Plan Review Details - Permit 06031215
Plan Review Stops For Permit 06031215
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-04-11 Cont ID  
Sent By rmcdouga Date 2006-04-11 Time 08:16 Rev Time 0.00
Received By rmcdouga Date 2006-04-11 Time 07:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-07 Cont ID  
Sent By rmcdouga Date 2006-04-07 Time 10:20 Rev Time 0.00
Received By rmcdouga Date 2006-04-07 Time 10:20 Sent To  
Notes
2006-04-07 00:00:00DENIED
  
 1) SUBMIT PROJECT SPECIFICATIONS AND
 MATERIAL TAKE OFF TO VERIFY FLAME
 SPREAD, FIRE RESISTANCE AND ENERGY CODE
 COMPLIANCE. 2004 FBC(EXISTING BUILDINGS)
 SECTIONS 501, 503 AND 504.
  
 2) SPECIFY THE REQUIRED FIRE RESISTANCE
 RATING FOR THE TENANT SEPARATION WALLS
 AND THE APPROVED ASSEMBLY NUMBER. SEE
 FBC 708.
  
 3) SPECIFY THE TYPE AND R-VALUES OF THE
 INSULATION AND INDICATE WHERE EACH WILL
 BE INSTALLED. INDICATE IF ROOF/CEILING
 ASSEMBLY HAS AN ATTIC OR IS SINGLE
 ASSEMBLY. SEE FBC CHAPTER 13.
  
 4) SPECIFY THE FLAME SPREAD CLASS FOR
 THE INTERIOR FINISHES. SEE FBC 803.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2006-03-28 Cont ID  
Sent By btrobaug Date 2006-03-28 Time 15:39 Rev Time 0.33
Received By btrobaug Date 2006-03-28 Time 15:35 Sent To  
Notes
2006-03-28 00:00:00 
 NO ELECTRICAL WORK TO BE DONE ON THIS
 PERMIT PER CONVERSATION WITH HAYDEN OF
 BUILT RIGHT CONSTRUCTION./WRT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2006-04-05 Cont ID  
Sent By mwennerg Date 2006-04-05 Time 10:30 Rev Time 0.00
Received By mwennerg Date 2006-04-05 Time 10:30 Sent To  
Notes
2006-04-05 00:00:00DRYWALL REMOVAL, REINSTALLATION AND
 FINISH ONLY.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-07 Cont ID  
Sent By rmcdouga Date 2006-04-07 Time 10:30 Rev Time 0.00
Received By rmcdouga Date 2006-03-27 Time 16:32 Sent To  
Notes
2006-03-27 00:00:00TO "BOB" #4-OK TO PUT ON "BOB" PER
 "RBROWN"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-03-30 Cont ID  
Sent By tgordon Date 2006-03-30 Time 14:12 Rev Time 0.15
Received By tgordon Date 2006-03-30 Time 14:12 Sent To  
Notes
2006-03-30 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-04-03 Cont ID  
Sent By jleech Date 2006-04-03 Time 12:38 Rev Time 0.00
Received By jleech Date 2006-04-03 Time 12:38 Sent To  
Notes
2006-04-03 00:00:00NO PLUMBING WORK DESRIBED.