Plan Review Details - Permit 06031133
Plan Review Stops For Permit 06031133
Review Stop G GAS REVIEW
Rev No 5 Status P Date 2006-09-12 Cont ID  
Sent By mperson Date 2006-09-12 Time 15:33 Rev Time 0.33
Received By mperson Date 2006-09-12 Time 15:33 Sent To PC
Notes
2006-09-12 00:00:00REVISION: DELETE EXISTING UNDERGROUND
 GALVANIZED AND REPLACE WITH NEW PE.

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2006-08-24 Cont ID  
Sent By mperson Date 2006-08-24 Time 14:44 Rev Time 0.33
Received By mperson Date 2006-08-24 Time 14:44 Sent To PC
Notes
2006-08-24 00:00:00******REVISION DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW FOR THE SUBMITTED
 REVISION:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (NOTE: PLEASE INCLUDE
 ABOVE GROUND PIPE MEASUREMENTS AS WELL
 AS THE UNDERGROUND PIPE MEASUREMENTS ON
 THE REVISION.)
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 (NOTE: PLEASE INCLUDE ABOVE GROUND PIPE
 MATERIAL AS WELL AS UNDERGROUND PIPE
 MATERIAL ON THE REVISION.)
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING (ISOMETRIC) SHALL CLEARLY
 PRINT AND SIGN NAME, AND ALSO DATE
 DRAWING. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 5. PER FBC-2004, CHAPTER 1, SECTION
 106.1 SUBMITTAL DOCUMENTS. IF THE DESIGN
 PROFESSIONAL IS AN ARCHITECT LEGALLY
 REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE
 AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART 1, FLORIDA STATUTES, THEN
 HE OR SHE SHALL AFFIX HIS OR HER SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA, AS
 REQUIRED BY FLORIDA STATUTES.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-07-05 Cont ID  
Sent By mperson Date 2006-07-05 Time 11:34 Rev Time 0.45
Received By mperson Date 2006-07-05 Time 11:34 Sent To PC
Notes
2006-07-05 00:00:00REVISION: CHANGED PIPING FROM ABOVE
 GROUND GALVANIZED TO UNDERGROUND PE.
 CHANGED WATER HEATER REMOVAL LOCATIONS.
 CHANGED ONE WATER HEATER MODEL NUMBER.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-04-03 Cont ID  
Sent By mperson Date 2006-04-03 Time 15:13 Rev Time 0.33
Received By mperson Date 2006-04-03 Time 15:13 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-03-27 Cont ID  
Sent By adarroug Date 2006-03-29 Time 14:44 Rev Time 0.45
Received By mperson Date 2006-03-27 Time 15:27 Sent To PC
Notes
2006-03-27 00:00:00****DENIED****
 REFERENCE FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR A GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: GALVANIZED PIPE UNDERGROUND NOT
 ALLOWED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004. NOTE: NEED MANUFACTURE CUT
 SHEETS ON REGULATERS.
 9. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 FUEL GAS CODE SEC 402.2
 10. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 17:44 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 17:44 Sent To P
Notes
2006-09-08 00:00:00TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-22 Cont ID  
Sent By adarroug Date 2006-08-22 Time 16:28 Rev Time 0.00
Received By adarroug Date 2006-08-22 Time 16:28 Sent To P
Notes
2006-08-22 00:00:00TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-30 Cont ID  
Sent By adarroug Date 2006-06-30 Time 09:51 Rev Time 0.00
Received By adarroug Date 2006-06-30 Time 09:51 Sent To P
Notes
2006-06-30 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-29 Cont ID  
Sent By adarroug Date 2006-03-29 Time 14:42 Rev Time 0.00
Received By adarroug Date 2006-03-29 Time 14:42 Sent To G
Notes
2006-03-29 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-29 Cont ID  
Sent By adarroug Date 2006-03-27 Time 14:43 Rev Time 0.00
Received By adarroug Date 2006-03-24 Time 17:42 Sent To G
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved