Plan Review Details - Permit 06031223
Plan Review Stops For Permit 06031223
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-06-13 Cont ID  
Sent By rmcdouga Date 2006-06-13 Time 12:43 Rev Time 0.00
Received By rmcdouga Date 2006-06-13 Time 12:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-05 Cont ID  
Sent By rmcdouga Date 2006-06-05 Time 09:04 Rev Time 0.00
Received By rmcdouga Date 2006-06-05 Time 07:10 Sent To  
Notes
2006-06-05 00:00:00DENIED
  
 1) SUBMIT THE ORIGINAL PERMIT
 APPLICATION AND NOTICE OF COMMENCEMENT.
  
 2) THE PRODUCT APPROVAL SUBMITTED FOR
 THE ROOFING MATERIAL DOES NOT MEET THE
 REQUIRED UPLIFT PRESSURE. THE PRODUCT
 APPROVAL FOR THE JOHNS MANVILLE SINGLE
 PLY ROOF SYSTEM LISTS MAXIMUM DESIGN
 PRESSURE AS -45 PSF WITH NO ENHANCED
 FASTENING ALLOWED. THE REQUIRED ROOF
 PRESSURES FROM TABLE 1609.6B ARE -59.2
 AT PERIMETER AREAS AND -89.0 AT THE
 CORNERS. SUBMIT PRODUCT APPROVAL FOR
 ROOFING MATERIAL THAT HAS ADEQUATE
 DESIGN PRESSURES. SEE COMMENT #4 ON LAST
 REVIEW.
  
 3) FBC 11-4.5.1 REQUIRES CHANGES IN
 LEVEL ON AN ACCESSIBLE ROUTE GREATER
 THAN 1/2 INCH SHALL BE ACCOMPLISHED BY
 MEANS OF A RAMP THAT COMPLIES WITH
 SECTION 11-4.7 OR 11-4.8. SPECIFY THE
 LOCATION OF RAMPS ON THE ACCESSIBLE
 ROUTES TO THE OFFICES. SPECIFY THE SLOPE
 OF THE RAMPS, ETC. COMMENT #7 ON LAST
 REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-15 Cont ID  
Sent By rmcdouga Date 2006-05-15 Time 11:42 Rev Time 0.00
Received By rmcdouga Date 2006-05-15 Time 11:42 Sent To  
Notes
2006-05-15 00:00:00DENIED BY BUILDING
  
 1) SPECIFY THE CONSTRUCTION TYPE AND
 TYPE OF OCCUPANCY BASED ON THE 2004
 FLORIDA BUILDING CODE. SEE #3 FROM
 PERVIOUS COMMENTS.
  
 2)THE WINDLOAD DATA ON THE PLAN
 REFRENCES FBC 1606.1.7. THIS SECTION HAS
 CHANGED IN THE 2004 FBC TO 1603.1.4.
 PLEASE CORRECT.
  
 3) SPECIFY THE FASTENING REQUIREMENTS
 FOR THE 3/4" PLYWOOD ROOF SHEATHING AS
 REQUIRED BY 2004 FBC TABLE 2304.9.1.
 #31, WHICH REQUIRES FASTENER SPACING OF
 4" OC AT COMPONENT AND CLADDING ROOF
 ZONE 3. SEE COMMENT #8 FROM PREVIOUS
 REVIEW.
  
 4) THE PRODUCT APPROVAL SUBMITTED FOR
 THE ROOFING MATERIAL DOES NOT MEET THE
 REQUIRED UPLIFT PRESSURE. PRODUCT
 APPROVAL LISTS MAXIMUM DESIGN PRESSURE
 AS -45 PSF WITH NO ENHANCED FASTENING
 ALLOWED. THE REQUIRED PRESSURES FROM
 TABLE 1609.6B ARE -59.2 AT PERMITER
 AREAS AND -89.0 AT THE CORNERS. SUBMIT
 APPROPRIATE PRODUCT APPROVAL.
  
 5) THE FIGURES GIVEN IN THE COMPONENT
 AND CLADDING TABLE ON THE PLANS ARE FOR
 A STRUCTURE WITH A ROOF SLOPE GREATER
 THAN 10 DEGREES. THESE STRUCTURES HAVE
 SLOPES LESS THAN 10 DEGREES. PLEASE
 CORRECT. SEE FBC TABLE 1609.6B.
  
 6) THE PLANS REFERENCE ASCE 7-98. THE
 AMENDMENTS TO THE 2004 FBC CHANGED THE
 EDITION OF ASCE 7 TO ASCE 7-02.
  
 7) INDICATE HOW THE ACCESSIBLE ROUTE
 WILL BE MAINTAINED INTO OFFICE 1 FROM
 THE EXTERIOR AND OFFICE 2 FROM BOTH THE
 EXTERIOR AND INTERIOR AFTER THE SLABS
 ARE RAISED (FBC 11-4.1.6). SEE COMMENT
 #12 FROM PREVIOUS REVIEW. SPECIFY THE
 ELEVATION CHANGES AND PROVIDE DETAILS OF
 RAMPS, ETC.
  
