Plan Review Details - Permit 06031034
Plan Review Stops For Permit 06031034
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-08 Cont ID  
Sent By rmcdouga Date 2006-05-08 Time 07:54 Rev Time 0.00
Received By rmcdouga Date 2006-05-08 Time 07:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-22 Cont ID  
Sent By rmcdouga Date 2006-03-22 Time 13:37 Rev Time 0.00
Received By rmcdouga Date 2006-03-22 Time 13:37 Sent To  
Notes
2006-03-22 00:00:00DENIED
  
 1) THE DESIGN PRESSURE FOR THE POLYGLASS
 MODIFIED BITUMEN SYSTEM IS TOO LOW AND
 REQUIRES ENHANCED FASTENING. LIMITATION
 NUMBER 7 ON PAGE 45 OF THE NOA REQUIRES
 THAT THESE CALCULATIONS ARE DONE BY AN
 ENGINEER OR ARCHITECT. SUBMIT SIGNED AND
 SEALED CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  