'T HAVE
 ANY STRUCTURAL SPECIFICATION. IT ONLY SHOWS LOCATION OF
 SIDING AND WINDOWS AND DOORS TO BE REPLACED. THERE ARE
 NO DRAWINGS AND SPECS ADDRESING THE ISSUE OF REPLACING
 ROTTEN FRAMING. THE ONLY ADDITIONAL DRAWING SUBMITTED
 WAS FOR A TYPICAL BUCK INSTALLATION.
 ***NOTE: SEE HARDIBOARD PRODUCT APPROVAL TO VERIFY
 COMPLIANCE WITH THE INSTALLATION. CHECK STUDS SPACING,
 ETC.
  
 2- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL FOR
 STRUCTURAL FRAMING CONNECTORS THAT WILL BE SPECIFIED ON
 THE STRUCTURAL DRAWINGS.
 ***NO DONE. THERE ARE NO STRUCTURAL DRAWINGS AND
 SPECS.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL FOR SIDING
 TO BE INSTALLED AS REQUIRED BY RULE 9B-72 OF DCA. ***
 PRODUCT APPROVAL SUBMITTTED IS FOR HARDIBOARD. NEED
 ALSO THE PRODUCT APPROVAL FOR WOOD SIDING IN FRONT
 ELEVATION AS CALLED FOR IN THE SUBMITTED DRAWING.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITTING
 ALL PRODUCT APPROVALS PRIOR TO SUBMITTAL TO THIS OFFICE
 AS REQUIRED BY SEC. 106.3.3 OF CITY AMENDMENTS TO FBC
 2004.
 ***NO DONE.
  
 5- PROVIDE FLORIDA OR APPLY FOR LOCAL PRODUCT APPROVALS
 FOR ALL TYPE AND SIZE OF WINDOWS AND WINDOWS TO BE
 REPLACED AS REQUIRED BY RULE 9B-72 OF DEPARTMENT OF
 COMMUNITY AFFAIRS (DCA).
 *** PRODUCT APPROVAL APPLICATIONS NEED TO HAVE THE NAME
 AND SIGNATURE OF APPLICANT.
 ***APPLICATIONS FOR SITE SPECIFIC PRODUCT APPROVAL WILL
 BEFORWARDED TO ROBERT BROWN FOR REVIEW AND APPROVAL.
  
 6- PROVIDE KEY PLAN AND A COMPLETE INSTALLATION
 SCHEDULE FOR STORM SHUTTERS. SEE ATTACHED SAMPLE OF
 STORM SHUTTERS INSTALLATION SCHEDULE.
 ***NEED TO PROVIDE ALL INFORMATION ON INSTALLATION
 SCHEDULE. MISSING OPENINGS SIZES, ETC.
  
 7- PROVIDE STRUCTURAL BUCK DETAILS FOR DOORS AND
 WINDOWS AS REQUIRED BY SEC. 1714.5.4.2 FBC 2004. ***
 CLARIFY BUILDING TYPE OF CONSTRUCTION. TYPICAL BUCK
 DETAIL DONE BY FREDRICK D. SHAFFER, PE CALLS FOR
 ATTACHMENT OF BUCKS TO MASONRY CONSTRUCTION. IS THIS
 BUILDING A WOOD FRAMED BUILDING OR CONCRETE BLOCK
 CONSTRUCTION?.
 *** ENGINEER NEEDS TO PROVIDE ALL INFORMATION REQUIRED
 BY SEC. 1603.1.4 FBC 2004.
 *** ENGINEER TO PROVIDE HIS FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002. SEE ATTACHED
 COPY.
 *** ENGINEER TO PROVIDE DRAWINGS WITH ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
  
 8- VALUATION OF PROJECT WILL BE EVALUATED AFTER
 COMPLETE SET OF DRAWINGS ARE SUBMITTED TO DEFINE
 SPECIFIC SCOPE OF WORK.
 ***NO DRAWINGS AND SPECS SHOWING PROPOSED SCOPE OF
 WORK.
  
 9- NEED TO PROVIDE 2 COPIES OF EVERYTHING INCLUDING
 DRAWINGS AND SHUTTERS INFORMATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-04 Cont ID  
Sent By jgomez Date 2006-08-04 Time 13:54 Rev Time 2.00
Received By jgomez Date 2006-08-04 Time 13:54 Sent To  
Notes
2006-08-04 00:00:00BUILDING REVIEW 2ND CHECKLIST:
  
 ***NOTE:
 CAPITAL LETTERS REFLECT ORIGINAL
 COMMENTS. LOWER CASE LETTERS REFLECT
 COMMENTS TO SUBMITTAL PACKAGE.
  
 1- PROVIDE COMPLETE SET OF STRUCTURAL
 DRAWINGS SHOWING STRUCTURAL WORK TO BE
 PERFORMED WITH COMPLETE SPECIFICATIONS
 AND DETAILSTHAT COMPLY WITH SECTION
 1609 OF FBC 2004 AND EXISTING BUILDINGS
 2004 CODE.
  