 8) SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR EXTERIOR DOORS THAT HAVE
 BEEN APPROVED BY THE DESIGNER OF RECORD
 PER FBC 106.3.3 AS AMENDED BY CITY OF
 WPB.
  
 9) TWO COPIES OF ALL PRODUCT APPROVALS
 ARE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-07 Cont ID  
Sent By rmcdouga Date 2006-04-07 Time 13:31 Rev Time 0.00
Received By rmcdouga Date 2006-04-07 Time 13:31 Sent To  
Notes
2006-04-07 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PLEASE CLARIFY THE SCOPE OF WORK.
 VERIFY THAT OFFICES 1, 2 AND 3 ARE
 EXISTING AND HAVE EXISTING FOUNDATIONS.
  
 3) SPECIFY THE CODE EDITION,
 CONSTRUCTION TYPE AND TYPE OF OCCUPANCY.
 INDICATE IF THE AREA IS FIRE
 SPRINKLERED.
  
 4) SPECIFY THE WIND DESIGN DATA, SUCH AS
 WIND SPEED, IMPORTANCE FACTOR, ETC. SEE
 2004 FBC 1603.1.4.
  
 5) SHOW COMPLIANCE WITH 2004
 FBC(EXISTING BUILDINGS) FOR LEVEL 2
 ALTERATIONS. SEE SECTIONS 601 THRU 611.
  
 6) SPECIFY INTERIOR FINISH FLAME SPREAD
 AND FIRE RESISTANCE.
  
 7) FBC 1805.2 REQUIRES FOOTINGS TO HAVE
 A MINIMUM DEPTH OF 12". CLARIFY THAT
 ITEM #4 FOR NEW RAISED CONCRETE FLOOR IS
 POURED OVER AN EXISTING FOUNDATION.
  
 8) SPECIFY THE FASTENING FOR THE PLYWOOD
 TO THE NEW 2X8 JOISTS. SEE FBC TABLE
 2304.9.1. (6"OC EDGES & INTERMEDIATE AND
 4"OC IN ZONE 3).
  
 9) PROVIDE A WINDOW AND DOOR BUCK
 DETAIL/FRAMING DETAIL FOR WINDOW AND
 DOOR OPENINGS.
  
 10) SPECIFY THE R-VALUE FOR WALL AND
 CEILING INSULATION. COMPLY WITH FBC
 CHAPTER 13.
  
 11) SPECIFY THE ROOF COVERING AND SUBMIT
 FL PRODUCT APPROVALS FOR ROOFING.
  
 12) INDICATE HOW THE ACCESSIBLE ROUTE
 WILL BE MAINTAINED FROM THE EXTERIOR
 INTO OFFICE 1 AND FROM BOTH EXTERIOR AND
 INTERIOR INTO OFFICE TWO WHEN THE CONC.
 FLOORS ARE RAISED. SEE FBC 11-4.1.6.
  
 13) SUBMIT FL PRODUCT APPROVALS FOR THE
 SIMPSON CONNECTORS.
  
 14) CITY OF WPB AMENDMENTS TO FBC
 106.3.3 REQUIRES THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 TO BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 15) SPECIFY THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES AT THE EXTERIOR
 OPENINGS FOR THE NEW WINDOWS AND DOORS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2006-04-10 Cont ID  
Sent By btrobaug Date 2006-04-10 Time 16:26 Rev Time 0.25
Received By btrobaug Date 2006-04-10 Time 16:18 Sent To  
Notes
2006-04-10 00:00:00 
 NO ELECTRICAL PLANS SUBMITTED, NO
 ELECTRICAL CONTRACTOR SIGNED ON, NOTES
 INDICATE ALL ELECTRICAL EXISTING AND NO
 WORK TO BE DONE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-06-14 Cont ID  
Sent By mwennerg Date 2006-06-14 Time 10:04 Rev Time 0.00
Received By mwennerg Date 2006-06-14 Time 10:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-03-31 Cont ID  
Sent By mwennerg Date 2006-03-31 Time 14:08 Rev Time 0.00
Received By mwennerg Date 2006-03-31 Time 14:08 Sent To  
Notes
2006-03-31 00:00:00******APPROVED******
  
 SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEM IF APPLICABLE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561Z0 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 15:19 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 15:19 Sent To B
Notes
2006-06-12 00:00:00TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-30 Cont ID  
Sent By adarroug Date 2006-05-30 Time 08:07 Rev Time 0.00
Received By adarroug Date 2006-05-30 Time 08:07 Sent To B
Notes
2006-05-30 00:00:00TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-06 Cont ID  
Sent By adarroug Date 2006-05-06 Time 16:16 Rev Time 0.00
Received By adarroug Date 2006-05-06 Time 16:16 Sent To B
Notes
2006-05-06 00:00:00TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-10 Cont ID  
Sent By btrobaug Date 2006-04-10 Time 16:29 Rev Time 0.00
Received By btrobaug Date 2006-03-27 Time 16:41 Sent To PC
Notes
2006-03-27 00:00:00TO "BOB"#5