 *** NO DONE. STRUCTURAL DRAWINGS WERE
 NOT SUBMITTED. THERE IS NOT INFORMATION
 GIVEN FOR REPLACING FRAMING AND SIDING.
  
 *** PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR STRUCTURAL FRAMING
 CONNECTORS THAT WILL BE SPECIFIED ON THE STRUCTURAL
 DRAWINGS.
  
 *** PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR SIDING TO BE INSTALLED AS
 REQUIRED BY RULE 9B-72 OF DCA.
  
 *** ENGINEER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS PRIOR TO SUBMITTAL TO THIS
 OFFICE AS REQUIRED BY SEC. 106.3.3 OF
 CITY AMENDMENTS TO FBC 2004.
  
 *** WHAT IS THE INTENTION OF THE LETTER
 FROM ENGINEERING EXPRESS?. IF IT IS TO
 APPLY FOR LOCAL PRODUCT APPROVAL FOR
 DOUBLE HUNG WINDOW, THEN, IT'S
 INCOMPLETE. NEED TO PROVIDE THE COMPLETE
 PACKAGE INCLUDING THE LOCAL PRODUCT
 APPROVAL APPLICATION AND QUALITY
 ASSURANCE (ENGINEER'S LETTER CERTIFYING
 THAT PRODUCT WAS CONSTRUED AND INSTALLED
 AS PER DESIGN SPECFIFICATIONS
 SUBMITTED). THEN, IT WILL BE
 FORWARDED TO ROBERT BROWN FOR LOCAL
 PRODUCT APPROVAL REVIEW.CALL ROBERT
 BROWN AT (561)805-6652 FOR QUESTIONS
 REGARDING LOCAL PRODUCT APPROVAL REVIEW
 TIME AND QUALITY ASSURANCE REQUIRED FOR
 ONE OF A KIND (SITE SPECIFIC) PRODUCT
 APPROVALS.
  
 2- PROVIDE FLORIDA OR APPLY FOR LOCAL
 PRODUCT APPROVALS FOR ALL TYPE AND SIZE
 OF WINDOWS AND WINDOWS TO BE REPLACED AS
 REQUIRED BY RULE 9B-72 OF DEPARTMENT OF
 COMMUNITY AFFAIRS (DCA). GO TO THE
 WEBSITE WWW.FLORIDABUILDING.ORG TO FIND
 ALL INFORMATION REGARDING PRODUCT
 APPROVALS IN FLORIDA.
 INFORMATION SUBMITTED IS NOT ACCEPTABLE.
 NEED COMPLETE FLORIDA OR LOCAL PRODUCT
 APPROVAL PACKAGE.
  
 *** WINDOW AND DOOR APPLICATIONS
 SUBMITTED FOR LOCAL PRODUCT APPROVAL
 WILL BE FORWARDED TO ROBERT BROWN, PLAN
 REVIEWER'S MANAGER, FOR LOCAL PRODUCT
 APPROVAL REVIEW. CALL ROBERT BROWN FOR
 QUESTIONS REGARDING PRODUCT APPROVAL
 REVIEW TIMING AND QUALITY ASSURANCE FOR
 ONE OF A KIND (SITE SPECIFIC) PRODUCT
 APPROVALS.
  
 *** DOOR STYLE SUBMITTED FOR LOCAL
 PRODUCT APPROVAL DOESN'T MATCH DRAWINGS
 SHOWN IN BLUEPRINT.
  
 *** PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR DOUBLE HUNG WINDOW.
  
 *** PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR STORM SHUTTERS> GO TO
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 FLORIDA PRODUCT APPROVALS.
  
 *** PROVIDE KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE FOR STORM
 SHUTTERS. SEE ATTACHED SAMPLE OF STORM
 SHUTTERS INSTALLATION SCHEDULE.
  
 3- PROVIDE STRUCTURAL BUCK DETAILS FOR
 DOORS AND WINDOWS AS REQUIRED BY SEC.
 1714.5.4.2 FBC 2004.
  
 ***NO DONE.
  
 4- PROVIDE 2 SETS OF SIGNED AND SEALED
 PLANS AND 2 SETS OF FLORIDA OR LOCAL
 PRODUCT APPROVALS FOR EACH TYPE OF DOOR
 AND WINDOW.
  
 *** NEED 2 LOCAL PRODUCT APPROVAL
 APPLICATIONS PER DOOR OR WINDOW. ONLY
 ONE SUBMITTED.
  
 5- NOTICE OF COMMENCEMENT DOESN'T HAVE
 ANY DESCRIPTION FOR THE GENERAL
 DESCRIPTION OF IMPROVEMENTS. COMPLETE
 INFORMATION AND RE-RECORD THE NOTICE OF COMMENCEMENT.
  
 *** NO DONE.
  
 6- VALUATION OF PROJECT WILL BE
 EVALUATED AFTER COMPLETE SET OF DRAWINGS
 ARE SUBMITTED TO DEFINE SPECIFIC SCOPE
 OF WORK.
  
 *** NO DONE. UNABLE TO DETERMINE SCOPE
 OF WORK. NO PLANS SUBMITTED SHOWING
 EXTEND OF WORK.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-28 Cont ID  
Sent By jgomez Date 2006-04-28 Time 16:50 Rev Time 0.50
Received By jgomez Date 2006-04-28 Time 16:50 Sent To  
Notes
2006-04-28 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE COMPLETE SET OF STRUCTURAL
 DRAWINGS SHOWING STRUCTURAL WORK TO BE
 PERFORMED WITH COMPLETE SPECIFICATIONS
 AND DETAILSTHAT COMPLY WITH SECTION
 1609 OF FBC 2004 AND EXISTING BUILDINGS
 2004 CODE.
  
 2- PROVIDE FLORIDA OR APPLY FOR LOCAL
 PRODUCT APPROVALS FOR ALL TYPE AND SIZE
 OF WINDOWS AND WINDOWS TO BE REPLACED AS
 REQUIRED BY RULE 9B-72 OF DEPARTMENT OF
 COMMUNITY AFFAIRS (DCA). GO TO THE
 WEBSITE WWW.FLORIDABUILDING.ORG TO FIND
 ALL INFORMATION REGARDING PRODUCT
 APPROVALS IN FLORIDA.
 INFORMATION SUBMITTED IS NOT ACCEPTABLE.
 NEED COMPLETE FLORIDA OR LOCAL PRODUCT
 APPROVAL PACKAGE.
  
 3- PROVIDE STRUCTURAL BUCK DETAILS FOR
 DOORS AND WINDOWS AS REQUIRED BY SEC.
 1714.5.4.2 FBC 2004.
  
 4- PROVIDE 2 SETS OF SIGNED AND SEALED
 PLANS AND 2 SETS OF FLORIDA OR LOCAL
 PRODUCT APPROVALS FOR EACH TYPE OF DOOR
 AND WINDOW.
  
 5- NOTICE OF COMMENCEMENT DOESN'T HAVE
 ANY DESCRIPTION FOR THE GENERAL
 DESCRIPTION OF IMPROVEMENTS. COMPLETE
 INFORMATION AND RE-RECORD THE NOTICE OF
 COMMENCEMENT.
  
 6- VALUATION OF PROJECT WILL BE
 EVALUATED AFTER COMPLETE SET OF DRAWINGS
 ARE SUBMITTED TO DEFINE SPECIFIC SCOPE
 OF WORK.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-11-21 Cont ID  
Sent By adarroug Date 2007-11-21 Time 08:51 Rev Time 0.00
Received By adarroug Date 2007-11-21 Time 08:51 Sent To B
Notes
2007-11-21 08:52:07TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-12 Cont ID  
Sent By adarroug Date 2007-10-12 Time 08:45 Rev Time 0.00
Received By adarroug Date 2007-10-12 Time 08:44 Sent To B
Notes
2007-10-12 08:45:19TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-05-10 Cont ID  
Sent By adarroug Date 2007-05-10 Time 13:55 Rev Time 0.00
Received By adarroug Date 2007-05-10 Time 13:55 Sent To B
Notes
2007-05-10 13:55:25TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 13:14 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 13:14 Sent To B
Notes
2007-05-02 13:15:02TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jgomez Date 2006-11-03 Time 15:11 Sent To  
Notes
2006-11-03 15:13:05CONTRACTOR SUBMITTED PACKAGE FOR LOCAL PRODUCT
 APPROVALS ALONG WITH PERMIT APPLICATION. PACKAGE
 FORWARDED TO ROBERT BROWN'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 17:26 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 17:26 Sent To B
Notes
2006-10-14 17:26:29TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 17:38 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 17:38 Sent To B
Notes
2006-08-02 00:00:00SENT TO "JGOMEZ"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-28 Cont ID  
Sent By jgomez Date 2006-04-28 Time 17:11 Rev Time 0.00
Received By jgomez Date 2006-03-30 Time 11:28 Sent To  
Notes
2006-03-30 00:00:00TO "MISC" BOX#1